Servo-Matik NETPRO-33H Technical Sheet: 10-40 kVA 3-Phase/3-Phase UPS

Original title Servo-Matik NETPRO-33H technical sheet; PDF technical specifications

Servo-Matik

Servo-Matik NETPRO-33H is a 10-30 kVA and 40 kVA three-phase high-frequency online UPS: 0.99 input power factor, 0.9 output power factor, 94 percent efficiency at 40 kVA, made in Turkey.

On this page

Overview

The document is the technical sheet for the NETPRO-33H series, a new-generation high-frequency online UPS from the Turkish manufacturer Servo-Matik. There are two pages: the 10, 15, 20 and 30 kVA models, and the 40 kVA model. The unit is true double conversion with a DSP-controlled IGBT rectifier and inverter and active power factor correction of 0.99 or better. General features include dual mains inputs, parallel/redundant operation, cold start, battery deep-discharge protection, standard static and manual bypass and RS232/USB connectivity.

Electrical values: nominal input is 220/380, 230/400 or 240/415 VAC (3 phase + neutral), input voltage range is 310 to 500 VAC, frequency tolerance is ±5 percent, input power factor is 0.99 and THDi is below 5 percent (below 3 percent in the general features). Output voltage tolerance is ±1 percent, output power factor is 0.9, crest factor is 3:1 and THDv is below 3 percent on linear and 5 percent on non-linear load. Overload for 10-30 kVA is 10 min at 110 percent, 1 min at 130 percent and bypass above 130 percent; for 40 kVA it is 60 min at 110 percent, 10 min at 125 percent and 1 min at 150 percent.

Efficiency is 89 percent for 10-30 kVA and 94 percent for 40 kVA. Batteries are maintenance-free dry type, adjustable 18 to 20 pieces (standard 20 × 12 VDC) for 10-30 kVA and 28-30-32 pieces for 40 kVA. Operating temperature is 0 to 40 °C, humidity 0 to 95 percent non-condensing, altitude below 1000 m, noise below 60 dB and protection class IP20. Standards are EN 62040-1, -2 and -3. Options include SNMP, programmable dry contacts, GPRS modem, Modbus, parallel scaling and isolation transformers.

The sheets are product data sheets; dimensions, weight and heat loss are not given in this document. Because the 10-30 kVA and 40 kVA rows carry different overload and efficiency values, the model-specific row should be used.

Key points

  1. 10, 15, 20, 30 and 40 kVA, three-phase in and out; DSP-controlled IGBT rectifier and inverter.
  2. Input 310 to 500 VAC, frequency tolerance ±5 percent, input power factor 0.99, THDi below 5 percent.
  3. Output voltage tolerance ±1 percent, output power factor 0.9, crest factor 3:1.
  4. THDv below 3 percent linear and 5 percent non-linear load.
  5. Efficiency 89 percent (10-30 kVA) and 94 percent (40 kVA).
  6. 10-30 kVA overload: 10 min at 110 percent, 1 min at 130 percent, bypass above; 40 kVA: 60 min at 110 percent, 10 min at 125 percent, 1 min at 150 percent.
  7. Battery: 18 to 20 pieces (10-30 kVA, standard 20 × 12 VDC), 28-30-32 pieces (40 kVA).
  8. 0 to 40 °C, below 1000 m, noise below 60 dB, IP20; EN 62040-1/-2/-3.

Using it in design

  • With an output power factor of 0.9 the 40 kVA model delivers 36 kW; check the load in kW.
  • Use the 310 to 500 VAC input window and 0.99 input power factor in generator sizing.
  • Compare the different overload curves of the 10-30 kVA and 40 kVA rows with load inrush.
  • Match battery piece count (18 to 20 or 28 to 32) with the UPS DC voltage window.
  • If parallel redundancy, SNMP and Modbus are required, list them as options in the specification.

Who should read it

Electrical designers and specification engineers selecting 10-40 kVA three-phase UPS in Turkey and neighbouring regions.

Document contents

  1. General features (10-30 kVA)
  2. Technical specifications (10-30 kVA)
  3. General features (40 kVA)
  4. Technical specifications (40 kVA)

Publication details

Authors
Servo-Matik
Publisher
Servo-Matik
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Servo-Matik Servo-Matik NETPRO-33H technical sheet; PDF technical specifications. Servo-Matik. https://servomatik.com/images/new_doc/pdf/en/ups-netpro33s-en.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.