Hannibal STS Series datasheet
Original title Hannibal STS Series datasheet, PDF p.3
Hannibal Power and Technology
The STS Series datasheet from Hannibal Power and Technology describes thyristor-based static transfer switches in single-phase ratings of 16-150 A and three-phase ratings of 50-800 A; synchronous transfer takes less than 4 ms, unsynchronised transfer about 10 ms, and efficiency is above 99%.
On this page
Overview
The four-page datasheet describes the microprocessor-controlled STS Series static transfer switch. The unit continuously monitors two independent AC sources, checks whether voltage and frequency stay within limits and whether the sources are synchronised with each other. While the preferred source is within limits the critical load stays on it; when it leaves the limits the load moves to the other source. Switching is done by thyristors with no moving parts. Source priority is selected on the front panel, asynchronous transfer can be enabled or disabled, and a third input source is optional.
The single-phase series comes in 16, 32, 50, 63, 100 and 150 A ratings, with voltage options of 110, 127, 208, 220, 230, 240 and 265 Vac and a ±20% voltage window. The three-phase series covers 50, 63, 100, 150, 200, 300, 400, 600 and 800 A, eight voltage options between 200 and 600 Vac and a ±15% window. In both series the frequency range is 45-65 Hz and adjustable, and transfer starts when a source leaves the window. The transfer type is stated as break before make.
The technical table gives transfer time as less than 4 ms when synchronised and about 10 ms when unsynchronised; the general features section quotes the same parameters as under 5 ms (a quarter cycle at 50 Hz) and under 11 ms. Pole arrangement is selectable with or without neutral switching: 1 or 2 poles in single phase, 3 or 4 poles in three phase. The overload steps are 100-110% continuous, up to 125% for 10 minutes, up to 150% for 1 minute, up to 200% for 10 seconds and above 200% for 250 ms.
Mechanical data is limited. The smaller single-phase ratings are 19-inch 1U and 2U rack units with net weights of 3 to 8 kg, and the larger ratings use a 500 x 450 x 1000 mm cabinet. Three-phase cabinets are listed in four sizes from 500 x 450 x 1000 mm up to 2100 mm in height, and the reader is referred to the manufacturer for weights. The standards are EN 62310-1, -2 and -3. Ingress protection is IP20 or IP21 as standard and up to IP66 as an option. Options include a maintenance bypass switch, redundant fans, earth-fault protection, Modbus RTU and SNMP.
Key points
- Single-phase ratings: 16, 32, 50, 63, 100, 150 A; three-phase ratings: 50, 63, 100, 150, 200, 300, 400, 600, 800 A.
- Transfer time: under 4 ms synchronised, about 10 ms unsynchronised (under 5 ms and under 11 ms in the general features).
- Efficiency above 99%; crest factor 3:1; transfer type break before make.
- Voltage window ±20% single phase, ±15% three phase; frequency window 45-65 Hz, adjustable.
- Overload: 100-110% continuous, up to 125% for 10 minutes, up to 150% for 1 minute, up to 200% for 10 seconds, above 200% for 250 ms.
- Pole arrangement: 1 or 2 poles single phase, 3 or 4 poles three phase (with or without neutral switching).
- Cooling: natural in single phase; dual-redundant forced fans in three phase, natural cooling optional.
- Operating temperature 0-50 °C, storage -10 to 70 °C, relative humidity below 90% non-condensing.
- Standards EN 62310-1, EN 62310-2, EN 62310-3; ingress protection IP20/IP21, up to IP66 optional.
- Communication: RS232 and dry contact standard; RS485, TCP/IP and SNMP optional; 4 dry contacts, 2x16 LCD panel.
Using it in design
- Compare the load's power-supply hold-up time with the 4 ms synchronised and roughly 10 ms unsynchronised transfer times; leave asynchronous transfer enabled only if the load tolerates it.
- In TN-S systems and where the two sources have separately earthed neutrals, choose the 2-pole or 4-pole arrangement with neutral switching.
- Set the current rating from load current and the overload curve (10 minutes at 125%, 1 minute at 150%), and coordinate the 250 ms limit above 200% with the clearing time of the downstream protective device.
- Add the optional maintenance bypass switch to the specification so the load stays energised during servicing.
- Three-phase cabinet weights are not published, so obtain them from the manufacturer for floor loading; cabinet sizes run from 500 x 450 x 1000 mm up to 2100 mm in height.
Who should read it
Electrical designers selecting an STS for dual-fed critical loads and engineers building redundancy architectures.
Document contents
- Static Transfer Switch STS Series
- General specifications
- Electrical specifications
- Input Specification: Single Phase
- Mechanical Specification: Single Phase
- General Specification
- Input Specification: Three Phase
- Mechanical Specification: Three Phase
- Options
Publication details
- Authors
- Hannibal Power and Technology
- Publisher
- Hannibal Power and Technology
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document