Technical guideFree to readYear not stated

KVA Oxxigen 70A automatic generator transfer panel: technical table

Original title KVA Oxxigen 70A complete generator automatic transfer panel, technical table

KVA

The KVA Oxxigen 70A is a complete generator control and automatic transfer panel for loads up to 70 A (AC1), used with generators up to 27 kVA at 220 Vac or 46 kVA at 380 Vac.

On this page

Overview

The Oxxigen 70A is a complete control and automatic transfer panel (QCTA) that KVA designed for small generator sets. The manufacturer's product page states that the model serves loads up to 70 A in utilisation category AC1. The page has Overview, Specifications and Downloads tabs; the technical table gives electrical data, transfer arrangement, components, protections and physical data under separate headings.

Electrically, the rated load current is 70 A (AC1) and the generator it can accompany is rated up to 27 kVA at 220 Vac and 46 kVA at 380 Vac. The alternator voltage range is 180-380 Vac phase to phase, frequency 50/60 Hz and the current transformer is 100/5 A. The control circuit is supplied at 8-32 Vdc; battery voltage is 12 or 24 Vdc, with 12 Vdc as the factory setting.

Transfer is open-transition (a break occurs) through two contactors that are interlocked both electrically and mechanically. The component list names a K30 XL controller, a K21 PRO battery charger, one protective breaker, one current transformer and eight controller fuses. Mains protections are under/over-voltage (27/59); generator protections are under/over-voltage, under/over-frequency (81) and time-delayed overcurrent (51). Engine protections cover temperature, oil pressure, water level, overspeed, start failure and overload.

The panel measures 400 × 400 × 205 mm and weighs 9 kg; the manufacturer gives a 15-month warranty (legal plus 12 additional months). The download section holds the operating manual and the electrical connection drawing. The page covers one model only; values for the other current ratings of the family are on their own pages.

Key points

  1. Maximum load current 70 A in utilisation category AC1.
  2. Accompanying generator rating: up to 27 kVA at 220 Vac and 46 kVA at 380 Vac.
  3. Alternator voltage 180-380 Vac (phase to phase), frequency 50/60 Hz, current transformer 100/5 A.
  4. Control supply 8-32 Vdc; battery 12 or 24 Vdc (factory setting 12 Vdc).
  5. Open-transition transfer with two contactors, electrical and mechanical interlock.
  6. Components: K30 XL controller, K21 PRO charger, one protective breaker, one CT, eight controller fuses.
  7. Mains protection 27/59; generator protection 27/59, 81 and 51; engine protection for temperature, oil pressure, water level, overspeed, start failure and overload.
  8. Size 400 × 400 × 205 mm, weight 9 kg; 15-month warranty.

Using it in design

  • Compare the generator rating with the limit at the chosen voltage (27 kVA at 220 Vac, 46 kVA at 380 Vac) and confirm the load current stays within 70 A AC1.
  • Account for the load break of open-transition transfer; place loads that cannot tolerate it behind a UPS.
  • Check that the CT ratio and the alternator voltage range match the generator output.
  • Carry the mains and generator protection functions into the protection coordination study.
  • Verify panel size and weight against the wall or plant-room mounting location.

Who should read it

Electrical designers and site engineers selecting automatic transfer panels for small generator sets.

Document contents

  1. Overview
  2. Specifications: Electrical
  3. Specifications: Transfer and Components
  4. Specifications: Protections
  5. Specifications: General (size, weight, warranty)
  6. Downloads

Publication details

Authors
KVA
Publisher
KVA
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

KVA KVA Oxxigen 70A complete generator automatic transfer panel, technical table. KVA. https://kva.com.br/produto/oxxigen-70a/

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.