nJoy Code 2000 official technical datasheet
Original title nJoy Code 2000 official technical datasheet, PDF pp.1–2
nJoy
The nJoy Code 2000 is a 2000 VA / 1200 W rack line-interactive UPS with simulated sine output, typical 4 ms (max 10 ms) transfer time, 17 minutes of backup at 25 percent load and a weight of 14.4 kg.
On this page
Overview
The datasheet presents the nJoy Code 2000 (PN: UPLI-LI200CO-AZ01B). It is a line-interactive UPS rated 2000 VA / 1200 W in a rack design. Input is single phase with ground, nominal 230 V AC, with an accepted range of 162-290 V AC and automatic 50 or 60 Hz sensing. In battery mode the output is a simulated sine wave, deviation is 10 percent and frequency is 50 or 60 Hz ± 1 Hz.
Transfer time from AC mode to battery mode is typically 4 ms and at most 10 ms. Efficiency is 95 percent or higher in AC mode and 60 percent or higher in battery mode, with a fully charged battery. Voltage correction uses boost and buck AVR, and the unit also offers off-mode charging, cold start and automatic restart when AC returns. Protections cover overload, discharge and overcharge. An LCD shows UPS status, load and battery level, and input and output voltage.
The battery set is two GP09122L batteries with a maximum charging current of 1 A, and recovery of the internal battery to 90 percent capacity takes 4 to 6 hours. Battery runtime is 17 minutes at 25 percent load, 3.7 minutes at 50 percent, 1.5 minutes at 75 percent and 0.6 minutes at full load. The output side has 8 IEC C13 outlets and the input has one IEC-320 C14. Management is through a USB port.
Physically the unit is 438 x 300 x 86 mm and 14.4 kg, with IP20 protection, noise below 45 dB and humidity of 0-90 percent (non-condensing) at 0-40 °C. The document describes an office and network rack class product, not a central data-centre UPS.
Key points
- Capacity 2000 VA / 1200 W; line-interactive; rack design.
- Input 230 V AC, single phase with ground; accepted range 162-290 V AC.
- Simulated sine output in battery mode; frequency 50 or 60 Hz ± 1 Hz.
- Transfer time typical 4 ms, max 10 ms; efficiency 95 percent or higher in AC mode and 60 percent or higher in battery mode.
- Battery: 2 x GP09122L; maximum charging current 1 A; 4-6 hours to 90 percent capacity.
- Runtime: 17 min at 25 percent load, 3.7 min at 50 percent, 1.5 min at 75 percent, 0.6 min at 100 percent.
- 8 IEC C13 outlets, one IEC-320 C14 input; USB management port.
- Size 438 x 300 x 86 mm, 14.4 kg; IP20; noise below 45 dB.
Using it in design
- Keep the load below 1200 W and check separately that the simulated sine output suits loads with active power factor correction (active PFC) supplies.
- With runtime limited to about 3.7 minutes at half load, pair the unit with software for controlled shutdown.
- Because of the 1 A charge current, include the 4-6 hour recharge time where outages are frequent.
- In the rack plan, allow for the 14.4 kg weight and the 8-outlet limit when distributing loads.
Who should read it
IT and electrical designers selecting small UPS units for network cabinets and office racks.
Publication details
- Authors
- nJoy
- Publisher
- nJoy
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
nJoy nJoy Code 2000 official technical datasheet, PDF pp.1–2. nJoy. https://cdn.njoy.global/hive_files/wp/products/1608473974dGVM8f.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.