EPI UPS product catalogue, TCA technical table, printed pp.20-21

Original title EPI UPS product catalogue, TCA technical table, printed pp.20–21

EPI UPS

EPI UPS's TCA series: 10-40 kVA three-phase rack UPS at unity output power factor, efficiency of 96% or more, THDi under 3%, and 30 kW in 2U, with external batteries.

On this page

Overview

In EPI UPS's 2025 catalogue the TCA series is presented as a 10-40 kVA three-phase rack or tower double-conversion on-line UPS. The rest of the catalogue covers the Lite, MTN, MHP, XR+, Xtreme, HM, HT and TG+ series, the modular RMD series, ATS, n-STS and STS products, inverters, AVRs and rectifiers; this summary rests only on the TCA table (pp.20-21). There are five models: TCA010LR, 015LR, 020LR, 030LR and 040LR, that is 10 kVA/10 kW, 15 kVA/15 kW, 20 kVA/20 kW, 30 kVA/30 kW and 40 kVA/40 kW.

Input is 3P5W (3P+N+PE), 380/400/415 VAC line-to-line, 220/230/240 VAC line-to-neutral, 50/60 Hz; input power factor is above 0.99 and current distortion is THDi under 3% at 100% linear load. The input voltage range is 304-478 VAC (line-to-line) at full load, with derating from 100% to 75% below 304 V, and the frequency range is 40-70 Hz. The bypass range is settable from -40% to +25% (default -20% to +15%) with a selectable frequency window of +/-1, +/-3 or +/-5 Hz.

At the inverter output, power factor is 1, voltage accuracy +/-1%, load response under 5% (20%-80%-20% step), recovery time under 20 ms (0%-100%-0%), THDu 1% on linear load and under 5% on non-linear load (IEC 62040-3), and crest factor 3:1. Overload capability is 110% for 1 hour, 125% for 10 minutes, 150% for 1 minute and 200 ms above 150%. Efficiency is given as 96% or more in normal mode and battery mode; this is a lower-bound claim, not a load curve.

Battery voltage is +/-240 VDC, charging capacity is 20% of output power and charging accuracy is +/-1%; batteries are external and weight is not published. Dimensions are 444 x 774 x 130 mm (3U) and 444 x 788 x 174 mm (4U), and the table does not map models to enclosures column by column. The unit has a 7 inch touch LCD, USB, RS232, RS485 and dry contact, with SNMP card, AS400 card, parallel kit, LBS, air filter and cold start as options. Certification is IEC 62040-1 and IEC 60950-1, protection is IP20, operation is 0-40 C, storage -25 to 70 C and humidity 0-95%.

Key points

  1. Five models: 10 kVA/10 kW, 15 kVA/15 kW, 20 kVA/20 kW, 30 kVA/30 kW, 40 kVA/40 kW; output power factor 1.
  2. Input is 3P+N+PE, 380/400/415 VAC; input power factor above 0.99; THDi under 3% (100% linear load); input range 304-478 VAC (line-to-line) at full load.
  3. Efficiency is 96% or more in normal and battery mode; inverter voltage accuracy +/-1%; THDu under 1% on linear load.
  4. Overload: 110% for 1 hour, 125% for 10 min, 150% for 1 min, 200 ms above 150%; crest factor 3:1.
  5. Bypass range is -40% to +25% (default -20% to +15%); frequency window +/-1, +/-3, +/-5 Hz.
  6. Battery +/-240 VDC, charging capacity 20% x Pout; external batteries; weight not published.
  7. Size: 444 x 774 x 130 mm (3U) and 444 x 788 x 174 mm (4U); 30 kW in 2U power density claim.
  8. Operation 0-40 C; storage -25 to 70 C; humidity 0-95% non-condensing; IP20; IEC 62040-1 and IEC 60950-1; USB, RS232, RS485, dry contact.

Using it in design

  • Calculate capacity directly in kW since output power factor is 1; the 40 kVA model carries 40 kW.
  • Assess the input range (304-478 V line-to-line at full load) and the derating below 304 V against weak mains conditions.
  • Size the external battery bank separately for +/-240 VDC and the charging capacity (20% of output power); since weight is not published, obtain it from the manufacturer for floor loading.
  • Use efficiency as a lower bound (96%); request a load-dependent efficiency curve from the manufacturer.
  • In rack layout allow for 3U and 4U heights and 774-788 mm depth, and verify the model-to-enclosure mapping.

Who should read it

Electrical designers and buyers selecting rack UPS for mid-size data rooms and IT infrastructure.

Document contents

  1. Catalogue contents
  2. TCA series summary and features
  3. TCA technical table (main input, battery, bypass, inverter, system, environment, dimensions)

Publication details

Authors
EPI UPS
Publisher
EPI UPS
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

EPI UPS EPI UPS product catalogue, TCA technical table, printed pp.20–21. EPI UPS. https://epi-ups.com/wp-content/uploads/2025/06/epi-cat-150625.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.