Technical guideFree to readYear not stated

Sunwoda Network Energy: SSI A6F1 and A10F2 Data-Centre Lithium Battery Specifications

Original title Sunwoda Network Energy: A6F1 and A10F2 specifications

Sunwoda Energy

Sunwoda's data-centre UPS and HVDC batteries SSI-480140-A6F1 (512 V, 140/70 Ah) and SSI-576166-A10F2 (576 V, 166/83 Ah) are specified with voltage window, maximum continuous discharge power, size and weight.

On this page

Overview

The brochure presents two lithium-ion battery families said to meet 100 kW to 2.5 MW UPS or HVDC power demand: SSI-480140-A6F1 and SSI-576166-A10F2. Both are offered for medium and large data centres and edge data centres, with emphasis on high efficiency, safety, modular design and easy maintenance. Much of the brochure is a list of data-centre backup projects worldwide.

The SSI-480140-A6F1 family has 512 V nominal voltage (maximum 576 V, minimum 432 V). Capacity columns are 140 Ah and 70 Ah, with nominal energy of 71.68 and 35.84 kWh. At 25 C, maximum sustained discharge power is 386 and 193 kW, maximum sustained discharge current 860 and 430 A, and charging current 7-70 A. Size is 600 x 900 x 2250 mm (47U) and weight 1100 and 680 kg.

The SSI-576166-A10F2 family is 576 V nominal (maximum 648 V, minimum 486 V). Capacity columns are 166 Ah and 83 Ah, nominal energy 95.6 and 47.8 kWh, maximum sustained discharge power at 25 C 760 and 380 kW, discharge current 1563 and 782 A, and charging current 8.3-83 A. Size is 800 x 800 x 2250 mm (47U) and weight 1400 and 900 kg. Both families are fan cooled, IP20, rated for 0-40 C operation, with power reduced outside 20-30 C and above 2000 m; the altitude limit is 3000 m.

Key points

  1. SSI-480140-A6F1: 512 V nominal (432-576 V), 140 Ah and 70 Ah, 71.68 and 35.84 kWh.
  2. SSI-576166-A10F2: 576 V nominal (486-648 V), 166 Ah and 83 Ah, 95.6 and 47.8 kWh.
  3. Maximum sustained discharge power (25 C): 386/193 kW (A6F1) and 760/380 kW (A10F2).
  4. Maximum sustained discharge current: 860/430 A (A6F1) and 1563/782 A (A10F2).
  5. Charging current: 7-70 A (A6F1) and 8.3-83 A (A10F2).
  6. Size: 600 x 900 x 2250 mm (47U), 1100/680 kg and 800 x 800 x 2250 mm (47U), 1400/900 kg.
  7. Fan cooling, IP20, 0-40 C; power reduced outside 20-30 C and above 2000 m; storage -20 to 60 C, recommended 15-25 C.
  8. Communication RS485, CAN, Ethernet and dry contact; LCD display; front maintenance.

Using it in design

  • Compare the DC bus voltage windows (432-576 V and 486-648 V) with the UPS battery voltage range and choose the family to match the UPS DC link.
  • Check runtime against UPS load power and maximum sustained discharge power, not nominal energy alone; power values depend on 25 C.
  • Each cabinet weighs 680-1400 kg, so verify floor loading and cabinet layout early.
  • Design cooling to hold the battery room in the 20-30 C band; power derates outside it.
  • Match the charging current ceiling to the UPS charger and source capacity.

Who should read it

Electrical designers and specification engineers selecting lithium batteries for data-centre UPS and HVDC systems.

Document contents

  1. Project references
  2. SSI-480140-A6F1 series parameters
  3. SSI-576166-A10F2 series parameters
  4. Telecom solution (48 V)

Publication details

Authors
Sunwoda Energy
Publisher
Sunwoda Energy
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Sunwoda Energy Sunwoda Network Energy: A6F1 and A10F2 specifications. Sunwoda Energy. https://en.sunwodaenergy.com/static/upload/file/20260619/1781849481178590.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.