Maverick Power Static Transfer Switches (STS) Data Sheet
Original title Maverick Static Transfer Switches datasheet STS-202605, PDF pp.1-2
Maverick Power
The technical data sheet for the Maverick Power STS family from 400 A to 1200 A: sub-cycle transfer, fully redundant design, cold-swappable module and key ratings.
On this page
Overview
The data sheet presents a blinkless transfer switch that uses power electronics to move between sources in as little as 4 milliseconds. The cold-swappable STS module can be completely replaced by one technician in 30 minutes, and the integrated bypass mode keeps connected loads powered during maintenance. The entire family is front-access only, so it can be installed directly against walls or adjacent equipment, suiting skid-mounted systems and compact electrical rooms.
The redundant design comprises two independent power paths, a fully redundant DC power bus, triple-redundant power supplies and redundant dual microprocessor boards and SCR drivers. On safety it lists plug-in or withdrawable molded case switches, a Kirk-key interlocked bypass, hot-swappable fans and power supplies. ATSM limits magnetic inrush; real-time SCR fault sensing and continuous internal sensor monitoring are included.
Standards: ITIC power acceptability curve compliance, UL 1008S listing (solid-state transfer switch) and FCC Part 15 Subpart B Class A. Key ratings: ampacity 400 A and 600 A, 800 A, and 1000 A and 1200 A; system voltage 208 to 480 V (400 to 800 A) and 380 to 480 V (1000 to 1200 A); withstand and close-on ratings of 50, 65 and 100 kA at 480 V and 50, 65 and 125 kA at 240 V; rated frequency 60 Hz; Type 1 enclosure; 99% efficiency at full load. Communications are Modbus RTU/TCP, EtherNet/IP, BACnet IP and DNP3.
Key points
- Transfer in as little as 4 ms; compliant with the ITIC power acceptability curve.
- The module is replaced by one technician in 30 minutes; the integrated bypass mode keeps loads powered.
- Front-only access: installation against walls or adjacent equipment.
- Fully redundant: dual independent power paths, DC power bus, triple-redundant power supplies, dual microprocessor boards and SCR drivers.
- Ampacity: 400 A and 600 A (84 x 48 x 32 in), 800 A (79 x 65 x 35 in), 1000 A and 1200 A (92 x 65 x 35 in).
- System voltage 208 to 480 V (400 to 800 A) and 380 to 480 V (1000 to 1200 A); rated frequency 60 Hz.
- Withstand and close-on ratings: 50, 65, 100 kA at 480 V; 50, 65, 125 kA at 240 V.
- 99% efficiency at full load; UL 1008S listed; Kirk-key interlocked bypass.
- Communications: Modbus RTU/TCP, EtherNet/IP, BACnet IP, DNP3.
Using it in design
- Check frequency compatibility: the product is rated for 60 Hz, so suitability on 50 Hz networks should be asked of the manufacturer separately.
- Select the 50, 65, 100 or 125 kA withstand rating against the fault current at the supply point.
- Front-only access removes rear service clearance from the electrical room layout, but the front access zone must be kept.
- Write the Kirk-key bypass sequence and the 30-minute module replacement time into the maintenance procedure.
- For monitoring, match Modbus, BACnet IP or DNP3 to the BMS and SCADA.
Who should read it
Electrical engineers designing dual-source critical distribution and teams writing STS specifications.
Document contents
- Sub-cycle transfer, cold-swappable module, front-only access
- Redundant design, safety, maximum uptime, standards and compliance
- Key specifications
Publication details
- Authors
- Maverick Power
- Publisher
- Maverick Power
- Year
- 2026
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Maverick Power (2026). Maverick Static Transfer Switches datasheet STS-202605, PDF pp.1-2. Maverick Power. https://maverickpwr.com/wp-content/uploads/2026/06/Static-Transfer-Switches-STS-Data-Sheet-1.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.