Shihlin XSTNA PC-class ATS: type designation and technical specifications

Shihlin Electric

Shihlin's XSTNA-125H/250H/630H is a three-position PC-class automatic transfer switch for AC 400 V, 16-630 A, 3P/4P, with Iq 120 kA, Uimp 8 kV, B and D controllers and mains-mains or mains-generator modes.

On this page

Overview

Shihlin Electric's XSTNA-125/250/630 series is a PC-class, three-position dual power automatic transfer switching equipment for emergency power systems with AC 50/60 Hz, rated voltage 400 V and operating current of 16-630 A. When one source becomes abnormal, the load is transferred automatically to the other. Applications are hospitals, shopping malls, chemical plants, metallurgy, buildings and fire protection systems. The structure uses three working positions (I-ON, II-ON, 0-OFF).

The type designation defines frame size (125/250/630), structure (H), poles (3P/4P), controller type (B/D), rated current, power supply mode (blank: mains-mains, F: mains-generator) and transfer mode (blank: automatic transfer with automatic return, S: no automatic return, D controller only). Power supply and transfer mode are factory-set and cannot be changed by the customer. Current steps: 125 frame 16-125 A (10 steps), 250 frame 125-250 A, 630 frame 315-630 A.

In the technical table, insulation voltage Ui is 800 V (125), 1000 V (250) and 690 V (630); impulse withstand voltage Uimp is 8 kV; rated voltage 400 V 50 Hz; Icm 17 kA (125 and 250) and 26 kA (630); limited short-circuit current Iq 120 kA. Transfer times of 0.56-2.0 s (±20%) are given. The B controller gives basic functions without voltage sensing; the D controller adds 40-300 V measurement, adjustable under/over voltage (defaults 176/264 V), frequency (40-60 Hz), 0-180 s transfer and recovery delays, engine exerciser timer, generator dry contact, forced 0-OFF position for fire linkage, RS485, remote operation and an LCD. The CE declaration of conformity covers only XSTNA-125H and 250H.

Key points

  1. Series: XSTNA-125H, 250H, 630H; AC 400 V, 50/60 Hz; 16-630 A; 3P and 4P.
  2. Current steps: 125 frame 16, 20, 25, 32, 40, 50, 63, 80, 100, 125 A; 250 frame 125, 160, 200, 225, 250 A; 630 frame 315, 350, 400, 500, 630 A.
  3. Ui 800 V (125), 1000 V (250), 690 V (630); Uimp 8 kV.
  4. Icm 17 kA (125 and 250), 26 kA (630); limited short-circuit current Iq 120 kA.
  5. Transfer times of 0.56-2.0 s (±20%).
  6. Power supply mode: mains-mains or mains-generator (F); S suffix for transfer without automatic return (D only).
  7. D controller: DC 24 V auxiliary supply, 40-300 V measurement, default under-voltage 176 V and over-voltage 264 V, 0-180 s delays, RS485, generator dry contact, fire-linked forced 0-OFF.
  8. B controller: no auxiliary supply, LED indicator, automatic transfer and automatic recovery.
  9. CE declaration covers XSTNA-125H and 250H; 630H is not listed in it.

Using it in design

  • Select frame and rated current by load current; compare the short-circuit level with Icm and Iq (120 kA) and check upstream protection coordination.
  • For generator applications, specify the F code (mains-generator) and the D controller (generator dry contact, engine exerciser, adjustable delays); settle at order stage that power supply and transfer mode are factory-set.
  • Compare the transfer time (0.56-2.0 s) with load tolerance; loads that cannot tolerate a brief interruption need the ATS used together with a UPS.
  • Choose the D controller for fire linkage and RS485 monitoring requirements.
  • Confirm the CE document scope for the 630H with the supplier.

Who should read it

Electrical designers selecting ATS for data centre auxiliary services and hospital and building emergency power systems.

Document contents

  1. Product information and key benefits
  2. Type designation
  3. Technical specifications
  4. Controller functions (B and D)
  5. Files and related products

Publication details

Authors
Shihlin Electric
Publisher
Shihlin Electric
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Shihlin Electric Shihlin XSTNA PC-class ATS: type designation and technical specifications. Shihlin Electric. https://global.seec.com.tw/en/product/6005.html

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.