Technical guideFree to readYear not stated

Elmeasure Automatic Transfer Switch ATeS brochure, pp.1-2

Elmeasure

Elmeasure's ATeS brochure gives current, short-circuit and setting data for a 4-pole, 415 V, 63-1600 A family of automatic transfer switches to IEC 60947-6-1, utilization category AC-33B.

On this page

Overview

Elmeasure's two-page brochure presents the ATeS (Automatic Transfer Switch) series as a mains-to-generator transfer switch with automatic generator start and stop. The models shown are ATeS2-125A, ATeS2-250A and a 160 A 4-pole version; the family is split into four frame groups of 63-125, 160-250, 315-630 and 800-1600 A. All are 4-pole, rated operating voltage 415 V, utilization category AC-33B, standard IEC 60947-6-1.

The technical table gives ratings per group: rated short-time withstand current Icw (0.1/1 s) of 9/5, 12/25, 50/25 and 25/50 kA; making capacity Icm of 8, 17, 26 and 55 kA; limiting short-circuit current Iq of 120 kA; and an operating life of 10000, 8000, 6000 and 5000 cycles. Power-circuit insulation voltage is 690 V with 8 kV impulse withstand, the control circuit is 500 V and 4 kV, and the control supply is 230 V/50 Hz.

Functionally, each source has under/over-voltage and under/over-frequency protection, single-phase-missing detection and optional inverse-curve overload tripping. Recovery, transfer, generator start and generator stop delays are adjustable from 3 to 600 s; selection modes are Auto, Manual, Remote and RS485, and the position order is I-OFF-II. A fire-alarm or external-fault trip input, a 3-position lock and manual emergency operation are also listed.

The brochure is product literature and says nothing about local certification, stock or suitability for a particular site. The voltage thresholds and delays are factory setting ranges, so short-circuit coordination and load current still need separate verification during design. Data centres and telecommunications are among the listed applications.

Key points

  1. Four frame groups: 63-125, 160-250, 315-630 and 800-1600 A; all 4-pole, 415 V rated operating voltage, AC-33B, IEC 60947-6-1.
  2. Icw (0.1/1 s) is 9/5, 12/25, 50/25 and 25/50 kA; Icm is 8, 17, 26 and 55 kA; Iq is 120 kA.
  3. Operating life is 10000, 8000, 6000 and 5000 cycles by group.
  4. Weight is 5, 10, 20 and 60 kg; outline sizes are 245x115x125, 373x175x200, 435x260x245 and 635x340x320 mm.
  5. Power-circuit insulation voltage is 690 V with 8 kV impulse withstand; control supply is 230 V/50 Hz.
  6. Primary-source settings: under-voltage 160-200 V, over-voltage 240-290 V, under-frequency 40-48 Hz, over-frequency 50-60 Hz; secondary-source under-voltage is 150-200 V.
  7. Recovery, transfer, generator start and generator stop delays are adjustable from 3 to 600 s.
  8. Ambient range is -20 to 55 C, humidity at most 50% at 40 C, and altitude up to 2000 m.

Using it in design

  • Select the ATS current class from load current; with discrete frame groups (125, 250, 630, 1600 A) a step up to the next group may be needed.
  • Compare the expected short-circuit current at the installation point with Icw and Icm; the 1 s withstand values differ between groups.
  • Set generator start and stop delays (3-600 s) against generator warm-up time and UPS battery autonomy.
  • Choose the voltage and frequency thresholds to match the load and the UPS input tolerance.
  • Check the ambient, humidity and altitude limits (-20 to 55 C, 2000 m) against the electrical-room conditions.

Who should read it

Electrical engineers designing mains-to-generator changeover and teams writing ATS specifications.

Document contents

  1. ATeS models
  2. Mechanical specification and dimensions
  3. Features, benefits and applications
  4. Technical specification

Publication details

Authors
Elmeasure
Publisher
Elmeasure
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Elmeasure Elmeasure Automatic Transfer Switch ATeS brochure, pp.1-2. Elmeasure. https://corp.vashiisl.com/wp-content/datasheet/Elmeasure/ATS.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.