nJoy Argus 3000 official technical datasheet

Original title nJoy Argus 3000 official technical datasheet, PDF pp.1–2

nJoy

The nJoy Argus 3000 is a 3000 VA / 1800 W, 2U rack line-interactive UPS with pure sine output, typical 4 ms transfer time, 8 IEC C13 outlets and 18 minutes of backup at 25 percent load.

On this page

Overview

The datasheet presents the nJoy Argus 3000 (PN: PWUP-LI300AG-CG01B). It is a line-interactive UPS rated 3000 VA / 1800 W in a 2U rack design. Input is nominal 230 V AC with an accepted range of 165-276 V AC, and 50 or 60 Hz is sensed automatically. Power factor is 0.6 or higher at nominal voltage and full load. In battery mode the output is pure sine, regulation is 10 percent, frequency is 50 or 60 Hz ± 1 Hz, and typical transfer time is given as 4 ms.

Voltage correction uses an AVR with one boost and one buck step. The output side has 8 IEC C13 battery-backed and surge-protected outlets plus RJ11/RJ45 in and out protection for modem, phone and LAN lines. Listed protections include overload, deep discharge, overcharge, over voltage, high temperature and input spike protection. The unit supports emergency power off (EPO), cold start, off-mode charging, generator compatibility and an SNMP card.

The battery set is four GP09122L batteries, and typical recharge time is 4 hours to 90 percent capacity. Battery runtime is 18 minutes at 25 percent load, 7.5 minutes at 50 percent, 4 minutes at 75 percent and under 2 minutes at full load. Management uses RS232 and HID USB ports, with software for monitoring and control over USB, LAN and the internet; the intelligent port is not included in the package.

Physically the unit is 400 x 438 x 88 mm (2U) and weighs 21.85 kg, with IP20 protection, 0-40 °C operation, 0-90 percent humidity (non-condensing) and noise below 50 dB. The document describes an office and network rack class product, not a central data-centre UPS.

Key points

  1. Capacity 3000 VA / 1800 W; line-interactive; 2U rack design.
  2. Input 230 V AC, accepted range 165-276 V AC; power factor 0.6 or higher at nominal voltage and full load.
  3. Pure sine output in battery mode, 10 percent regulation, typical transfer time 4 ms.
  4. AVR: 1 boost and 1 buck step.
  5. 8 IEC C13 outlets and RJ11/RJ45 line protection; EPO and SNMP card support.
  6. Battery: 4 x GP09122L; typical recharge 4 hours to 90 percent capacity.
  7. Runtime: 18 min at 25 percent load, 7.5 min at 50 percent, 4 min at 75 percent, under 2 min at 100 percent.
  8. Size 400 x 438 x 88 mm, 21.85 kg; IP20; 0-40 °C; noise below 50 dB.
  9. Certificate: 2011/65/EU (RoHS).

Using it in design

  • Keep the load list at or below 1800 W and compare load power factor with the 0.6 lower bound.
  • Read the runtime table against the real load: about 7.5 minutes at half load and under 2 minutes at full load; choose a larger class if longer runtime is needed.
  • Include the 2U space and 21.85 kg weight in the rack loading plan for network and office racks.
  • If remote monitoring is required, order the SNMP card separately; the intelligent port is not included in the package.

Who should read it

IT and electrical designers selecting small UPS units for network cabinets and office racks.

Publication details

Authors
nJoy
Publisher
nJoy
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

nJoy nJoy Argus 3000 official technical datasheet, PDF pp.1–2. nJoy. https://cdn.njoy.global/hive_files/wp/products/1600541469wgMQph.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.