Camsco W Series: parameters of W-2 stage transfer switch
Camsco
Camsco's W-2 two-stage member of the W series dual-power automatic transfer switches: 13 current steps from 20 to 500 A, AC 400 V rated voltage, 800 V isolation and 8 kV impulse withstand.
On this page
Overview
Camsco's product page introduces the W series dual-power automatic transfer switches, which belong to the PC class. There are two types: the W-2 two-stage and the WN3 three-stage switch. On a switching signal the W-2 transfers power immediately from one source to the other without stopping at an OFF position; its rated current is 20 A to 500 A.
The WN3 can transfer immediately, after a preset delay, or stop at the middle OFF position after the signal. This matters for designs where loads with residual voltage, such as motors, need a pause between sources. The WN3 covers a wide rated-current range, 20 A to 5000 A.
The W-2 parameter table gives isolation voltage AC 800 V, impulse withstand 8 kV, rated voltage AC 400 V (AC 660/690 V and DC 125/250 V in brackets), dual throw, and 2, 3 or 4 poles. Rated current steps are 20, 40, 63, 80, 100, 125, 160, 200, 225, 250, 350, 400 and 500 A.
The WN3 table gives the same isolation and impulse values, AC 400 V rated voltage and 2/3/4 pole options, with current ranges grouped from 20-63 A up to 5000 A. The page shows an 'out of stock, contact us' note and carries no certification or local-suitability information.
Key points
- W-2: two-stage, immediate transfer with no OFF position in between.
- W-2 rated current 20-500 A in 13 steps: 20, 40, 63, 80, 100, 125, 160, 200, 225, 250, 350, 400, 500 A.
- Rated voltage AC 400 V (AC 660/690 V and DC 125/250 V options noted).
- Isolation voltage AC 800 V, impulse withstand 8 kV.
- Poles 2P, 3P or 4P; dual throw.
- WN3: three-stage, delayed transfer or stop at OFF; 20-5000 A.
- W-2 20 A model: rated current 20 A, rated voltage 400 V.
Using it in design
- Select the transfer switch current against load current and short-circuit coordination; W-2 steps are discrete, with no intermediate values.
- For motor or transformer loads, assess the WN3 OFF position and delayed transfer against residual-voltage issues.
- Decide the 4-pole option together with neutral-switching requirements in TN-S systems.
- Verify page data separately against local certification and supply status.
Who should read it
Electrical designers selecting automatic source transfer and panel builders.
Document contents
- Introduction to the W series
- W-2 two-stage switch parameters
- W-N3 three-stage switch parameters
Publication details
- Authors
- Camsco
- Publisher
- Camsco
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Camsco Camsco W Series: parameters of W-2 stage transfer switch. Camsco. https://www.camsco.com.tw/automatic-transfer-switch/W-series-dual-power-automatic-transfer-switches.html
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.