HPL AV ATS catalogue April 2025, printed pp.3-6 (PDF pp.3-4)
HPL Electric & Power
HPL Electric & Power's catalogue of a 40 A to 1600 A range of true 4-pole motorised load transfer switches and automatic transfer switches (ATS).
On this page
Overview
The catalogue describes the AV ATS series as a true 4-pole, motor-operated changeover switch with positive break indication. It transfers the load between two three-phase supplies using remote volt-free contacts, from an external automatic controller or a push-button station. It is intended for low-voltage systems in which interruption of the load supply during transfer is acceptable; it does not offer closed-transition transfer.
The technical tables follow IEC 60947-3 and IEC 60947-6-1. The series is offered in four frame sizes for AC-23A and AC-31B load switching duty, with three I-O-II positions and manual and electrical operation under a non-defeatable mechanical interlock. For each current step the tables give insulation voltage, dielectric strength, impulse voltage, short-circuit withstand, making and breaking capacity, mechanical and electrical life, switching time, connection sizes and weight.
Three versions are distinguished. The controller-less version is a motorised changeover switch. The CME 310 includes an input control supply and logic with LED indication: it monitors both sources, issues generator (DG) start and stop commands and selects the preferred source. The CME 360 is a smart controller that measures both sources: over/under voltage, frequency and current monitoring, over 45 parameters, event recording of the last 10 faults, RS485 Modbus (optional Ethernet) communication and remote operation through PLC/SCADA/EMS.
Model identity, supply voltage and switching configuration should stay attached to each selection. For example, the AV ATS CME 360 frame 0, 40 A model enters the catalogue as 40 A. The controller operates at 60 V DC or 230 V AC, with other voltages on request.
Key points
- Current range 40 A to 1600 A; true 4-pole, motorised, three-position I-O-II.
- Standards: IEC 60947-6-1 and IEC 60947-3; CE marked and RoHS compliant.
- Four frame sizes; AC-23A and AC-31B load switching duty.
- The load supply is briefly interrupted during transfer; closed-transition transfer is not intended.
- CME 310: source monitoring, DG start/stop, preferred-source selection, LED indication, available across the range.
- CME 360: over 45 parameters, event record of the last 10 faults, RS485 Modbus and optional Ethernet, 6-month kWh and MD history.
- CME 360 operating voltage 60 V DC or 230 V AC; built-in controller for all ratings from 40 A to 1600 A.
- The AV ATS CME 360 frame 0, 40 A model is listed at 40 A.
Using it in design
- Do not use this type of transfer switch alone for loads that need seamless transfer; place it behind a UPS or on loads that tolerate interruption (cooling, ventilation).
- When selecting a switch, look not only at rated current but also at the utilisation category (AC-23A, AC-31B), the site short-circuit current and the associated fuse rating.
- Decide whether generator start/stop logic sits in the ATS controller or a separate panel; compare the scope of the CME 310 and CME 360.
- State in the specification whether BMS or SCADA integration needs RS485 Modbus or Ethernet.
- Compare the electrical blackout time during transfer with the hold-up time of the load and the UPS.
Who should read it
Electrical engineers designing generator and mains changeover, and teams writing ATS specifications.
Document contents
- AV ATS introduction and standards
- Salient features
- Technical specification tables (40-1600 A)
- ATS versions: without controller, CME 310, CME 360
Publication details
- Authors
- HPL Electric & Power
- Publisher
- HPL Electric & Power
- Year
- 2025
- Document language
- Unverified
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
HPL Electric & Power (2025). HPL AV ATS catalogue April 2025, printed pp.3-6 (PDF pp.3-4). HPL Electric & Power. https://www.hplindia.com/wp-content/uploads/2025/04/AV-ATS-Catalogue-2025-14th-April-25.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.