Layer Electronics Proton technical data
Original title Layer Electronics Proton technical data, PDF pp.1–2
Layer Electronics
Layer Electronics's Proton series is a single-phase, VFI-class, sine-wave UPS family from 0.6 to 6.5 kVA, with efficiency above 92%, a static switch under 2 ms and 150% overload for 1 minute.
On this page
Overview
The two-page datasheet lists the Proton model codes from P-401 to P-481 and the power steps of 0.6, 1, 1.5, 2, 3, 4, 5 and 6.5 kVA. Each power step has three model variants corresponding to 1, 2 and 3 hours of stored energy time. The series has single-phase input and output, VFI class (EN 62040-3) and sine-wave output.
Input voltage is 220/230/240 V +/-20% (100-127 V on request) and frequency 50/60 Hz +/-5%. Output voltage is +/-1%, frequency +/-0.2%, harmonic distortion under 2% and crest factor 2:1 (non-linear load 75%). Overload capability is 125% for 10 minutes, 150% for 1 minute and 200% for 0.1 second. Efficiency is above 92% and the static switch mains-to-UPS transfer time is under 2 ms.
The battery type is sealed lead-acid; NiCd, Li-Ion and NaNiCl2 are available on request. Restored energy time is 4 hours to 90% charge level. Protections cover overload, overtemperature, battery, input and inverter voltage limits and synchronism; short circuit is electronically protected and an EMI/RFI filter is fitted. LEDs and alarms report mains, output, battery, overload and fault states; the computer interface is RS232, RS485, SNMP and CAN (optional).
Dimensions and weight are not given in the datasheet and are provided on request. Operating temperature is 0-50 C, humidity 0-95% non-condensing, noise under 60 dBA at 1 m and protection IP20. Standards are EN 60146-1-1 and EN IEC 62040-1, -2 and -3, with CE marking under 2014/30/EU, 2014/35/EU and 2011/65/EU. The stored energy time is listed as 1, 2 and 3 hours without a stated load condition and should not be taken as a runtime guarantee.
Key points
- Power steps 0.6, 1, 1.5, 2, 3, 4, 5 and 6.5 kVA; models P-401 to P-481.
- Each step has variants with 1, 2 and 3 hours of stored energy time.
- Single-phase input 220/230/240 V +/-20%, 50/60 Hz +/-5%; output +/-1%, +/-0.2%.
- Sine-wave output; harmonic distortion under 2%; crest factor 2:1.
- Overload 125% for 10 min, 150% for 1 min, 200% for 0.1 s.
- Efficiency above 92%; static switch under 2 ms; class VFI.
- Sealed lead-acid battery; 90% recharge in 4 hours.
- Operation 0-50 C, humidity 0-95%, IP20, noise under 60 dBA.
- Dimensions and weight are provided on request.
Using it in design
- Do not take the stored energy time (1-3 hours) as runtime without a stated load; run the battery calculation with your actual load.
- Because dimensions and weight are not in the datasheet, request them from the manufacturer for layout.
- Compare the 2:1 crest factor limit on non-linear load with the peak current of the IT load.
- Take efficiency as above 92% and ask the manufacturer for the load point for heat-load calculations.
- For 100-127 V sites, note in the specification that this voltage is available on request.
Who should read it
Designers looking for single-phase VFI-class UPS for small industrial and critical loads.
Document contents
- Technical data: Proton series (model, input, output, batteries, protections, signals, environment, dimensions, classification, compliance)
Publication details
- Authors
- Layer Electronics
- Publisher
- Layer Electronics
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Layer Electronics Layer Electronics Proton technical data, PDF pp.1–2. Layer Electronics. https://layer.it/main/media/2023/10/Proton-eng.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.