ES-TECH International SUN-STS, model specification table
ES-TECH International
A product page from South Korean manufacturer ES-TECH International describing three models of its SUN-STS single-phase transfer switch in a 19-inch 2U rack chassis: RMRDS-5000S (23 A, 5 kVA), RMRDS-7500S (34 A, 7.5 kVA) and RMRDS-10KS (45 A, 10 kVA), with switching time below 8 ms.
On this page
Overview
The page presents the static transfer switch that ES-TECH International calls SUN-STS. The unit takes two separate power supplies at its input and keeps the load output fed when one of the lines fails. It is designed for 19-inch racks, and the manufacturer states that it is optimised for the power requirements of HFC (hybrid fibre-coaxial) networks, so cable and telecom network nodes are the primary target. Status is read from a large graphic LCD on the front panel. The manufacturer is headquartered in Hongseong, South Korea.
The specification table compares three models. All are single-phase (2 poles plus earth), work at 220 V ±15% input and output at 50/60 Hz, and use terminal blocks for input and output connections. Output current is given as 23 A (5 kVA) for RMRDS-5000S, 34 A (7.5 kVA) for RMRDS-7500S and 45 A (10 kVA) for RMRDS-10KS. Switching time is below 8 ms, the protection row reads 125% load for 2 hours, and rated capacity is for continuous use.
All three models share one chassis: 482 x 430 x 88 mm (WxDxH), 2U. Weights are 5 kg, 6 kg and 7.5 kg. The manufacturer states that capacity is easily changed by changing the switching device used; the common chassis follows from that approach. Operating temperature is 0 °C to +50 °C, relative humidity below 95% and noise below 36 dB.
Functionally the unit supports manual and automatic switching, stores events and allows the records to be reviewed later. The page gives no numeric data for the synchronisation window, transfer thresholds, communication interface, efficiency or applied standards. A switching time below 8 ms is shorter than a half cycle at 50 Hz (10 ms) and stays within the hold-up time of typical IT power supplies. In a data centre, devices of this class are used to connect single-corded rack equipment to two independent feeds.
Key points
- Models: RMRDS-5000S 23 A (5 kVA), RMRDS-7500S 34 A (7.5 kVA), RMRDS-10KS 45 A (10 kVA).
- Single-phase (2P + earth), 220 V ±15%, 50/60 Hz input and output.
- Switching time below 8 ms; manual and automatic switching.
- Protection: 125% load for 2 hours; rated capacity is for continuous use.
- Chassis: 482 x 430 x 88 mm (WxDxH), 19-inch 2U; terminal block connections.
- Weight: 5 kg, 6 kg and 7.5 kg.
- Environment: 0 °C to +50 °C, relative humidity < 95%, noise < 36 dB.
- Graphic LCD on the front panel and event logging.
Using it in design
- Use it to connect single-corded rack loads of 5-10 kVA to the A and B feeds, selecting the model from the rack current (23, 34 or 45 A).
- Compare the sub-8 ms switching time with the hold-up time of the load power supplies, and separately require that the two sources are kept synchronised.
- Because connections are by terminal block, design the in-rack PDU on the output separately, and select cable cross-section for the current on the 45 A model.
- The 50 °C upper operating temperature permits mounting on the hot aisle side; still confirm rear-of-rack temperature by measurement.
- The page gives no communication interface or standards compliance, so request written information from the manufacturer for DCIM integration and CE or KC certification.
Who should read it
Electrical engineers designing redundant rack-level supply and infrastructure teams operating single-corded equipment at telecom or edge nodes.
Document contents
- SUN-STS (Static Transfer Switch) introduction
- Features & Benefits
- Specifications: Input, Output, Rated capacity, Dimension, Weight, Environment
Publication details
- Authors
- ES-TECH International
- Publisher
- ES-TECH International
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
ES-TECH International ES-TECH International SUN-STS, model specification table. ES-TECH International. https://es-tech.co.kr/eng_web/power_item10.php
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.