RE&D PureWave T30H model specifications: 30 kVA / 30 kW UPS
Original title RE&D PureWave T30H model specifications
Renewable Energy & Drives (RE&D)
Renewable Energy & Drives (RE&D) PureWave T30H is a 30 kVA / 30 kW three-phase double-conversion online UPS at 208/120 V with unity output power factor, UL 1778 certified, efficiency up to 94 percent.
On this page
Overview
The document is the PureWave T30H product page on the Renewable Energy & Drives site (part of Severn Drives & Energy). The T30H is a double-conversion online model in the low-voltage modular UPS family: three-phase in, four-wire out, 30 kVA and, with unity output power factor, 30 kW. Input and output are 208/120 or 220/127 Vac (3Ph+N+PE), and the stated market is the United States.
The electrical figures are: input operating range 66 to 166 Vac at 40 percent load and 96 to 166 Vac at 100 percent load; input power factor of 0.99 or better; input current distortion of 3 percent or less on non-linear load. Output voltage regulation is ±1 percent and voltage distortion is 2 percent on linear and 5 percent on non-linear load or less, with a 3:1 crest factor. Double-conversion efficiency is up to 94 percent. Overload capability is 110 percent for 60 minutes, 125 percent for 10 minutes, 150 percent for 1 minute and over 150 percent for 1.2 seconds.
The battery is external: the unit ships without batteries and connects to a string of 16 to 26 VRLA blocks (20 by default), from ± 96 to ± 156 Vdc, in PureWave BT cabinets sized to the required autonomy. Maximum charging current is 20 A. Up to six units can run in parallel, with shared-battery operation. Dimensions (W × D × H) are 300 × 800 × 1000 mm, weight is 96 kg and noise is below 60 dB. Operating temperature is 0 to 40 °C, humidity 0 to 95 percent non-condensing, and altitude below 1000 m, with derating between 1000 and 3000 m. Safety standards are UL 1778 and CSA C22.2 No. 107.3-14, and EMC follows FCC Part 15 Subpart B.
The page is a model data sheet: it defines one rating and configuration rather than giving design guidance. Detailed datasheets are issued on request.
Key points
- 30 kVA / 30 kW, three-phase input and four-wire output, 208/120 or 220/127 Vac.
- Double-conversion online; efficiency up to 94 percent.
- Input power factor of 0.99 or better; input current THDi of 3 percent or less on non-linear load.
- Output regulation ±1 percent; THDv 2 percent linear and 5 percent non-linear or less; crest factor 3:1.
- Overload: 110 percent for 60 min, 125 percent for 10 min, 150 percent for 1 min, above that 1.2 s.
- External battery: 16 to 26 VRLA blocks (20 default), ± 96 to ± 156 Vdc.
- Up to 6 units in parallel, with shared battery.
- Size 300 × 800 × 1000 mm, weight 96 kg, noise below 60 dB.
- Operation at 0 to 40 °C; derating required between 1000 and 3000 m.
- UL 1778 and CSA C22.2 No. 107.3-14 certified.
Using it in design
- With unity output power factor the 30 kVA rating is 30 kW; check the kW load list against this value.
- Set the autonomy and DC voltage window together with the battery cabinet choice, and confirm the BT cabinet pairing with the manufacturer.
- The load-dependent input window (66 Vac at 40 percent load, 96 Vac at 100 percent) determines battery use on a weak supply; compare it with the measured mains quality.
- For redundancy, consider the parallel topology (up to 6 units) and the shared-battery option.
- For space and acoustics, check footprint, weight and noise against floor loading and room acoustics.
Who should read it
Electrical designers and specification engineers selecting 208/120 V low-voltage UPS for the US market.
Publication details
- Authors
- Renewable Energy & Drives (RE&D)
- Publisher
- Renewable Energy & Drives (RE&D)
- Year
- Year not stated
- Document language
- Unverified
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Renewable Energy & Drives (RE&D) RE&D PureWave T30H model specifications. Renewable Energy & Drives (RE&D). https://www.renewable-d.com/products/purewave-t30h
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.