EPI STS Series 50-1250 A, catalogue pp.84-85 (PDF pp.1-2)

Original title EPI STS Series 50–1250 A, catalogue pp.84–85 (PDF pp.1–2)

EPI UPS

A catalogue extract from EPI UPS presenting its 50 to 1250 A static transfer switch (STS) series: operating principle, protections and a technical table for 3-pole and 4-pole models.

On this page

Overview

The catalogue explains that an STS moves load instantly between two independent sources and that, when one fails, the switch to the backup is so fast the load does not notice. Transfer is automatic when a source leaves tolerance, or manual by an operator from the front panel or remotely. Transfer is instantaneous if the sources are in phase.

Protection falls under two headings. For overloads and load faults the user can choose the level at which internal protection acts. On an output short circuit the STS blocks transfer between the two sources so the fault does not propagate to other loads; a back-feed control circuit triggers protection devices that stop energy feeding back to an input. Microprocessor control monitors SCR operation continuously and offers remote diagnostics over RS232 and TCP/IP.

The technical table gives 11 current ratings: 50, 100, 150, 200, 250, 300, 400, 600, 800, 1000 and 1250 A, each as a 3-pole (3-P) and 4-pole (4-P) version. Input voltage is 380/400/415 V AC, 3 phase + N + earth; frequency 50/60 Hz with an adjustable 48-65 Hz range; transfer type is break before make. Transfer time is below 4 ms for synchronous sources and below 10 ms for non-synchronous ones.

Some rows in the table (noise, dimensions and weight for the largest models) are left open, so those models need manufacturer confirmation. The source documents discrete current ratings and product-specific configuration limits; it does not establish local certification, stock or site suitability.

Key points

  1. Model 3-P50A has a rated current of 50 A and an input voltage of 380/400/415 V AC (3 phase + N + earth).
  2. Ratings: 50, 100, 150, 200, 250, 300, 400, 600, 800, 1000, 1250 A; 3-pole and 4-pole versions.
  3. Input voltage tolerance is 180-264 V AC (phase-neutral); frequency range 48-65 Hz with adjustable limits.
  4. Full-load efficiency is above 99 percent; input voltage THD below 10 percent; crest factor 3:1.
  5. Transfer time is below 4 ms for synchronous and below 10 ms for non-synchronous sources; type is break before make.
  6. Overload: 0-100 percent continuous, 101-150 percent for 1 min, 151-200 percent for 10 s, above 300 percent for 250 ms.
  7. Protections: output overload, short circuit, over temperature, back-feed and SCR fault.
  8. RS232 standard, RS485 and TCP/IP optional, 5 programmable relay outputs.
  9. Operation at 0-40 C, humidity below 90 percent (non-condensing), forced cooling with redundant fans; EN62310-1 and -2.

Using it in design

  • Select the STS rating from the discrete values and choose 3-pole or 4-pole (neutral switching) to suit the earthing and neutral scheme.
  • Compare the 4 ms (synchronous) and 10 ms (non-synchronous) transfer times with the load power supplies' hold-up time.
  • Assess the overload curve alongside the load profile and downstream protection selectivity.
  • For the largest models, obtain noise, dimension and weight data from the manufacturer; do not fill open rows with assumptions.
  • Confirm local certification and stock separately.

Who should read it

Electrical designers and tender engineers selecting STS equipment for dual-fed loads.

Document contents

  1. Operating principle
  2. Protection against environmental disturbances
  3. Total microprocessor control
  4. Protection against power supply faults
  5. Accessibility
  6. Technical data table

Publication details

Authors
EPI UPS
Publisher
EPI UPS
Year
2023
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

EPI UPS (2023). EPI STS Series 50–1250 A, catalogue pp.84–85 (PDF pp.1–2). EPI UPS. https://epi-ups.com/wp-content/uploads/2022/05/STS-Series.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.