Bellwin AT1-8A-15 technical specifications

Bellwin

A Bellwin product page for the AT1-8A-15: a 1U metered rack PDU with automatic transfer (ATS), 110 VAC input, 15 A maximum, eight IEC 60320 C13 outlets and an A/B source transfer time of 8 to 16 ms.

On this page

Overview

The product page from the Taiwanese manufacturer Bellwin Information brings together the ordering options, feature list and specification table of the AT1-8A-15. The unit has two separate power inlets: when source A develops a fault it moves the load to source B automatically, and it returns to source A once that source recovers. The page gives the transfer time as 8 to 16 ms. Status is shown by LED and a buzzer sounds on overload. The model is intended to give single-corded IT equipment a dual feed inside the rack.

According to the specification table, input voltage is 110 VAC, maximum input current is 15 A and frequency is 50/60 Hz. The input side has two IEC 60320 C20 inlets with separate power cords. The output has eight IEC 60320 C13 sockets on a single branch, each limited to 10 A. Standby consumption is 15 W. A three-digit LCD shows the device IP address, voltage and total current, and the current metering error is 1%.

The AT series is the metered type: outlets are not switched individually and the unit monitors the total load. An administrator can follow voltage, current, frequency, power factor, energy (kWh), temperature and humidity remotely through a web browser. Network functions include SNMP v1, v2c and v3, SNMP traps, Syslog, encrypted e-mail and SMS alerts, IP and MAC filtering, event logging and online firmware upgrade. Ethernet speed is 10/100 Mbps. Two COM ports serve terminal and API control and RS232-to-IP conversion. A digital temperature and humidity sensor is optional.

The enclosure is an iron case that mounts in a 19-inch standard rack at 1U; dimensions are 445 x 253 x 44 mm. Operating temperature is 0 to 45 °C, storage temperature 0 to 60 °C, and relative humidity 0 to 90% without condensation. The page gives no weight, and it does not state the type of transfer mechanism, the short-circuit rating or certifications. The product is marked as not available for online sale; a series brochure and an ATS operation manual are offered as separate documents.

Key points

  1. Input: 110 VAC, 15 A maximum, 50/60 Hz; two IEC 60320 C20 inlets.
  2. Output: 8 IEC 60320 C13 sockets on one branch; 10 A maximum per socket.
  3. A/B source transfer time 8...16 ms; automatic return when source A recovers.
  4. Standby consumption 15 W; current metering error 1%; three-digit LCD.
  5. Dimensions 445 x 253 x 44 mm; 1U in a 19-inch rack; iron case.
  6. Operating 0...45 °C, storage 0...60 °C; humidity 0...90% non-condensing.
  7. Management: SNMP v1/v2c/v3, traps, Syslog, e-mail and SMS alerts, IP/MAC filters, 10/100 Mbps Ethernet, 2 COM ports.
  8. Remotely monitored quantities: voltage, current, frequency, power factor, kWh, temperature and humidity.

Using it in design

  • Check total rack load against the 15 A input limit and each device against the 10 A per-socket limit.
  • Compare the 8...16 ms transfer time with the power-supply hold-up time of the connected equipment; use the unit for single-corded devices only.
  • Connect the two inlets to independent A and B distribution paths; each path must be able to carry the full ATS load.
  • Confirm that the socket type (IEC 60320 C13) and the 110 VAC input voltage match the site distribution and the equipment cords.
  • Reserve 1U of height and 253 mm of depth in the rack plan, and add the 15 W standby consumption to the rack heat load.

Who should read it

Data-centre electrical designers and infrastructure operations teams choosing an in-rack dual-feed solution for single-corded network and IT equipment.

Document contents

  1. Product options
  2. Product Features
  3. Specifications
  4. Diagram
  5. DM
  6. Operation Manual

Publication details

Authors
Bellwin
Publisher
Bellwin
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Bellwin Bellwin AT1-8A-15 technical specifications. Bellwin. https://www.bellwin.com.tw/shop/at1-8a-15-67

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.