N-Power Pro-Vision Black M: Standard and LT Model Technical Tables

Original title N-Power Pro-Vision Black M: standard and LT model technical tables

N-Power

N-Power Pro-Vision Black M is a 1 to 10 kVA single-phase double-conversion UPS with output power factor 0.8 (0.9 at 6 to 10 kVA), system efficiency up to 95%, a 100 to 300 V input range and 0 ms battery transfer.

On this page

Overview

Pro-Vision Black M is N-Power's online double-conversion single-phase UPS series, offered in 1, 2, 3, 6 and 10 kVA models with standard, long-time (LT) and rack/tower (RT) versions. The series continues the earlier Pro-Vision Black. Output power factor is raised to 0.8 (0.9 at 6 to 10 kVA); for example the 3 kVA model delivers 2.4 kW, the 6 kVA model 5.4 kW and the 10 kVA model 9.0 kW.

The input voltage range is widened to 100 to 300 V (140 V at 100% load, 110 V at 50% load). Input power factor is at least 0.98 and input current THD is below 6%. Output voltage is 208/220/230/240 V (set at the panel) with ±1% regulation, and THD is below 3% on linear load and below 5% on non-linear load. Transfer from mains to battery and back is 0 ms, transfer to bypass is under 4 ms and transfer to ECO mode under 10 ms. Efficiency is at least 90% at 100% load and at least 94% in ECO mode.

On the battery side the units use sealed lead-acid batteries in 24 V (2 x 12 V), 48 V (4 x 12 V) or 72 V (6 x 12 V) groups depending on the model. Three-stage charging gives 1 A on standard models and 6 A on LT models. External battery blocks (BOH17 Black, BOH34 Black) connect to the 6 to 10 kVA LT models. Operating temperature is 0 to 40 °C with no derating up to 1500 m. The page is a product page published in Russian.

Key points

  1. Models: 1, 2, 3, 6, 10 kVA; standard, LT and RT versions.
  2. Ratings: 1 kVA / 0.8 kW (RT 0.9), 2 kVA / 1.6 kW (RT 1.8), 3 kVA / 2.4 kW (RT 2.7), 6 kVA / 5.4 kW, 10 kVA / 9.0 kW.
  3. Input 110 to 300 V (50% load), 140 to 300 V (100% load); input power factor ≥0.98.
  4. Output 208/220/230/240 V, ±1%; THD <3% (linear), <5% (non-linear).
  5. Transfer: mains to battery 0 ms; to bypass <4 ms; to ECO <10 ms.
  6. Efficiency ≥90% (100% load), ≥94% in ECO mode; system efficiency up to 95%.
  7. Battery 24, 48 or 72 V; 3-stage charging; charging current 1 A (standard), 6 A (LT).
  8. Operation 0 to 40 °C; no derating up to 1500 m.

Using it in design

  • On the 1 to 3 kVA models with power factor 0.8, check load in kW: the 3 kVA model gives 2.4 kW.
  • At sites with weak mains or generators, an input range down to 140 V reduces battery use.
  • On 6 to 10 kVA LT models, size external battery blocks (BOH17, BOH34) together with the charging current.
  • ECO-mode transfer is under 10 ms; consider keeping the mode off for sensitive loads.
  • Because the page tables are in Russian, state the specification language and model codes (M, LT, RT) explicitly.

Who should read it

Engineers and buyers selecting single-phase UPS units for small critical loads.

Document contents

  1. Product introduction and model list
  2. Distinguishing features of Pro-Vision Black M
  3. Pro-Vision Black M P (2016 revision)
  4. Common parameters: input, output, battery, environment
  5. Model tables (1000 to 10000)

Publication details

Authors
N-Power
Publisher
N-Power
Year
Year not stated
Document language
Russian
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

N-Power N-Power Pro-Vision Black M: standard and LT model technical tables. N-Power. https://www.xn--80aacyeau1asblh.xn--p1ai/catalogue/ups-sale/pro-vision-black-m?page=&print=1&tmpl=component

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.