Dotvolt Volt EX 100/120/180/200 kVA 3/3 technical sheet
Original title Dotvolt Volt EX 100/120/180/200 kVA 3/3 technical sheet, PDF p.2
Dotvolt
A two-page technical sheet published by Dotvolt for the 100, 120, 180 and 200 kVA models of its Volt EX three-phase in, three-phase out online UPS range: output power factor 1, 95.5% efficiency in online mode, 98.5% in ECO mode and parallel operation of up to 4 units.
On this page
Overview
The sheet covers the upper power band of the Volt EX family from Dotvolt, a manufacturer based in Türkiye. All four models deliver kW equal to kVA (100 kVA / 100 kW, 120 / 120, 180 / 180, 200 / 200). The first page lists the design features: front-access plug-in power modules, dual mains input, built-in mains input, bypass input, output and maintenance bypass breakers, a 7-inch touch screen, emergency power off (EPO), generator compatibility and a 50/60 Hz frequency converter function.
The table on the second page is organised under input, output, bypass, efficiency, battery, system, communication, alarm, environmental and dimension headings. Input and output are both 3 x 380/400/415 VAC (3Ph+N). The input voltage window depends on load: 110-300 VAC at 50% load and 178-276 VAC at 100% load. Input power factor is at least 0.99 at full load and input current distortion is below 4%. Output voltage regulation is typically within 1% on balanced load and 2% on unbalanced load.
The battery side is flexible: the number of 12 V blocks can be set between 32 and 40, which gives a battery bus between ±192 V and ±240 V. Float charge is 2.28 VDC per cell (adjustable from 2.25 to 2.33), boost charge is 2.35 VDC per cell, and temperature compensation is included. The table carries two separate charge-current rows: selectable maximums of 24, 30 and 54 A depending on rating, and 1, 2 and 3.5 A for the standard model.
Efficiency is given as single points (online 95.5%, battery mode 94.5%, ECO 98.5%) with no curve against load. The dimension row prints 1000 x 430 x 1200 mm (WxDxH) and 200 kg net for 100-120 kVA, and 1000 x 6000 x 1200 mm and 265 kg net for 180-200 kVA. The 6000 mm depth appears in the sheet in that form; a dimensioned drawing from the manufacturer is needed for layout work. The sheet does not say whether the weight includes batteries.
Key points
- Models: 100 kVA / 100 kW, 120 kVA / 120 kW, 180 kVA / 180 kW, 200 kVA / 200 kW; output power factor 1.
- Input: 3 x 380/400/415 VAC (3Ph+N), 110-300 VAC at 50% load, 178-276 VAC at 100% load; frequency range 40-70 Hz; power factor ≥ 0.99; THDi < 4%.
- Efficiency: 95.5% online, 94.5% in battery mode, 98.5% in ECO mode.
- Overload: 110% for 1 hour, 111-125% for 10 minutes, 126-150% for 1 minute, above 150% for 200 ms.
- Output voltage distortion at most 2% on linear load and 4% on non-linear load; crest factor 3:1; transfer time 0 ms.
- Battery: 32-40 blocks of 12 V (±192 V to ±240 V), float 2.28 VDC/cell, boost 2.35 VDC/cell, typical recharge to 90% capacity in 4 hours.
- Up to 4 units in parallel; SNMP is optional, RS232/USB is standard.
- Environment: 0-40 °C, 0-90% relative humidity (non-condensing), altitude up to 1000 m, IP20.
- Standards: IEC/EN 62040-1 and IEC/EN 62040-2 Category C3.
- Net weight: 200 kg for 100-120 kVA, 265 kg for 180-200 kVA.
Using it in design
- With power factor 1, take kW capacity equal to the kVA rating, and apply the 4-unit parallel limit when sizing N+1.
- Use input power factor 0.99 and THDi < 4% for generator and transformer sizing and 95.5% online efficiency for UPS losses; request a curve from the manufacturer for part-load efficiency.
- In battery room design, carry the 32-40 blocks per string option and the chosen charge-current ceiling into the autonomy and recharge-time calculation.
- As an EMC Category C3 product, place the unit as second-environment (industrial) equipment and assess filtering where it shares a space with sensitive devices.
- Lay out the 180-200 kVA cabinet from the manufacturer's dimensioned drawing, not from the 6000 mm depth printed in the sheet, and obtain the weight with batteries separately for floor loading.
- For sites above 1000 m or rooms above 40 °C, request derating factors from the manufacturer.
Who should read it
Electrical designers selecting a UPS in the 100-200 kVA range, engineers writing specifications and procurement teams assessing a local supplier in the Turkish market.
Document contents
- Product features
- Giriş (Input)
- Çıkış (Output)
- Bypass
- Verim (Efficiency)
- Akü (Battery)
- Sistem Özellikleri (System features)
- Haberleşme (Communication)
- Alarm
- Çevresel (Environmental)
- Uluslararası Güvenlik Standartları (International safety standards)
- Boyutlar ve Ağırlık (Dimensions and weight)
Publication details
- Authors
- Dotvolt
- Publisher
- Dotvolt
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Dotvolt Dotvolt Volt EX 100/120/180/200 kVA 3/3 technical sheet, PDF p.2. Dotvolt. https://www.dotvolt.com.tr/wp-content/uploads/2024/04/100-120-180-200-kVA-3-3-Data-Sheet-20230622.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.
