SINA Engineering TERAPICCO English Product Catalogue: Ultra-High-Speed Static Transfer Switch
Original title SINA Engineering TERAPICCO English product catalogue
SINA Engineering
SINA Engineering's TERAPICCO is an ultra-high-speed static transfer switch that transfers in under 500 microseconds, works with synchronous or asynchronous AC and DC sources; conventional STS is 4 to 10 ms and ATS 10 to 100 ms.
On this page
Overview
The document is the product catalogue for TERAPICCO, an ultra-high-speed static transfer switch (STS) from Korea's SINA Engineering. The device selects one of two redundant supplies to critical, power-sensitive loads and, if the supply fails, transfers to the other within 500 microseconds. The catalogue compares this with the 4 to 10 ms transfer of a conventional STS and the 10 to 100 ms of a mechanical ATS, noting that sensitive loads can shut down in those times.
The highlighted features are patented ultra-fast switching (AC and DC, synchronous and asynchronous sources), real-time analysis of power faults (outage, surge, sag, frequency fluctuation, harmonics), overcurrent and short-circuit detection and protection, redundant internal control power and controller, and fanless natural cooling. It also explains that in a conventional SCR-based STS with asynchronous sources a line short may occur. The advantage of a distributed small STS arrangement over a centralized large STS is given as one STS failure not affecting other loads.
The product tables list four models. The rack types are I-UHS RMS030 (with maintenance switch, 30 A, 1-phase/2-pole, 8000 Arms short-circuit current, 0.5 cycle) and I-UHS RS030; the wall types are the STS-1000 (6.5 A) and STS-2000 (12 A), both 1-phase/2-pole, 100-240 V~ (selectable 110 to 240 V), 50/60 Hz, 5000 Arms (0.5 cycle) short-circuit current. Common values: no practical limit on input synchronization or power factor, overload capacity of 110 percent (fault alarm after 1 minute), break-before-make transfer, automatic or manual, external fuse or circuit breaker required, operation from -20 to 50 °C and a standard 36-month warranty.
The catalogue is single-phase; the need for a large three-phase STS for a data centre is outside its scope. The STS-1000 measures 127.5 × 190.6 × 289 mm and weighs 4.2 kg, and the STS-2000 152.5 × 190.6 × 289 mm and 4.3 kg. Standards listed are KC registration, IEC 62310-1,2 and a CE certificate of conformity.
Key points
- Transfer time under 500 microseconds; conventional STS 4 to 10 ms, mechanical ATS 10 to 100 ms.
- Works with synchronous and asynchronous sources, AC and DC; break-before-make type.
- Four models: I-UHS RMS030 (30 A, with maintenance switch), I-UHS RS030, STS-1000 (6.5 A) and STS-2000 (12 A).
- 1-phase/2-pole, selectable 100-240 V~, 50/60 Hz; no practical limit on input synchronization and power factor.
- Short-circuit current 5000 Arms (STS-1000/2000) and 8000 Arms (I-UHS RMS030), 0.5 cycle.
- Overload capacity 110 percent, fault alarm after 1 min; external fuse or circuit breaker required.
- Redundant internal control power and processor; fanless natural cooling.
- Operation -20 to 50 °C; standard 36-month warranty; KC, IEC 62310-1,2, CE.
Using it in design
- For small critical loads fed from two asynchronous sources (for example two separate UPS outputs), compare the line-short risk of a conventional SCR STS with TERAPICCO's asynchronous transfer ability.
- Judge load drop-out tolerance (for example PLC contactor release time) against 500 microseconds versus the 4 to 10 ms of a conventional STS.
- Evaluate a distributed small STS per rack against a single large central STS in terms of single points of failure.
- Select the current rating (6.5, 12 or 30 A) against the rack load total and external fuse or breaker coordination.
- For maintenance, choose the model with the maintenance switch or add an external maintenance bypass to the diagram.
Who should read it
Electrical engineers designing dual-source supply at rack and equipment level.
Document contents
- Terapicco overview
- Product features
- Reasons to choose Terapicco
- Operation example
- Differentiation from existing products: central and distributed STS
- Terapicco advantages
- Product specification: rack type
- Product specification: wall type
- Terapicco maintenance
- Company information, patents and certifications, company history
Publication details
- Authors
- SINA Engineering
- Publisher
- SINA Engineering
- Year
- Year not stated
- Document language
- Unverified
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
SINA Engineering SINA Engineering TERAPICCO English product catalogue. SINA Engineering. http://sinaeng.co.kr/catalog/index-en.html
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.