Technical guideFree to readYear not stated

G4 Electric Chave de Transferência ATS, technical configuration table

G4 Electric

A product page from Brazilian supplier G4 Electric describing a single-phase 20 A automatic transfer switch that gives single-corded IT equipment a redundant supply from two uninterruptible sources, in two models: ATS mono/20A-220V and ATS mono/20A-120V, with a typical transfer time of 2.5-4 ms and mains-loss detection in 3-5 ms.

On this page

Overview

The page presents, in Portuguese, the automatic transfer switch of G4 Electric, a supplier of UPS, battery and solar solutions based in Cachoeirinha, Rio Grande do Sul. The manufacturer states the starting point plainly: most IT assets such as modems, switches, access points, DVRs, telephone exchanges and routers have no dual internal power supplies. The ATS gives these devices a redundant supply from two separate uninterruptible power sources. Maintenance on one source can then be carried out during business hours without interrupting supply.

The technical table gives two models: ATS mono/20A-220V with a 220 VAC input (phase, neutral, earth) and ATS mono/20A-120V with a 120 VAC input. Both have a nominal capacity of 20 A rms at 60 Hz. Input voltage tolerance is configured at the factory to ±10%, ±15% or ±20%. Output voltage is the same as the input voltage, and output overload protection is by a 20 A rms fuse. Detection time for loss of mains is typically 3-5 ms and transfer time typically 2.5-4 ms.

Status is shown by seven indicator LEDs; the RS-232 port is reserved for factory and technician use, so no user-facing remote monitoring interface is defined. Operating temperature is 0-45 °C and relative humidity 20-95% non-condensing. Cooling is by natural convection and audible noise is below 45 dBA. The degree of protection is IP 20 and the finish is matt black. The unit measures 68 x 431 x 230 mm (HxWxD) and weighs 8 kg; packed it measures 120 x 500 x 315 mm and weighs 9 kg.

Applications are listed as data centre, telecom, internet service providers, industry and servers. The warranty section states that cover is reduced to 90 days where the unit is used in unsuitable conditions such as excessive humidity or temperature, intense sun, sea air, pole mounting or confined spaces without sufficient cooling. The manufacturer notes that products can be modified to customer needs. Being defined for 60 Hz only, the product is aimed at Brazil and similar 60 Hz grids.

Key points

  1. Models: ATS mono/20A-220V (220 VAC) and ATS mono/20A-120V (120 VAC); single phase, phase + neutral + earth.
  2. Nominal capacity 20 A rms; frequency 60 Hz.
  3. Input tolerance configured at the factory to ±10%, ±15% or ±20%.
  4. Mains-loss detection time typically 3-5 ms; transfer time typically 2.5-4 ms.
  5. Output overload protection by a 20 A rms fuse.
  6. Indication: 7 LEDs; RS-232 is for factory and technician use only.
  7. Environment: 0-45 °C, 20-95% humidity non-condensing; natural convection; noise < 45 dBA; IP 20.
  8. Dimensions 68 x 431 x 230 mm (HxWxD), weight 8 kg.
  9. Warranty is reduced to 90 days in unsuitable environmental conditions.

Using it in design

  • Use an ATS per rack to feed single-corded network and communication equipment from two separate UPSs, limiting total load to 20 A (about 4.4 kVA at 220 V, 2.4 kVA at 120 V).
  • Compare the sum of detection and transfer times (typically 5.5-9 ms) with the hold-up time of the load power supplies; at 60 Hz this is around one half cycle (8.3 ms).
  • Fix the voltage tolerance band (±10%, ±15% or ±20%) at order stage; it is set at the factory and cannot be changed on site.
  • Because output protection is by fuse, add spare fuses to the operating procedure and check selectivity with downstream circuits.
  • With no user-facing communication interface, plan external metering (an intelligent PDU or voltage sensor) to monitor ATS status in DCIM.
  • The product is defined for 60 Hz; for projects on 50 Hz grids, obtain written confirmation of suitability from the manufacturer.

Who should read it

Electrical and IT infrastructure engineers designing redundant rack-level supply and teams selecting equipment for Latin American projects on 60 Hz grids.

Document contents

  1. Chave de Transferência Automática (introduction)
  2. Especificações Técnicas: Entrada, Saída, Sinalização & Comunicação, Ambiente, Dimensões & Peso
  3. Aplicações
  4. Garantia

Publication details

Authors
G4 Electric
Publisher
G4 Electric
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

G4 Electric G4 Electric Chave de Transferência ATS, technical configuration table. G4 Electric. https://www.g4electric.com.br/chave-de-transferencia-ats/

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.