TAIXI TXQ5 Automatic Transfer Switch: Technical Parameters and Controller Configurations
Original title TAIXI TXQ5 Automatic Transfer Switch: technical parameters and controller configurations
TAIXI Electric
TAIXI Electric's TXQ5 automatic transfer switch (ATS) covers 20 to 800 A on 400 V 50 Hz supply, is CB class, complies with IEC 60947-6-1 and comes with A or B type controllers; transfer time (no delay) is 2.5-5 s.
On this page
Overview
The product page presents the TXQ5 series for three-phase four-wire, 50 Hz, 400 V dual-supply networks, automatically moving load from one source to the other at rated operational currents up to 800 A. The series complies with GB/T 14048.11 and IEC 60947-6-1, is a CB-class (circuit-breaker based) product and is used in industry, commercial buildings, high-rise buildings and housing. Operating conditions are stated as -5 to +40 C ambient (24-hour average not above +35 C) and not more than 50% relative humidity at +40 C.
The series is given in two tables. For TXQ5B-63, TXQ5-63 and TXQ5-100 the current choices are 20-63 A, 10-63 A and 25-100 A, with executive circuit breakers NB1-63H, NM1-63 and NM1-100. For TXQ5-225, 400, 630 and 800 the current ranges are 100-225, 225-400, 400-630 and 630-800 A with NM1-series breakers. Short-circuit breaking capacity codes are S, H and R, with Icn from 10 to 100 kA. Use category is AC-33iB or AC-33B, and life is 6000, 4000 and 3000 operations.
For safety, mechanical and electrical interlocking are used together; the electrical interlock reads the breaker contact position directly, so automatic transfer is prevented with welded contacts, damaged handle, circuit fault or tripping. Units other than TXQ5B-63 have an isolation function. The controller is type A (basic) or type B (liquid crystal display); control voltage is 230 V 50 Hz, taken from phase A of the two supplies.
Key points
- Rated voltage 400 V 50 Hz; current steps from 10 A to 800 A; 3P and 4P options.
- Standards: GB/T 14048.11 and IEC 60947-6-1; electrical class CB.
- Short-circuit breaking capacity codes S, H, R; Icn from 10 to 100 kA (for example 50, 75 and 100 kA for NM1-800).
- Conversion time (no delay): <=2.5 s on small frames, <=3 s on mid frames, up to <=5 s on the 630-800 A frame.
- Life is 6000 operations (63-225 A), 4000 (400 A) and 3000 (630-800 A).
- Undervoltage default 187 V (adjustable 160-200 V), overvoltage default 263 V (adjustable 240-290 V).
- Conversion and return delay default to 5 s, adjustable 0-180 s (type A) or 0-30 s (type B); generator start and stop delay default to 5 s.
- Protection class IP20 (TXQ5B-63) and IP30 (except main circuit terminals); controller consumption 5 W or <=10 W.
Using it in design
- Choose the S, H or R code by comparing the highest system short-circuit current with Icn; do contact-welding and selectivity studies through the executive breaker.
- At 2.5-5 s conversion time this is an open-transition solution, not an uninterrupted one; combine it with a UPS for critical load.
- Set the undervoltage and overvoltage thresholds and delays against the generator start-up time.
- Write the grid-grid or grid-generator mode and automatic return behaviour into the operating procedure.
- The ambient limit is -5 to +40 C, so control the temperature inside the panel.
Who should read it
Electrical engineers designing dual-supply mains and generator changeover, and those writing ATS specifications.
Document contents
- General information and standards
- Service conditions
- TXQ5B-63, TXQ5-63, TXQ5-100 parameters
- TXQ5-225 to TXQ5-800 parameters
- Controller characteristics and functions
- Parameter settings
Publication details
- Authors
- TAIXI Electric
- Publisher
- TAIXI Electric
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
TAIXI Electric TAIXI TXQ5 Automatic Transfer Switch: technical parameters and controller configurations. TAIXI Electric. https://www.txele.com/p2/dual-power-transfer-switch/
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.