Sunwoda UPS Lithium Battery for Data Centers: Parameters
Original title Sunwoda UPS Lithium Battery for Data Centers: Parameter
Sunwoda Energy
Sunwoda's SSI data-centre UPS lithium battery is a lead-acid replacement; the two cabinets give 70 kW rated/300 kW maximum continuous discharge at 140 Ah, and 25 kW/50 kW at 100 Ah.
On this page
Overview
The page presents Sunwoda Energy's UPS lithium battery family for data centres. The manufacturer says it can replace lead-acid directly with no custom UPS development, that the modular design allows independent maintenance and is compatible with old and new batteries, and that maximum 4C discharge meets a 15-minute backup requirement. Listed uses include finance, healthcare, government, education, petrochemical and precision manufacturing.
The parameter section gives two models. For SSI-480140A4F1, rated power is 70 kW, maximum continuous discharge power 300 kW, rated capacity 140 Ah and dimensions 600 x 1000 x 2050 mm (W x D x H). For SSI-480100A1F1, rated power is 25 kW, maximum continuous discharge power 50 kW, rated capacity 100 Ah and dimensions 600 x 600 x 2050 mm. Both communicate by RS485, CAN, Ethernet and dry contact.
The page does not give cell chemistry, voltage window, weight or safety certifications; those belong in the product information file. The power values describe discharge capability and should enter runtime calculations together with rated capacity.
Key points
- Two models: SSI-480140A4F1 and SSI-480100A1F1.
- SSI-480140A4F1: 70 kW rated, 300 kW maximum continuous discharge, 140 Ah, 600 x 1000 x 2050 mm.
- SSI-480100A1F1: 25 kW rated, 50 kW maximum continuous discharge, 100 Ah, 600 x 600 x 2050 mm.
- Maximum 4C discharge, aimed at a 15-minute backup requirement.
- Direct replacement for lead-acid; no custom UPS development needed.
- Communication: RS485, CAN, Ethernet and dry contact.
Using it in design
- Check runtime against the cabinet's maximum continuous discharge power and capacity together; for a 15-minute target, power depends on the maximum value more than the rated one.
- In a lead-acid replacement, confirm the UPS manufacturer supports lithium and that charging parameters match.
- Cabinets are 600 mm wide and 2050 mm high; reflect this in the battery room layout and floor loading plan.
- Include the BMS communication (RS485, CAN, Ethernet, dry contact) in the monitoring system design.
Who should read it
Electrical designers selecting data-centre UPS batteries or evaluating a move from lead-acid to lithium.
Publication details
- Authors
- Sunwoda Energy
- Publisher
- Sunwoda Energy
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Sunwoda Energy Sunwoda UPS Lithium Battery for Data Centers: Parameter. Sunwoda Energy. https://sunwodaenergy.com/network/ups-lithium-battery-for-data-centers.html
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.