Kemsan military-class static switch KSTS33-RACK technical specification

Original title Kemsan military-class static switch KSTS33-RACK technical specification image

Kemsan

The KSTS33-RACK specification sheet from Eskişehir-based Kemsan describes a rack-mount three-phase military-class static transfer switch in 20, 30 and 40 kW ratings: transfer in under 4 ms between synchronous sources and under 10 ms between asynchronous sources, efficiency above 98% and an RFI level to MIL-STD-461.

On this page

Overview

The sheet is the bilingual Turkish and English specification table for the KSTS33-RACK static transfer switch made by Kemsan (Kaynak Elektronik) in Turkey. The unit comes in three models rated in kW: 20 kW, 30 kW and 40 kW; no rated current appears in the table. The operating principle is static, using semiconductor technology. Input and output are 3 phases plus neutral at 115/200, 220/380 or 254/440 VAC and 50, 60 or 400 Hz. The 400 Hz option shows that the unit is also aimed at aviation and defence power systems.

The voltage window is adjustable within ±15% and the frequency window within ±5%; upper and lower limits for input voltage and frequency and the phase-balance protection are adjustable as well. Transfer time is under 4 ms between synchronous sources and under 10 ms between asynchronous sources. Five transfer modes are defined: delay, current, flying (adjustable time), synchronous and redundant. Efficiency is above 98%. Overload capability is 60 seconds in the 101-200% range, and the unit has over-temperature protection, overcurrent protection with a fuse and electronic short-circuit protection.

Physically the unit measures 427 x 527 x 133.35 mm (W x D x H); the height corresponds to 3U in a 19-inch rack. Weight is 23 kg for the 20 and 30 kW models and 28 kg for the 40 kW model. Operating temperature is -20 °C to +50 °C, humidity below 95% non-condensing and operating altitude up to 2000 m. The protection class is selectable between IP20 and IP54. The unit offers a graphical LCD, LEDs for inputs, output, communication and errors, a memory of the last 99 warnings, RS232/RS422/RS485 communication (selectable, standard) and optional SNMP/Modbus.

Key points

  1. Model KSTS33-RACK; three ratings: 20 kW, 30 kW, 40 kW.
  2. Input and output 3 phases plus neutral; 115/200, 220/380 or 254/440 VAC (adjustable ±15%); 50/60/400 Hz (adjustable ±5%).
  3. Transfer time: under 4 ms for synchronous sources, under 10 ms for asynchronous sources.
  4. Efficiency above 98%; overload 101-200% for 60 seconds.
  5. Five transfer modes: delay, current, flying, synchronous, redundant.
  6. Dimensions 427 x 527 x 133.35 mm; weight 23 kg (20 and 30 kW), 28 kg (40 kW).
  7. Operating environment -20 °C to +50 °C, humidity below 95%, up to 2000 m; protection class IP20 to IP54.
  8. RFI level MIL-STD-461; communication RS232/RS422/RS485, optional SNMP/Modbus; memory of 99 warnings.

Using it in design

  • Consider it as an in-rack STS between two UPS paths for dual-fed 20-40 kW rack rows or single-corded critical loads; add its 3U height to the cabinet plan.
  • Ratings are in kW, so obtain the rated current at the chosen voltage from the manufacturer and select the supply breakers accordingly.
  • Compare the transfer time of up to 10 ms between asynchronous sources with the hold-up time of IT power supplies; keep the sources synchronised where possible and use the synchronous transfer mode.
  • Set the voltage and frequency windows (within ±15% and ±5%) against UPS output tolerances and the acceptance limits of the load.
  • The -20 °C to +50 °C operating range and protection up to IP54 suit unconditioned containerised or field-deployed data centres.
  • On defence projects with electromagnetic compatibility requirements, match the MIL-STD-461 declaration against the specification.

Who should read it

Electrical designers selecting rack-mount STS units and engineers working on defence, containerised and field-deployed data-centre projects.

Document contents

  1. Input Specifications
  2. Output Specifications
  3. Protection
  4. Physical Specifications
  5. General Specifications

Publication details

Authors
Kemsan
Publisher
Kemsan
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Kemsan Kemsan military-class static switch KSTS33-RACK technical specification image. Kemsan. https://www.kemsan.com.tr/uploads/sts2-jpg.jpg

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.