Himel HDQ3HB Transfer Switch Equipment

Original title Himel HDQ3HB Transfer Switch Equipment, PDF pp.2-3

Himel

Himel's HDQ3HB catalogue describes CB-class automatic transfer switches built on HDM3 moulded-case breakers in five frame sizes (63, 100, 250, 400, 630 AF) from 10 A to 630 A, with a short-circuit breaking capacity of 25 kA or 50 kA and a transfer time of up to 3 seconds.

On this page

Overview

The catalogue presents the HDQ3HB transfer switch equipment in Himel's 3 series low-voltage range. The product transfers automatically between a normal and a standby power supply, where the standby source can be a second utility feed or a generator. The construction is CB class: HDM3 series moulded-case circuit breakers act as the switching elements, so overload and short-circuit protection sit inside the unit. The standards are given as GB 14048.11 (AC-33iB) and IEC 60947-6-1 (AC-32B). The controller is available as an integrated or a split type.

The range has five frames. The 63 AF frame covers rated currents of 10-63 A, the 100 AF frame 16-100 A, the 250 AF frame 100-250 A, the 400 AF frame 200-400 A and the 630 AF frame 400-630 A. Rated operating voltage is 400 V at 50 Hz with 3 or 4 poles. The 63 and 100 AF frames are level S with 25 kA breaking and 52.5 kA making capacity; the 250 AF and larger frames are level F with 50 kA breaking and 105 kA making capacity.

The ordering code strings together frame, breaking level, current, poles and controller type. HDQ3HB63S103Z, for example, is the 63 AF frame, 25 kA, 10 A, 3-pole unit with an integrated controller. The controller supports utility-to-utility and utility-to-generator operation with auto-return, non-return and mutual-backup modes. The factory over-voltage threshold is 264 V and the under-voltage threshold 184 V. Transfer and return delays are adjustable from 0 to 99.9 s (factory 3 s), and generator start and stop delays from 0 to 99.9 s (factory 15 s).

A transfer time of up to 3 seconds shows that this equipment is built for source changeover, not for uninterrupted transfer; IT loads must be carried by a UPS during the changeover. Mechanical life is 10,000 cycles on the 63 and 100 AF frames and 5,000 cycles on the larger frames. The catalogue also gives the dimensions of integral and split versions, mounting-hole sizes and the standard 1.6 m controller lead (custom lengths up to 5 m).

Key points

  1. Five frames: 63, 100, 250, 400, 630 AF; rated current range 10-630 A; 3 or 4 poles.
  2. Standards GB 14048.11 AC-33iB and IEC 60947-6-1 AC-32B; CB class, based on HDM3 moulded-case breakers.
  3. Rated operating voltage 400 V, 50 Hz; rated insulation voltage 690 V or 800 V depending on frame.
  4. Short-circuit breaking capacity Icn: 25 kA for 63 and 100 AF, 50 kA for 250, 400 and 630 AF; making capacity Icm 52.5 kA and 105 kA.
  5. Transfer time 3 s or less.
  6. Mechanical life: 10,000 cycles for 63 and 100 AF, 5,000 cycles for 250-630 AF.
  7. Factory settings: over-voltage 264 V, under-voltage 184 V, transfer and return delay 3 s, generator start and stop delay 15 s.
  8. Integral 3-pole dimensions (W x H x D): 63 AF 375 x 220 x 121 mm, 100 AF 415 x 220 x 148 mm, 250 AF 465 x 220 x 148 mm, 400 AF 610 x 330 x 185 mm.
  9. Ordering code example: HDQ3HB63S103Z, 63 AF, S (25 kA), 10 A, 3 poles, integrated controller.

Using it in design

  • With a transfer time of up to 3 seconds, use this unit at the UPS input or on mechanical-load boards; a point feeding IT load directly needs a static transfer switch.
  • Compare the prospective short-circuit current at the installation point with the 25 kA (63 and 100 AF) or 50 kA (250 AF and above) breaking capacity.
  • Study the built-in overcurrent protection of the CB-class construction for selectivity with the upstream and downstream breakers.
  • In generator systems, set the start delay (factory 15 s) against the generator's time to accept load and the UPS autonomy.
  • For earthing arrangements that require a switched neutral, choose the 4-pole ordering code (ending in 4Z).
  • In panel design, allow for the frame-dependent dimensions and the 85 x 166 x 92 mm space of a split controller.

Who should read it

Electrical designers selecting automatic transfer switches for low-voltage switchboards, and panel builders.

Document contents

  1. Range Presentation
  2. Features
  3. Ordering Code
  4. Order Information
  5. Technical Parameters: Electrical performance
  6. Control function
  7. Controller protection and setting functions
  8. Dimensions (mm)
  9. Product Features

Publication details

Authors
Himel
Publisher
Himel
Year
Year not stated
Document language
Unverified
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Himel Himel HDQ3HB Transfer Switch Equipment, PDF pp.2-3. Himel. https://www.himel.com/assets/images/upload/catalogue/17173977871713877036.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.