Power Inspired VFI Online UPS Systems Catalogue, 1-10 kVA

Original title Power Inspired VFI Series brochure rev1.3, p.2

Power Inspired

Power Inspired VFI brochure: tower (VFI-T), rack/free-standing (VFI-B) and 10 kVA hardwired (VFI-KT) double-conversion UPS with 0.9 output power factor, 1-10 kVA and 94% efficiency in ECO mode.

On this page

Overview

The brochure presents Power Inspired's 1-10 kVA double-conversion VFI UPS family. The VFI-T series is 1 and 3 kVA tower units with IEC sockets and daisy-chainable battery packs. The VFI-KT is a 10 kVA hardwired system with a removable bypass module, so the UPS can be serviced or replaced without downtime or a separate wrap-around bypass switch, and it can be paralleled for redundancy. The VFI-B series mounts in a rack or free-standing, horizontally or vertically; the pluggable 1.5 and 3 kVA models have easy-to-remove, hot-swappable battery trays, and 3 and 6 kVA high-capacity-charger models serve very long runtime applications.

Common features: high power density (0.9 output power factor), low input current harmonic distortion, selectable high-efficiency (ECO) mode, an intelligent port for SNMP or relay cards, LCD display, cold start, EPO, load shed and three-stage charging. Models: VFI1000T 1000 VA / 900 W, VFI3000T 3000 / 2700 W, VFI10KT 10 kVA / 9 kW, VFI1500B 1500 / 1350, VFI3000B 3000 / 2700, VFI3000BL 3000 / 2700 and VFI6000BL 6000 / 5400.

Efficiency is 88-93.5% in AC mode (93.5% for 10 kVA), 84-87% in battery mode and 94% in ECO mode. Output regulation is ±1% or ±2%, crest ratio 3:1, THD at most 3% on linear and 5% on non-linear load. Battery strings are 36 V, 72 V or ±120 V; the 10 kVA uses 12 V 9 Ah x16 (±120 V). Dimensions range from 144x400x215 mm (13 kg) to 250x502x616 mm (64 kg). Environment is 0-40 °C, 0-90% RH, altitude to 1500 m (derating above). Safety is EN 62040-1 and EMC EN 62040-2.

Key points

  1. Ratings: 1000T 1000 VA / 900 W, 3000T 3000 / 2700 W, 10KT 10 kVA / 9 kW, 1500B 1500 / 1350 W, 3000B 3000 / 2700 W, 3000BL 3000 / 2700 W, 6000BL 6000 / 5400 W.
  2. Output power factor 0.9; crest ratio 3:1; THD at most 3% linear and 5% non-linear.
  3. Efficiency: 88-93.5% in AC mode, 84-87% in battery mode, 94% in ECO mode.
  4. Transfer: zero from line to battery, typically 4 ms to bypass; frequency converter mode sets 50 or 60 Hz output.
  5. Overload (10 kVA): 110% for 60 min, 125% for 10 min, up to 150% for 1 min or 3 s depending on model.
  6. Battery: 12 V 9 Ah blocks, 36 V (x3), 72 V (x6), ±120 V (x16) for 10 kVA; matching cabinet for 10KT holds 12 V 9 Ah x32.
  7. Size and weight: VFI10KT 250x502x616 mm, 64 kg; VFI1000T 144x400x215 mm, 13 kg.
  8. Environment 0-40 °C, 0-90% RH, altitude 1500 m; EN 62040-1 and EN 62040-2.

Using it in design

  • In small rooms, match tower, in-rack or free-standing options to the layout and weigh the horizontal and vertical mounting of the VFI-B in the rack plan.
  • Compare the VFI-KT's removable bypass module and paralleling option with the need for service without downtime.
  • Meet the required autonomy with matching battery cabinets and the 3 and 6 kVA high-capacity-charger models, and check recharge time.
  • Use the 0.9 power factor to compare real kW capacity (for example 2700 W for 3000 VA) with the load list.
  • Apply altitude derating at sites above 1500 m.

Who should read it

Designers selecting single- and three-phase UPS for small and medium IT rooms.

Document contents

  1. VFI-T Series
  2. VFI-KT
  3. VFI-B Series
  4. VFI Features
  5. Specifications
  6. Matching Battery Cabinets

Publication details

Authors
Power Inspired
Publisher
Power Inspired
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Power Inspired Power Inspired VFI Series brochure rev1.3, p.2. Power Inspired. https://www.powerinspired.com/brochures/BR-UPS-VFI.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.