LSP Automatic Transfer Switch Equipment Catalogue, p.55 (G3M100-220/4)
Original title LSP Automatic Transfer Switch Equipment catalogue, p.55
LSP
LSP's ATSE catalogue covers PC-class automatic transfer switches from 6 to 630 A in seven series; the model on p.55, G3M100-220/4, is a 100 A, 4-pole, three-position switch with fire-fighting interlock.
On this page
Overview
LSP's Automatic Transfer Switch Equipment (ATSE) catalogue gathers dual-supply transfer switches of PC class (able to be switched on and loaded without generating short-circuit current) that comply with IEC 60947-6-1. There are seven series: L2R, L2S and L2H (6 to 63 A, 2 and 4 pole), M2R (6 to 100 A, DIN-rail residential type), N2M (80 to 630 A), S3M (125 to 630 A) and G3M (100 to 630 A). The supplies are defined as A (main) and B (standby).
Transfer times vary by series: 100 ms for L2R and M2R, 20 ms for L2H, 900 ms for N2M, at most 200 ms for S3M and 3 s for G3M. The S3M and G3M series offer three-phase sampling, three-position (A-0-B) transfer and a firefighting interlock. N2M targets critical applications such as fire protection, telecom and healthcare and needs no additional control power at 220 V. The F and T add-ons provide generator start/stop and an external communication interface.
For G3M100-220/4 on page 55 the values are: rated voltage 400 V (phase-to-phase) and 230 V (phase-to-neutral), case grade 100 A, 4 poles, usage category AC-33B, short-time withstand 5 kA / 30 ms, short-circuit making capacity 8 kA, automatic transfer time (A to B) 3 s, load disconnect time 1.3 s, mechanical life 10,000 and electrical life 1,500 operations, maximum 60 operations per hour, IP20 and under/over-voltage thresholds of 165/270 V. The document is a product catalogue and gives no selection method.
Key points
- Seven series: L2R, L2S, L2H (6 to 63 A), M2R (6 to 100 A), N2M (80 to 630 A), S3M (125 to 630 A), G3M (100 to 630 A); IEC 60947-6-1, PC class.
- Automatic transfer time: L2R/M2R up to 100 ms; L2H 20 ms; S3M up to 200 ms; N2M up to 900 ms; G3M 3 s.
- M2R: DIN-rail, 40/63/100 A, 110 V, conditional short-circuit Iq 50 kA, mechanical life ≥5,000, electrical life ≥2,000.
- N2M125 (3 and 4 pole): 80/125 A, Icw 10 kA, transfer ≤900 ms, mechanical life 20,000, electrical life 6,000.
- S3M125: 125 A, 4 pole, AC-33iB, transfer ≤200 ms, 60 operations per hour, firefighting interlock, three-position (A-0-B).
- G3M100 (p.55): 100 A, 4 pole, transfer 3 s, load disconnect 1.3 s, Icw 5 kA/30 ms, Icm 8 kA, mechanical 10,000, electrical 1,500.
- F add-on: mains to generator, generator start output (3 A / 230 V AC), 5 s stop delay; T add-on communication.
- Return transfer delay (B to A) adjustable 0 to 30 s (N2M and S3M).
Using it in design
- For data-centre mains-generator transfer, choose series with 200 to 900 ms transfer such as N2M or S3M; UPS battery backup must bridge that gap.
- Use 3 s series such as G3M only for auxiliary loads that tolerate an interruption.
- Verify switch current against load current and short-circuit ratings (Icw, Icm) against the expected fault current; a short-circuit protective device is still required.
- For generator control, use the F (mains to generator) add-on and set the return transfer delay (0 to 30 s) to avoid load flapping.
- Where a fire-fighting interlock is required, specify the S3M and G3M series.
Who should read it
Electrical engineers designing generator-mains transfer and dual-source distribution.
Document contents
- ATSE L2R series
- ATSE L2S series
- ATSE L2H series
- ATSE M2R series
- ATSE N2M series
- ATSE S3M series
- ATSE G3M series
Publication details
- Authors
- LSP
- Publisher
- LSP
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
LSP LSP Automatic Transfer Switch Equipment catalogue, p.55. LSP. https://www.lsprotec.com/downloads/lsp-automatic-transfer-switch-catalogue.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.