Sunstone Power SPT12-7.2: Specification

Sunstone Power

The Sunstone Power SPT12-7.2 is a 12 V, 7.2 Ah (C20, 1.80 V/cell, 25 C) AGM VRLA battery, 151 x 65 x 100 mm, about 2.12 kg, with 105 A (5 s) maximum discharge current and 5-year design life.

On this page

Overview

The product page presents a sealed, maintenance-free VRLA block from the SPT series, built with AGM (absorbent glass mat) technology for general use. Applications listed include UPS, telecommunications, and alarm and security systems. The case is ABS, with a V0 flame-retardant option. Design life is 5 years at 25 C, self-discharge is 3% per month, and the warranty is 1 year on float use at 25 C.

Nominal voltage is 12 V (6 cells). Capacity depends on discharge time: 7.2 Ah at 20 h to 1.80 V/cell, 6.8 Ah at 10 h to 1.75 V/cell, 6.2 Ah at 5 h to 1.75 V/cell and 4.3 Ah at 1 h to 1.60 V/cell (all at 25 C). Length is 151 +/-2 mm, width 65 +/-2 mm, container height 94 +/-2 mm and total height with terminal 100 +/-2 mm.

Approximate weight is 2.12 kg, terminal F1 or F2, maximum discharge current 105 A (5 seconds) and internal resistance about 23 mOhm. The data is for a single block; UPS runtime, string wiring and battery life calculations need the manufacturer's discharge tables.

Key points

  1. Nominal voltage 12 V (6 cells); capacity 7.2 Ah (20 h, 1.80 V/cell, 25 C).
  2. Other capacities: 6.8 Ah (10 h, 1.75 V/cell), 6.2 Ah (5 h, 1.75 V/cell), 4.3 Ah (1 h, 1.60 V/cell).
  3. Dimensions: 151 x 65 mm, container height 94 mm, 100 mm with terminal.
  4. Approximate weight 2.12 kg; ABS case with V0 flame-retardant option.
  5. Maximum discharge current 105 A (5 s); internal resistance about 23 mOhm.
  6. Design life 5 years at 25 C; self-discharge 3% per month; warranty 1 year.
  7. Terminal type F1 or F2.

Using it in design

  • Do not use the 7.2 Ah (C20) figure for runtime; use the value that matches the discharge time and end voltage, such as 4.3 Ah at 1 hour.
  • Use the 100 mm height including terminal in rack and cabinet design.
  • In short-circuit current and protection selection, account for the internal resistance (about 23 mOhm) and the 105 A maximum discharge current.
  • Because the 5-year design life is referenced to 25 C, tie the battery replacement plan to temperature.

Who should read it

Designers and maintenance teams selecting batteries for small UPSs and alarm systems.

Document contents

  1. Product description
  2. SPT series
  3. Specification

Publication details

Authors
Sunstone Power
Publisher
Sunstone Power
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Sunstone Power Sunstone Power SPT12-7.2: Specification. Sunstone Power. https://sunstonepower.com/AGM_Battery/165.html

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.