Technical guideFree to readYear not stated

Dotvolt Volt EX Series 40/60/80 kVA 3/3 Online UPS datasheet

Dotvolt

A two-page datasheet from Dotvolt for the 40, 60 and 80 kVA three-phase online UPS models of its Volt EX series: output power factor 1 (40/40, 60/60, 80/80 kVA/kW), 96% efficiency in online mode, 99% in ECO mode and parallel operation of up to 4 units.

On this page

Overview

The datasheet describes the mid-power band of Dotvolt's Volt EX family. All three models deliver active power equal to their kVA rating: 40 kVA / 40 kW, 60 kVA / 60 kW and 80 kVA / 80 kW. The first page lists the headline features: DSP-based control, a 5-inch colour touch screen, silicon carbide diodes to raise efficiency, dual mains input, a powerful battery charger with adjustable current, a flexible battery count and built-in mains input, bypass input, output and maintenance bypass breakers.

The technical table on the second page covers input, output, bypass, efficiency, system, communication, alarm, environmental, standards and dimension headings. Input and output are 3 x 380/400/415 VAC (3Ph+N); the input is accepted from -30% to +20% of nominal voltage and from 40 to 70 Hz. At full load the input power factor is at least 0.99 and current distortion is below 3%. Output voltage distortion is at most 1% on linear load and 3% on non-linear load.

Overload capability is stepped: 1 hour at 100-110%, 10 minutes at 111-125%, 1 minute at 126-150% and 400 ms above 150%. The bypass line carries more than 130% for 1 minute and its voltage window is adjustable. Efficiency is printed as single points: 96% in online and battery mode and 99% in ECO mode. The sheet has no numeric rows for battery block count, charge voltage or charge current.

Environmental conditions are 0-40 °C, 0-95% non-condensing relative humidity and altitude up to 1500 m, with IP20 protection. IEC/EN 62040-1 is cited for safety and IEC/EN 62040-2 Category C3 for EMC. The dimension row prints two cabinet sizes (300 x 815 x 1000 mm and 360 x 790 x 1010 mm, WxDxH) and three net weights (250, 108 and 113 kg). The PDF metadata title carries the name of the 100-200 kVA sheet, while both visible pages belong to the 40/60/80 kVA family.

Key points

  1. Models: 40 kVA / 40 kW, 60 kVA / 60 kW, 80 kVA / 80 kW; output power factor 1.
  2. Input: 3 x 380/400/415 VAC (3Ph+N), voltage range -30% to +20%, frequency 40-70 Hz, power factor ≥ 0.99, THDi < 3% at full load.
  3. Efficiency: 96% online, 96% battery mode, 99% ECO mode.
  4. Overload: 1 hour at 100-110%, 10 minutes at 111-125%, 1 minute at 126-150%, 400 ms above 150%; bypass above 130% for 1 minute.
  5. Output: ±1% voltage regulation in battery mode, THDv ≤ 1% on linear and ≤ 3% on non-linear load, crest factor 3:1.
  6. Up to 4 UPSs in parallel; RS232/USB standard, SNMP optional.
  7. Environment: 0-40 °C, 0-95% relative humidity (non-condensing), altitude ≤ 1500 m, IP20.
  8. Standards: IEC/EN 62040-1 and IEC/EN 62040-2 Category C3.
  9. Dimension row: 300 x 815 x 1000 mm and 360 x 790 x 1010 mm; net weights printed as 250, 108 and 113 kg.

Using it in design

  • In small and medium data rooms, take kW capacity equal to the kVA rating and build N+1 redundancy within the 4-unit parallel limit.
  • Use input power factor 0.99 and THDi < 3% for upstream sizing and 96% online efficiency for the heat load (about 4% loss at 80 kW load).
  • If the energy model relies on the 99% ECO efficiency, record in the design decision that the load is fed through bypass and protection is reduced.
  • Battery string voltage and charge current are absent from this sheet, so obtain model-level battery data from the manufacturer before sizing batteries.
  • Use the manufacturer's dimensioned drawing to map the dimension and weight values to each model, and check floor loading with the weight including batteries.

Who should read it

Electrical designers selecting a UPS in the 40-80 kVA range, engineers writing specifications for small and medium data rooms and procurement teams comparing suppliers.

Document contents

  1. Product features
  2. Giriş (Input)
  3. Çıkış (Output)
  4. Bypass
  5. Verim (Efficiency)
  6. Sistem Özellikleri (System features)
  7. Haberleşme (Communication)
  8. Alarm
  9. Çevresel (Environmental)
  10. Uluslararası Güvenlik Standartları (International safety standards)
  11. Boyutlar ve Ağırlık (Dimensions and weight)

Publication details

Authors
Dotvolt
Publisher
Dotvolt
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Dotvolt Dotvolt Volt EX Series 40/60/80 kVA 3/3 Online UPS datasheet. Dotvolt. https://www.dotvolt.com.tr/wp-content/uploads/2024/04/40-60-80-kVA-3-3-Data-Sheet-20230703.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.