RE&D PureWave T100H model specifications: 100 kVA / 100 kW UPS

Original title RE&D PureWave T100H model specifications

Renewable Energy & Drives (RE&D)

Renewable Energy & Drives (RE&D) PureWave T100H is a 100 kVA / 100 kW three-phase double-conversion online UPS at 208/120 V with unity output power factor, UL 1778 certified, efficiency up to 94 percent.

On this page

Overview

The document is the PureWave T100H product page on the Renewable Energy & Drives site (part of Severn Drives & Energy). The T100H is a double-conversion online model in the low-voltage modular UPS family: three-phase in, four-wire out, 100 kVA and, with unity output power factor, 100 kW. Input and output are 208/120 or 220/127 Vac (3Ph+N+PE), and the stated market is the United States.

The electrical figures are: input operating range 66 to 166 Vac at 40 percent load and 96 to 166 Vac at 100 percent load; input power factor of 0.99 or better; input current distortion of 3 percent or less on non-linear load. Output voltage regulation is ±1 percent and voltage distortion is 2 percent on linear and 5 percent on non-linear load or less, with a 3:1 crest factor. Double-conversion efficiency is up to 94 percent. Overload capability is 110 percent for 60 minutes, 125 percent for 10 minutes, 150 percent for 1 minute and over 150 percent for 1.2 seconds.

The battery is external: the unit ships without batteries and connects to a string of 16 to 26 VRLA blocks (20 by default), from ± 96 to ± 156 Vdc, in PureWave BT cabinets sized to the required autonomy. Maximum charging current is 80 A. Up to six units can run in parallel, with shared-battery operation. Dimensions (W × D × H) are 600 × 850 × 1600 mm, weight is 321 kg and noise is below 68 dB. Operating temperature is 0 to 40 °C, humidity 0 to 95 percent non-condensing, and altitude below 1000 m, with derating between 1000 and 3000 m. Safety standards are UL 1778 and CSA C22.2 No. 107.3-14, and EMC follows FCC Part 15 Subpart B.

The page is a model data sheet: it defines one rating and configuration rather than giving design guidance. Detailed datasheets are issued on request.

Key points

  1. 100 kVA / 100 kW, three-phase input and four-wire output, 208/120 or 220/127 Vac.
  2. Double-conversion online; efficiency up to 94 percent.
  3. Input power factor of 0.99 or better; input current THDi of 3 percent or less on non-linear load.
  4. Output regulation ±1 percent; THDv 2 percent linear and 5 percent non-linear or less; crest factor 3:1.
  5. Overload: 110 percent for 60 min, 125 percent for 10 min, 150 percent for 1 min, above that 1.2 s.
  6. External battery: 16 to 26 VRLA blocks (20 default), ± 96 to ± 156 Vdc.
  7. Up to 6 units in parallel, with shared battery.
  8. Size 600 × 850 × 1600 mm, weight 321 kg, noise below 68 dB.
  9. Operation at 0 to 40 °C; derating required between 1000 and 3000 m.
  10. UL 1778 and CSA C22.2 No. 107.3-14 certified.

Using it in design

  • With unity output power factor the 100 kVA rating is 100 kW; check the kW load list against this value.
  • Set the autonomy and DC voltage window together with the battery cabinet choice, and confirm the BT cabinet pairing with the manufacturer.
  • The load-dependent input window (66 Vac at 40 percent load, 96 Vac at 100 percent) determines battery use on a weak supply; compare it with the measured mains quality.
  • For redundancy, consider the parallel topology (up to 6 units) and the shared-battery option.
  • For space and acoustics, check footprint, weight and noise against floor loading and room acoustics.

Who should read it

Electrical designers and specification engineers selecting 208/120 V low-voltage UPS for the US market.

Publication details

Authors
Renewable Energy & Drives (RE&D)
Publisher
Renewable Energy & Drives (RE&D)
Year
Year not stated
Document language
Unverified
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Renewable Energy & Drives (RE&D) RE&D PureWave T100H model specifications. Renewable Energy & Drives (RE&D). https://www.renewable-d.com/products/purewave-t100h

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.