Technical guideFree to read2023

IMP Pumps NMT MAX II technical data 2023

Original title IMP Pumps: NMT MAX II Technical Data 2023

IMP Pumps

The IMP Pumps NMT MAX II 2023 technical data covers electronically controlled wet-running circulators for heating, air conditioning and cooling; Qmax 72.7 m³/h, Hmax 18.9 m, DN32-DN100 and EEI of 0.20 or lower.

On this page

Overview

This 2023 technical catalogue from Slovenian manufacturer IMP Pumps presents the NMT MAX II wet-running circulators with permanent-magnet (ECM) electronic control. The pumps suit heating, air conditioning, closed cooling circuits and industrial systems. Qmax is 72.7 m³/h and Hmax 18.9 m; connection sizes are DN32, 40, 50, 65, 80 and 100, nominal pressure PN6/10, supply 1 x 230 V 50 Hz and protection class IP 44.

The model name encodes connection size and maximum head; for example 40/120 means DN40 and 12 m. The series is split by communication option into S, U and C versions. Standard modes are auto, proportional pressure, constant pressure, fixed speed and night mode, with dry-run detection and automatic venting. The S, U and C versions add inputs and protocols progressively, including start/stop input, relay output, 0-10 V, 4-20 mA, PWM, Modbus (RS485 and TCP/IP), web server and BACnet.

The catalogue holds a table of model code, EEI, fitting length, pipe size, pressure class and maximum power (Pmax); for example Pmax is 110 W for the 40/40 and 1,550 W for the 65/180. EEI values are mostly 0.20 or lower (0.21 for the 40/180). Hydraulic performance is given as curves. Permissible media are water or water-glycol (parameters to be checked above 20% glycol) at -10 to +110 °C.

The catalogue explains efficiency requirements under the ErP regulation: an energy index of at most 0.23 (Part 2) from 2015 and the same limit in a second step from 2020. The scope covers heating, air conditioning and cooling circulation and contains no data-centre-specific calculation.

Key points

  1. Qmax 72.7 m³/h, Hmax 18.9 m; DN32, 40, 50, 65, 80 and 100.
  2. PN6/10; 1 x 230 V, 50 Hz; IP 44; insulation class F.
  3. The model name encodes connection size and maximum head (40/120 = DN40, 12 m).
  4. Modes: auto, proportional pressure, constant pressure, fixed speed, night mode; dry-run detection.
  5. Communication options S, U, C: 0-10 V, 4-20 mA, PWM, Modbus (RS485 and TCP/IP), web server and BACnet.
  6. EEI mostly 0.20 or lower (0.21 for the 40/180).
  7. Maximum power examples: 110 W for the 40/40 and 1,550 W for the 65/180.
  8. Medium temperature -10 to +110 °C; glycol mixtures above 20% need parameter checks.

Using it in design

  • When selecting circulators for chilled-water loops, compare the maximum head in the model name with design-point pressure loss and check the performance curve.
  • Choose proportional or constant pressure mode by loop type and specify the Modbus or BACnet communication version if the BMS needs it.
  • For circuits above 20% glycol, write a manufacturer parameter check into the specification.
  • Use EEI ≤ 0.20 as the ErP efficiency target in pump selection.
  • Check capacity for main data-centre chilled-water loops; these pumps are limited to DN100 and 72.7 m³/h and suit auxiliary circuits.

Who should read it

Mechanical designers and procurement engineers selecting circulation pumps for chilled-water and auxiliary water circuits.

Document contents

  1. ErP regulation
  2. About the company
  3. About products
  4. NMT MAX II overview
  5. Transition from NMT MAX to NMT MAX II
  6. Electrical connection and glands
  7. Model overview
  8. Display operation
  9. Performance curves
  10. Model options
  11. Dimensions

Publication details

Authors
IMP Pumps
Publisher
IMP Pumps
Year
2023
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

IMP Pumps (2023). IMP Pumps: NMT MAX II Technical Data 2023. IMP Pumps. https://imp-pumps.com/wp-content/uploads/2021/11/Katalog_NMT_MAX_II_ANG_mail-4.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.