GRL DNQ8 Automatic Transfer Switch: Current Parameters and Main Technical Parameters
Original title GRL DNQ8 automatic transfer switch: Current Parameters and Main Technical Parameters
GRL
The GRL DNQ8 automatic transfer switch (ATS) series covers 16-3200 A at AC 400 V, 50 Hz to IEC 60947-6-1, with a 0.7 s or 1.8 s transfer time and use categories AC33B/AC33iB.
On this page
Overview
The page is the product introduction for the GRL DNQ8 automatic transfer switch series. The device physically separates two sources, such as a utility and a generator, and is described as an ATS type used in data-centre structures with several sources including grid, generators and UPSs. The control section has a metal casing, the switch body is glass-fibre unsaturated polyester resin, rated voltage is AC 400 V at 50 Hz, control is 220 V and rated current is 16-3200 A.
The main parameters table lists agreed heating current (20 values from 16 to 3200 A), rated insulation voltage (500, 690, 800 V), rated impulse withstand voltage (6, 8, 12 kV), rated short-time withstand current Icw (5, 8, 12.5 and 32 kA for 0.5 s), use categories AC33B and AC33iB, transfer time (0.7 s or 1.8 s), mechanical life (8000, 6000, 3000, 2000 operations) and electrical life (3000, 2500, 1500, 1000). Four-pole weight ranges from 3.4 kg to 68 kg. The current parameters section counts 27 current steps in three-pole and four-pole (switched neutral) versions.
The product uses a dual-power, horizontal-pulling mechanism with micro-motor pre-storage aimed at zero arcing; mechanical and electrical interlocking, an independent load isolation switch, position indication and padlocking are listed. Type I is a basic fully automatic mains-to-mains unit; Type II offers forced switching options for generator and fire-fighting use. Operating environment is up to 2000 m altitude, -5 to +40 °C and up to 95% relative humidity. Standards are IEC 60947-1, -3 and -6 and the GB/T 14048 series.
Key points
- Rated voltage AC 400 V (50 Hz), control motor AC 220 V; rated current 16-3200 A, 3-pole and 4-pole (switched neutral).
- Use categories AC33B and AC33iB; transfer time I-II or II-I of 0.7 s or 1.8 s.
- Rated insulation voltage 500/690/800 V; impulse withstand 6/8/12 kV.
- Short-time withstand current Icw (0.5 s) steps: 5, 8, 12.5 and 32 kA.
- Mechanical life 8000, 6000, 3000 and 2000 operations; electrical life 3000, 2500, 1500 and 1000 (by frame).
- Four-pole weight is 3.4 kg to 68 kg; 27 current steps are offered.
- Operating conditions: up to 2000 m, -5 to +40 °C, relative humidity up to 95%.
- Standards: IEC 60947-1, IEC 60947-3, IEC 60947-6; GB/T 14048.1 and related GB parts.
Using it in design
- Select the ATS from load current together with rated voltage, rated current and pole count (4-pole where neutral switching is needed), as the page's selection example does.
- Compare Icw with the expected short-circuit current at the installation point and the upstream protection clearing time.
- Weigh the 0.7 s or 1.8 s transfer time against critical-load outage tolerance and generator changeover sequence.
- Check whether the UPS covers the transfer interruption, depending on whether the ATS sits at the UPS input or on the bypass line.
Who should read it
Electrical designers selecting generator-utility changeover equipment and panel builders.
Document contents
- Automatic Transfer Switch Product Overview
- Application
- Example of Model Selection
- Standards
- Main Technical Parameters
- Performance and Characteristics
- Operating Environment
- Current Parameters
- Introduction to Model Selection
Publication details
- Authors
- GRL
- Publisher
- GRL
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
GRL GRL DNQ8 automatic transfer switch: Current Parameters and Main Technical Parameters. GRL. https://grlgroup.com/automatic-transfer-switch-dnq8
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.