Technical guideFree to read2018

Nader Low-Voltage Product Selection Manual 2018 V1, printed pp.25-26

Nader

Nader's 73-page Low-Voltage Product Selection Manual, version 2018 V1, presents the NDQ3H series of PC-class automatic transfer switches on pages 25 and 26. The series spans frame sizes from 63 A to 5000 A and rated currents from 16 A to 5000 A, with a contact changeover time of no more than 100 ms for the two-position type.

On this page

Overview

The document is the 2018 V1 selection manual that gathers the low-voltage range of the Chinese manufacturer Nader in one volume. The distribution scheme at the front places the products on three distribution levels: air circuit breakers and automatic transfer equipment on level one, moulded case circuit breakers on level two, and miniature circuit breakers, residual current devices, isolating switches, contactors and thermal relays on level three. Each series gets a quick selection table and a table of main performance parameters.

Printed pages 25 and 26 are devoted to the NDQ3H series automatic transfer switch (ATS). It is a purpose-built PC-class transfer device, without short-circuit breaking capability. The order code combines frame size, controller type (A basic, B advanced, C communication, D intelligent), rated current, number of poles (2, 3 or 4), structure (integral or separated) and switch positions (two or three). The frame sizes are 63, 125, 250, 400, 630, 800, 1250, 3150 and 5000 A.

The performance table falls into two groups by frame size. Frames from 63 to 800 A have a rated insulation voltage of AC 800 V and an impulse withstand voltage of 8 kV; contact changeover time is at most 100 ms for the two-position type and 140 ms for the three-position type, and total changeover operating time is at most 360 ms and 400 ms respectively. Frames of 1250 A and above have AC 1000 V insulation and 12 kV impulse withstand, with contact changeover of at most 200 ms and operating time of at most 500 ms. Utilisation categories are AC-33A, AC-33B and AC-33iB depending on frame, and the control voltage is AC 230 V.

On the following pages (27 onwards) the manual also presents the circuit-breaker-based NDQ5W series: CB-class transfer equipment in 1600, 2500 and 4000 A frames, of drawer type, with AC 1000 V insulation, 12 kV impulse withstand and controller options for two or three sources and for bus-coupler schemes. The document is a selection summary dated 2018; it has no dimensional drawings, wiring diagrams or coordination tables. Those details require the technical catalogue of the series concerned.

Key points

  1. NDQ3H: purpose-built PC-class automatic transfer switch; frame sizes 63, 125, 250, 400, 630, 800, 1250, 3150 and 5000 A.
  2. Rated currents: 16, 20, 25, 32, 40, 50 and 63 A in the 63 A frame; 80, 100 and 125 A in the 125 A frame; 160, 180, 200, 225 and 250 A in the 250 A frame; 4000 and 5000 A in the largest frame.
  3. 63 to 800 A frames: insulation voltage AC 800 V, impulse withstand voltage 8 kV. Frames of 1250 A and above: AC 1000 V and 12 kV.
  4. Contact changeover time: at most 100 ms for the two-position type and 140 ms for the three-position type; at most 200 ms on the large frames.
  5. Changeover operating time: at most 360 ms for the two-position type and 400 ms for the three-position type; at most 500 ms on the large frames.
  6. 2, 3 or 4 poles; working voltage AC 230 V for 2-pole and AC 400 V for 3-pole and 4-pole units; control voltage AC 230 V.
  7. Controller options: A basic, B advanced, C communication and D intelligent; integral or separated structure.
  8. NDQ5W (p. 27): CB class, 1600, 2500 and 4000 A frames; rated short-circuit breaking capacity 55, 85 and 100 kA respectively; utilisation category AC-33iB.

Using it in design

  • The PC-class NDQ3H does not interrupt short-circuit current; provide a suitable upstream circuit breaker or fuse and coordinate the switch's short-time withstand current with that protection.
  • The interruption during transfer is in the order of 100 to 500 ms; feed IT load through a UPS downstream of this switch and compare the UPS input-interruption tolerance with that time.
  • Choose the three-position type where a safe intermediate position is needed between generator and mains, and the two-position type where the shortest changeover is needed.
  • Specify the 4-pole version in earthing arrangements that require the neutral to be switched.
  • For main distribution transfers above 1250 A, compare the PC-class NDQ3H with the breaker-based NDQ5W in terms of fault level and maintenance access (drawer construction).

Who should read it

Electrical designers and panel builders selecting transfer switches and protective devices for low-voltage distribution.

Document contents

  1. Power Distribution Scheme; Product Profile
  2. Air circuit breaker: NDW2, NDW3
  3. Moulded case circuit breaker: NDM3, NDM3A, NDM3Z, NDM3L, NDM3E
  4. Automatic transfer switch: NDQ3H, NDQ5W
  5. Disconnecting switch: NDG2, NDGR2 and other series
  6. Miniature circuit breaker: NDM1, NDB1, NDB2
  7. Contactors and other control products

Publication details

Authors
Nader
Publisher
Nader
Year
2018
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Nader (2018). Nader Low-Voltage Product Selection Manual 2018 V1, printed pp.25-26. Nader. https://poligon.info/uploads/booklet/file/20/Nader-Catalog-Book.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.