Servo-Matik NETPRO-33P Technical Sheet: 300-800 kVA 3-Phase/3-Phase UPS
Original title Servo-Matik NETPRO-33P technical sheet; PDF technical specifications
Servo-Matik
Servo-Matik NETPRO-33P is a 300-800 kVA three-phase high-frequency online UPS: 0.8 output power factor, 93 percent efficiency, input THDi below 5 percent, 500-entry event memory, made in Turkey.
On this page
Overview
The document is the technical sheet for the Servo-Matik NETPRO-33P series: 300, 400, 500, 600 and 800 kVA three-phase-in, three-phase-out online UPS. The unit is true double conversion with a DSP-controlled IGBT rectifier and inverter and active power factor correction of 0.99 or better. General features include selectable input and output voltage and frequency, parallel/redundant operation, cold start, selectable charge current, standard static and manual bypass, a memory of 500 warning and event records, and RS232/RS485 connectivity.
Electrical values: nominal input is 220/380, 230/400 or 240/415 VAC (3 phase + neutral + PE), input voltage range is ±20 percent, frequency tolerance ±5 percent, input power factor 0.98-0.99 and THDi below 5 percent. Output is 380/400/415 VAC with ±1 percent tolerance, output power factor 0.8, crest factor 3:1 and THDv below 3 percent linear and 5 percent non-linear load. Overload is 10 minutes at 125 percent, 1 minute at 150 percent and bypass above 150 percent. Efficiency is 93 percent.
Batteries are maintenance-free dry type, standard 2 × 30 pieces of 12 VDC (variable). Operating temperature is 0 to 40 °C, humidity 0 to 95 percent non-condensing, altitude below 1000 m, noise below 75 dB at 1 m and protection class IP20. Dimensions (W × D × H, cm) are 78 × 126 × 190 for 300 kVA, 160 × 86.8 × 180 for 400 kVA, 219 × 81 × 203 for 500 and 600 kVA and 321.6 × 86.8 × 180 for 800 kVA; weight without batteries is 890, 1370, 1480, 1690 and 1750 kg. Standards are EN 62040-1, -2 and -3.
The document is a product data sheet; heat dissipation and an efficiency-versus-load curve are not given.
Key points
- 300, 400, 500, 600 and 800 kVA, three-phase in and out; DSP-controlled IGBT rectifier and inverter.
- Input voltage range ±20 percent, input power factor 0.98-0.99, THDi below 5 percent.
- Output 380/400/415 VAC, ±1 percent, output power factor 0.8, crest factor 3:1.
- THDv below 3 percent linear and 5 percent non-linear load.
- Overload: 10 min at 125 percent, 1 min at 150 percent, bypass above 150 percent.
- Efficiency 93 percent; 500 warning/event record memory.
- Standard battery 2 × 30 pieces of 12 VDC (variable).
- Weight without batteries 890 kg (300 kVA) to 1750 kg (800 kVA); noise below 75 dB; IP20.
Using it in design
- With an output power factor of 0.8 the 800 kVA model delivers 640 kW; check the load in kW.
- Calculate floor loading from the weight without batteries (890 to 1750 kg) plus battery weight.
- Use the dimension table to set UPS room layout and service access clearances.
- Use the input THDi (below 5 percent) and 0.98-0.99 power factor in generator and transformer sizing.
- Compare the noise level (below 75 dB) with the UPS room acoustic design.
Who should read it
Data-centre designers and specification engineers selecting large three-phase UPS in Turkey and neighbouring regions.
Document contents
- General features
- Optional features
- Technical specifications: input, output, static bypass, battery, general, communication, environment
- Physical parameters
Publication details
- Authors
- Servo-Matik
- Publisher
- Servo-Matik
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Servo-Matik Servo-Matik NETPRO-33P technical sheet; PDF technical specifications. Servo-Matik. https://servomatik.com/images/new_doc/pdf/en/ups-netpro33h-en.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.