Technical guideFree to readYear not stated

EverExceed Static Transfer Switch: Technical Data

EverExceed

EverExceed's SCR-based STS lists single-phase 16-125 A (3.5-27.5 kVA) and three-phase 63 A (45 kVA) columns, with switching time of 4 ms or less (single phase) and 8 ms or less (three phase).

On this page

Overview

EverExceed's product page describes the STS as a thyristor-module (SCR) device that switches between two input power supplies without interruption, used in computer rooms, internet data centres, telecommunications, financial data centres and industrial process control centres. Its technical features include 32-bit DSP fully digital control, a dual AC power switch, fast power-failure detection, an LED and LCD monitor and an independent RS485 communication interface.

The specification table gives ten current columns: 16 A (3.5 kVA), 25 A (6.2 kVA), 32 A (7.7 kVA), 40 A (10 kVA), 45 A (11 kVA), 63 A (15 kVA), 80 A (19 kVA), 100 A (24 kVA), 125 A (27.5 kVA) and 63 A (45 kVA). The table separates single-phase and three-phase columns. Single-phase input is 220 Vac (customizable) with a 190-260 Vac input range; three-phase is 320-440 Vac. Automatic switching thresholds are 220 Vac +/-15% and 380 Vac +/-12.5%.

Switching parameters: priority switching is 4 ms or less single phase and 8 ms or less three phase; the switching element is contactless SCR; the mode is break before make; the condition is power failure, overvoltage or undervoltage. Frequency is 50 Hz +/-10%. Overload: load current up to 110% is continuous and above 110% shuts down immediately; another column gives continuous operation below 105% and shutdown after 60 ms above 105%. Protection covers under- and over-voltage, overload, over-temperature and short circuit.

Environmental and physical data: insulation strength is 2000 Vac/10 mA/60 s, humidity 0-90% non-condensing, operating temperature -10 to 50 C, storage -40 to 70 C and noise below 55 dB at 1 m. Dimensions are 490x343x44 mm (1U), 490x338x88 mm (2U) and 490x412x132 mm (3U); the page does not say which current column corresponds to which height. The same page also presents unrelated products such as a DK series ATS cabinet, a DT series low-voltage switchgear cabinet and a UPS distribution cabinet; these are not part of the STS data.

Key points

  1. Ten current columns: 16, 25, 32, 40, 45, 63, 80, 100, 125 A and a three-phase 63 A; capacity 3.5 to 45 kVA (3.5, 6.2, 7.7, 10, 11, 15, 19, 24, 27.5, 45 kVA).
  2. Single-phase input is 220 Vac (customizable), range 190-260 Vac; three-phase range is 320-440 Vac; frequency 50 Hz +/-10%.
  3. Priority switching time is 4 ms or less single phase and 8 ms or less three phase; contactless SCR; break before make.
  4. Switching threshold is 220 Vac +/-15% and 380 Vac +/-12.5%; hysteresis error +/-5 V.
  5. Overload: continuous below 110% and immediate shutdown above; another column shuts down after 60 ms above 105%.
  6. Operation -10 to 50 C, storage -40 to 70 C, humidity 0-90% non-condensing, noise below 55 dB (1 m); insulation strength 2000 Vac/60 s.
  7. Dimensions: 490x343x44 mm (1U), 490x338x88 mm (2U), 490x412x132 mm (3U).
  8. Communication is RS485; optional LCD (voltage, frequency, current, load percentage).

Using it in design

  • Select load current from the 16-125 A single-phase columns and, for three-phase loads, consider only the listed 63 A/45 kVA column; larger currents need another product.
  • Compare transfer time with load tolerance: 4 ms or less single phase and 8 ms or less three phase; being break-before-make, there is a very short gap on transfer.
  • Choose the input voltage range (190-260 V single phase, 320-440 V three phase) and switching thresholds to suit the sources' voltage tolerance.
  • Check overload behaviour (immediate shutdown above 110%) against load inrush and design the backup path after shutdown.
  • Reserve 1U, 2U or 3U height in the rack elevation, and request a drawing from the manufacturer for the model-to-height mapping.

Who should read it

Electrical engineers designing dual-feed supplies for data rooms and telecom loads, and teams writing STS specifications.

Document contents

  1. Technical features
  2. Applications
  3. Specification table (input, switching, environment)

Publication details

Authors
EverExceed
Publisher
EverExceed
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

EverExceed EverExceed Static Transfer Switch: Technical Data. EverExceed. https://www.everexceed.com/static-transfer-switch_p474.html

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.