N-Power Pro-Vision Black M: Standard and LT Model Technical Tables
Original title N-Power Pro-Vision Black M: standard and LT model technical tables
N-Power
N-Power Pro-Vision Black M is a 1 to 10 kVA single-phase double-conversion UPS with output power factor 0.8 (0.9 at 6 to 10 kVA), system efficiency up to 95%, a 100 to 300 V input range and 0 ms battery transfer.
On this page
Overview
Pro-Vision Black M is N-Power's online double-conversion single-phase UPS series, offered in 1, 2, 3, 6 and 10 kVA models with standard, long-time (LT) and rack/tower (RT) versions. The series continues the earlier Pro-Vision Black. Output power factor is raised to 0.8 (0.9 at 6 to 10 kVA); for example the 3 kVA model delivers 2.4 kW, the 6 kVA model 5.4 kW and the 10 kVA model 9.0 kW.
The input voltage range is widened to 100 to 300 V (140 V at 100% load, 110 V at 50% load). Input power factor is at least 0.98 and input current THD is below 6%. Output voltage is 208/220/230/240 V (set at the panel) with ±1% regulation, and THD is below 3% on linear load and below 5% on non-linear load. Transfer from mains to battery and back is 0 ms, transfer to bypass is under 4 ms and transfer to ECO mode under 10 ms. Efficiency is at least 90% at 100% load and at least 94% in ECO mode.
On the battery side the units use sealed lead-acid batteries in 24 V (2 x 12 V), 48 V (4 x 12 V) or 72 V (6 x 12 V) groups depending on the model. Three-stage charging gives 1 A on standard models and 6 A on LT models. External battery blocks (BOH17 Black, BOH34 Black) connect to the 6 to 10 kVA LT models. Operating temperature is 0 to 40 °C with no derating up to 1500 m. The page is a product page published in Russian.
Key points
- Models: 1, 2, 3, 6, 10 kVA; standard, LT and RT versions.
- Ratings: 1 kVA / 0.8 kW (RT 0.9), 2 kVA / 1.6 kW (RT 1.8), 3 kVA / 2.4 kW (RT 2.7), 6 kVA / 5.4 kW, 10 kVA / 9.0 kW.
- Input 110 to 300 V (50% load), 140 to 300 V (100% load); input power factor ≥0.98.
- Output 208/220/230/240 V, ±1%; THD <3% (linear), <5% (non-linear).
- Transfer: mains to battery 0 ms; to bypass <4 ms; to ECO <10 ms.
- Efficiency ≥90% (100% load), ≥94% in ECO mode; system efficiency up to 95%.
- Battery 24, 48 or 72 V; 3-stage charging; charging current 1 A (standard), 6 A (LT).
- Operation 0 to 40 °C; no derating up to 1500 m.
Using it in design
- On the 1 to 3 kVA models with power factor 0.8, check load in kW: the 3 kVA model gives 2.4 kW.
- At sites with weak mains or generators, an input range down to 140 V reduces battery use.
- On 6 to 10 kVA LT models, size external battery blocks (BOH17, BOH34) together with the charging current.
- ECO-mode transfer is under 10 ms; consider keeping the mode off for sensitive loads.
- Because the page tables are in Russian, state the specification language and model codes (M, LT, RT) explicitly.
Who should read it
Engineers and buyers selecting single-phase UPS units for small critical loads.
Document contents
- Product introduction and model list
- Distinguishing features of Pro-Vision Black M
- Pro-Vision Black M P (2016 revision)
- Common parameters: input, output, battery, environment
- Model tables (1000 to 10000)
Publication details
- Authors
- N-Power
- Publisher
- N-Power
- Year
- Year not stated
- Document language
- Russian
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
N-Power N-Power Pro-Vision Black M: standard and LT model technical tables. N-Power. https://www.xn--80aacyeau1asblh.xn--p1ai/catalogue/ups-sale/pro-vision-black-m?page=&print=1&tmpl=component
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.