N-Power Pro-Vision Black M P4 6000–20000 VA manual, 13 December 2019
N-Power
This Russian-language manual from N-Power, dated 13 December 2019, describes the 6, 10 and 20 kVA double-conversion on-line UPS models in the P4 revision of the Pro-Vision Black M series. The units deliver 6, 10 and 20 kW at unity power factor on a 230 V output, and the standard, LT, tower and RT enclosures are each listed with their own dimensions and weights.
On this page
Overview
The manual covers the P4 revision of the N-Power Pro-Vision Black M family and gathers the 6000, 10000 and 20000 VA units in one document. The model table (printed p. 2) draws two distinctions at once: standard units with internal batteries versus LT versions that run from an external battery bank, and upright tower enclosures versus RT enclosures that fit a 19-inch rack. In the 10 kVA class the single-phase-input models sit alongside 3/1 versions with three-phase input and single-phase output, and the 20 kVA models are listed only as 3/1 LT units.
The physical data table (printed pp. 8-9) gives separate dimensions and weights for every variant. Standard tower enclosures are 191 mm wide and 711 mm high; the 6 kVA model is 501 mm deep and weighs 53 kg, and the 10 kVA model is 531 mm deep and weighs 62 kg. LT tower enclosures without batteries drop to 350 mm in height and 14.5 to 16.5 kg. RT enclosures are 440 mm wide: models with internal batteries are 176 mm high and 660 mm deep, while RT LT models are 88 mm high.
The document ties the operating limits to the selected output voltage: the output power factor is 1 at 230 V and falls to 0.9 when a 208 V output is selected. All models use the double-conversion on-line topology and VRLA batteries. It is a product manual for small and medium equipment rooms and edge cabinets; the dimensions and weights quoted for LT models describe the UPS electronics only, so the external battery cabinet is accounted for separately.
Key points
- Scope: Pro-Vision Black M P4 revision, 6, 10 and 20 kVA; unity power factor at 230 V output (6, 10 and 20 kW), power factor 0.9 at 208 V output.
- Standard tower models: 6 kVA 191 × 501 × 711 mm, 53 kg; 10 kVA 191 × 531 × 711 mm, 62 kg (width × depth × height).
- LT tower models: 6 kVA 191 × 501 × 350 mm, 14.5 kg; 10 kVA 191 × 531 × 350 mm, 16.5 kg; 20 kVA 3/1 191 × 537 × 515 mm, 26.5 kg.
- RT models with internal batteries: 440 × 660 × 176 mm; 6 kVA 58 kg, 10 kVA 67 kg.
- RT LT depth depends on the input type: 580 mm for the single-phase-input 6 and 10 kVA models, 650 mm for the three-phase-input 10 kVA 3/1 model, and 440 × 780 × 132 mm at 25.5 kg for the 20 kVA 3/1 model.
- All models are double-conversion on-line with VRLA batteries; LT versions require an external battery bank.
Using it in design
- In rack layouts, pick the RT LT depth by input type: 580 mm for single-phase input, 650 mm for 3/1 input and 780 mm for the 20 kVA model, then confirm rack depth and rear cable clearance against it.
- Fix the output voltage in the load calculation: for a 208 V output, take active power as 0.9 times the kVA rating.
- When an LT model is selected, add the external battery cabinet's footprint, weight and floor loading as separate items; the 12 to 26.5 kg figures in the table cover the electronics enclosure only.
- For a 20 kVA requirement, plan the three-phase supply and the single-phase output distribution (3/1) together, and size the output board for the single-phase 20 kVA current.
Who should read it
Electrical designers selecting 6 to 20 kVA UPS units for small equipment rooms and edge cabinets, and engineers laying out racks.
Publication details
- Authors
- N-Power
- Publisher
- N-Power
- Year
- 2019
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
N-Power (2019). N-Power Pro-Vision Black M P4 6000–20000 VA manual, 13 December 2019. N-Power. https://st.n-power.su/7/2756/584/manual-pro-vision-black-m-p4_ru.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.