Technical guideFree to readYear not stated

ETEK Electric transfer switches: EKATS5, EKATS3 and EK2R technical specifications

ETEK Electric

The transfer switch product page of ETEK Electric lists eight automatic transfer switch families of PC class to IEC 60947-6-1 and four manual families to IEC 60947-3: change-over time is 20 ms for EKATS5 at 10-63 A and EKATS3 at 10-80 A and below 50 ms for EK2R at 16-125 A, while EKATS1 extends to 3200 A.

On this page

Overview

The page brings together the automatic (ATS) and manual (MTS) transfer switches that ETEK Electric, a maker of solar and electrical protection products, offers for residential, commercial and industrial distribution systems. The products switch between the main utility supply and a backup generator or alternative source. The automatic families are EKTS1, EKS5, EKS2T, EKATS5, EKATS4, EKATS3, EKATS1 and EK2R; the manual families are ETCS101, EKGLZ1, EKCS101H and EKCS101G. For each family a short specification list gives the standard, number of poles, rated currents, voltage, change-over time, life and utilisation category.

Three families stand out among the small-current modular automatic switches. EKATS5: 10, 16, 20, 25, 32, 40, 50 and 63 A; AC 220 V (110 V on request), 2, 3 or 4 poles, change-over time 20 ms, utilisation category AC-31B, IP30. EKATS3: nine ratings from 10 to 80 A, Ui 690 V, Uimp 8 kV, again with a 20 ms change-over time. EK2R: ten ratings from 16 to 125 A, utilisation category AC-33iB, conditional short-circuit current Iq 50 kA, with contact, operating, return and off times all below 50 ms.

On the larger families the times are in the order of seconds. For EKS5 (16-630 A, frame currents 125, 250, 400 and 630 A) the conversion and action times are 0.58 s and 1.35 s at 125 A and 2.0 s and 2.0 s at 630 A. The three-position EKS2T (16-630 A) gives similar values. EKATS1 runs from 16 A to 3200 A with a transfer time typically below 1 second and at most below 3 seconds. EKTS1 (32-630 A) is defined for grid-to-grid and grid-to-generator applications, and the EKTS1-N type requires a dedicated ATS controller.

Among the manual switches, ETCS101, EKCS101H and EKCS101G are modular changeover switches for 35 mm DIN rail (16-125 A, I-0-II contact form). EKGLZ1 covers 125-3150 A in 3 and 4 poles; short-time withstand current Icw is 10 kA/1 s for 125-315 A, 20 kA/1 s for 400-630 A and 35 kA/1 s for 800-3150 A. All automatic products on the page are electromechanical PC class: the load is briefly de-energised during change-over, so for IT load they are used together with a UPS.

Key points

  1. The automatic families are PC class to IEC 60947-6-1; pole options are 2P, 3P and 4P.
  2. EKATS5: 10, 16, 20, 25, 32, 40, 50, 63 A; AC 220 V; change-over time 20 ms; mechanical life ≥ 6000 and electrical life ≥ 1500 operations; AC-31B; IP30.
  3. EKATS3: 10, 16, 20, 25, 32, 40, 50, 63, 80 A; AC 220 V; Ui 690 V, Uimp 8 kV; change-over time 20 ms.
  4. EK2R: 16, 20, 25, 32, 40, 50, 63, 80, 100, 125 A; AC-33iB; Iq 50 kA; all transfer times < 50 ms; mechanical life ≥ 5000 and electrical life ≥ 2000 operations.
  5. EKS5: 16-630 A; conversion / action time from 0.58 s / 1.35 s (125 A) to 2.0 s / 2.0 s (630 A); Ui 800 V, Uimp 8 kV.
  6. EKATS1: 16-3200 A, AC 400 V 50 Hz; transfer time typically < 1 s, maximum < 3 s.
  7. EKATS4: 10-63 A, AC 380 V; ambient -5 °C to +40 °C, altitude ≤ 2000 m.
  8. Manual EKGLZ1: 125-3150 A; Icw 10 kA/1 s (125-315 A), 20 kA/1 s (400-630 A), 35 kA/1 s (800-3150 A).
  9. Modular manual switches (ETCS101, EKCS101H, EKCS101G) mount on 35 mm DIN rail; the maximum back-up fuse for ETCS101 is 125 A gG.

Using it in design

  • For the main transfer between utility and generator, choose a 4-pole PC-class ATS and assess the 1-3 second transfer time together with UPS battery autonomy and generator start time.
  • Compare the ATS short-circuit capability (Iq 50 kA for EK2R, the Icw values for EKGLZ1) with the prospective fault current at the busbar and confirm coordination with the upstream protective device.
  • Match the utilisation category to the load: AC-33 switches suit motor and mixed loads, AC-31 switches suit resistive and slightly inductive loads.
  • Do not use the modular switches with 20 ms or 50 ms change-over directly on IT load; these times can exceed power supply hold-up. Consider them for lighting, auxiliary cooling and control circuits.
  • Set the maintenance and replacement interval by comparing the number of test transfers per year with the electrical life (1000-2000 operations).
  • For maintenance bypass and source selection, plan the 125-3150 A manual EKGLZ1 switches as a path parallel to the ATS on the single-line diagram.

Who should read it

Electrical engineers designing source transfer in low-voltage distribution, switchboard designers and project teams integrating generators.

Document contents

  1. Our Product Ranges
  2. Automatic Transfer Switch: EKTS1, EKS5, EKS2T, EKATS5, EKATS4, EKATS3, EKATS1, EK2R
  3. Manual Transfer Switch: ETCS101, EKGLZ1, EKCS101H, EKCS101G
  4. Quality Assurance and Certifications

Publication details

Authors
ETEK Electric
Publisher
ETEK Electric
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

ETEK Electric ETEK Electric transfer switches: EKATS5, EKATS3 and EK2R technical specifications. ETEK Electric. https://www.eteksolar.com/transfer-switch

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.