EPI UPS product catalogue, TCA technical table, printed pp.20-21
Original title EPI UPS product catalogue, TCA technical table, printed pp.20–21
EPI UPS
EPI UPS's TCA series: 10-40 kVA three-phase rack UPS at unity output power factor, efficiency of 96% or more, THDi under 3%, and 30 kW in 2U, with external batteries.
On this page
Overview
In EPI UPS's 2025 catalogue the TCA series is presented as a 10-40 kVA three-phase rack or tower double-conversion on-line UPS. The rest of the catalogue covers the Lite, MTN, MHP, XR+, Xtreme, HM, HT and TG+ series, the modular RMD series, ATS, n-STS and STS products, inverters, AVRs and rectifiers; this summary rests only on the TCA table (pp.20-21). There are five models: TCA010LR, 015LR, 020LR, 030LR and 040LR, that is 10 kVA/10 kW, 15 kVA/15 kW, 20 kVA/20 kW, 30 kVA/30 kW and 40 kVA/40 kW.
Input is 3P5W (3P+N+PE), 380/400/415 VAC line-to-line, 220/230/240 VAC line-to-neutral, 50/60 Hz; input power factor is above 0.99 and current distortion is THDi under 3% at 100% linear load. The input voltage range is 304-478 VAC (line-to-line) at full load, with derating from 100% to 75% below 304 V, and the frequency range is 40-70 Hz. The bypass range is settable from -40% to +25% (default -20% to +15%) with a selectable frequency window of +/-1, +/-3 or +/-5 Hz.
At the inverter output, power factor is 1, voltage accuracy +/-1%, load response under 5% (20%-80%-20% step), recovery time under 20 ms (0%-100%-0%), THDu 1% on linear load and under 5% on non-linear load (IEC 62040-3), and crest factor 3:1. Overload capability is 110% for 1 hour, 125% for 10 minutes, 150% for 1 minute and 200 ms above 150%. Efficiency is given as 96% or more in normal mode and battery mode; this is a lower-bound claim, not a load curve.
Battery voltage is +/-240 VDC, charging capacity is 20% of output power and charging accuracy is +/-1%; batteries are external and weight is not published. Dimensions are 444 x 774 x 130 mm (3U) and 444 x 788 x 174 mm (4U), and the table does not map models to enclosures column by column. The unit has a 7 inch touch LCD, USB, RS232, RS485 and dry contact, with SNMP card, AS400 card, parallel kit, LBS, air filter and cold start as options. Certification is IEC 62040-1 and IEC 60950-1, protection is IP20, operation is 0-40 C, storage -25 to 70 C and humidity 0-95%.
Key points
- Five models: 10 kVA/10 kW, 15 kVA/15 kW, 20 kVA/20 kW, 30 kVA/30 kW, 40 kVA/40 kW; output power factor 1.
- Input is 3P+N+PE, 380/400/415 VAC; input power factor above 0.99; THDi under 3% (100% linear load); input range 304-478 VAC (line-to-line) at full load.
- Efficiency is 96% or more in normal and battery mode; inverter voltage accuracy +/-1%; THDu under 1% on linear load.
- Overload: 110% for 1 hour, 125% for 10 min, 150% for 1 min, 200 ms above 150%; crest factor 3:1.
- Bypass range is -40% to +25% (default -20% to +15%); frequency window +/-1, +/-3, +/-5 Hz.
- Battery +/-240 VDC, charging capacity 20% x Pout; external batteries; weight not published.
- Size: 444 x 774 x 130 mm (3U) and 444 x 788 x 174 mm (4U); 30 kW in 2U power density claim.
- Operation 0-40 C; storage -25 to 70 C; humidity 0-95% non-condensing; IP20; IEC 62040-1 and IEC 60950-1; USB, RS232, RS485, dry contact.
Using it in design
- Calculate capacity directly in kW since output power factor is 1; the 40 kVA model carries 40 kW.
- Assess the input range (304-478 V line-to-line at full load) and the derating below 304 V against weak mains conditions.
- Size the external battery bank separately for +/-240 VDC and the charging capacity (20% of output power); since weight is not published, obtain it from the manufacturer for floor loading.
- Use efficiency as a lower bound (96%); request a load-dependent efficiency curve from the manufacturer.
- In rack layout allow for 3U and 4U heights and 774-788 mm depth, and verify the model-to-enclosure mapping.
Who should read it
Electrical designers and buyers selecting rack UPS for mid-size data rooms and IT infrastructure.
Document contents
- Catalogue contents
- TCA series summary and features
- TCA technical table (main input, battery, bypass, inverter, system, environment, dimensions)
Publication details
- Authors
- EPI UPS
- Publisher
- EPI UPS
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
EPI UPS EPI UPS product catalogue, TCA technical table, printed pp.20–21. EPI UPS. https://epi-ups.com/wp-content/uploads/2025/06/epi-cat-150625.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.