A C&S Electric product flyer for the CATS series of 4-pole automatic transfer switches (ATS), giving rated currents from 40 A to 3200 A, short-circuit withstand, programmable thresholds and dimensions.

On this page

Overview

The flyer presents the CATS family, which transfers load quickly and smoothly during a power outage or disturbance. Time delays keep the source stable during switching. The application list covers airports and railways, commercial buildings, automotive, data centres and telecommunications, oil and gas, manufacturing, healthcare, and banking.

The electrical table has seven current groups: 40/63/80 A, 100/125 A, 160/200/250 A, 315/400/630 A, 800 A, 1000-1600 A and 2000-3200 A. All are 4-pole, 415 V operating voltage, 690 V insulation voltage, utilization category AC-32B and IEC 60947-6-1. Short-time withstand Icw (0.1/1 s) rises from 7/5 kA to 75/50 kA. Operating cycles are 10000 for small ratings and 5000 for large ones.

The programmable logic covers undervoltage and overvoltage (160-210 V and 240-285 V), under- and over-frequency (40-48 Hz and 50-60 Hz), phase sequence and overload (with external CT) for both sources. Timers range 0-300 s for recovery and transfer, 0-60 s for generator start and 0-900 s for generator stop. Mode selection is auto, manual or remote, with position order I-OFF-II.

General conditions are -20 to 55 C ambient, humidity not above 50 percent at 40 C and altitude not above 2000 m. The values are product-specific and do not establish local certification, stock or site suitability.

Key points

  1. The CATS 40 A, 4-pole, has a rated current of 40 A and a rated operating voltage of 415 V.
  2. Current groups: 40/63/80, 100/125, 160/200/250, 315/400/630, 800, 1000-1600 and 2000-3200 A.
  3. Insulation voltage is 690 V in the power circuit and 500 V in the control circuit; impulse withstand is 8 kV (up to 250 A) and 12 kV (315 A and above).
  4. Icw (0.1/1 s): 7/5, 9/5, 25/12, 50/25, 50/25, 65/50 and 75/50 kA; limiting short-circuit current Iq is 120 kA.
  5. Operating cycles: 10000, 10000, 8000, 6000, 5000, 5000, 5000.
  6. Timers: recovery and transfer 0-300 s, generator start 0-60 s, generator stop 0-900 s.
  7. Operating conditions: -20 to 55 C, up to 2000 m; EMC Class B.
  8. Dimension and weight examples: 226 x 108 x 195 mm and 4 kg (smallest) up to 665 x 350 x 400 mm and 60 kg (largest column).

Using it in design

  • Select the ATS rating against load current and discrete values; for range columns (1000-1600, 2000-3200 A) obtain the exact model code from the manufacturer.
  • Compare Icw and Icm with the available short-circuit level, and check the 2000 m altitude and -20/55 C conditions.
  • Program voltage, frequency and phase-sequence thresholds to the generator and mains characteristics, and combine recovery and transfer delays with selectivity and generator warm-up time.
  • Check that utilization category AC-32B suits the load type.
  • Confirm local certification and stock separately; the flyer does not establish them.

Who should read it

Electrical designers selecting ATS equipment and engineers preparing generator transfer schemes.

Document contents

  1. Features and applications
  2. Technical characteristics
  3. Electrical characteristics
  4. Program configuration
  5. General and electromagnetic characteristics
  6. Mechanical characteristics

Publication details

Authors
C&S Electric
Publisher
C&S Electric
Year
2023
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

C&S Electric (2023). C&S Electric ATS Flyer 2023, pp.1,3-4. C&S Electric. https://cselectric.co.in/wp-content/uploads/2023/07/ATS-Flyer-2023.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.