TOSUNlux Power Distribution System 2025-2026, automatic changeover switches
Original title TOSUNlux Power Distribution System 2025–2026, automatic changeover switches
TOSUNlux
The dual-power automatic changeover section of the TOSUNlux power distribution catalogue, giving current steps and utilisation categories for series such as TSMQ1-100, TSMQ8 and TSMQ2.
On this page
Overview
The catalogue covers a broad range of low-voltage products from modular breakers to panels. Its automatic transfer section (about pp.40-48) classifies the dual-power automatic changeover switches: the CB-class TSMQ7-XFZ, the modular TSMQ1-100, the PC-class TSMQ8, TSMQ3 and TSMQ4, the intelligent TSMQ2 and the high-current HGLD and HGLZ families. For each product, operating mode, rated current and utilisation category are given in separate table rows.
The TSMQ1-100 modular switch is defined for up to 415 V and 100 A: 20, 32, 40, 50, 63, 80 and 100 A, 2P or 4P, category AC-33iB, 50 kA limited short-circuit current and a mechanical life of 5000 operations. The TSMQ8 is a PC-class infrequent-changeover switch described for up to 400 V and 63 A, with 6-40 A steps, 5 kA short-circuit current and an NT00 63 A protective fuse.
For the TSMQ3 (three-position 1-0-2, AC-33iB) the steps are 16-63, 20-125, 160-250 and 315-630 A, and for the TSMQ4 (two-position 1-2, AC-33B) 16 to 250 A; the TSMQ4 has a mechanical life of 20000 and an electrical life of 6000 operations and an operating cycle of at most 360 per hour. Working modes are coded R (mains priority), B (standby priority), F (generator priority) and T (with communication). The TSMQ2 intelligent switch is listed at 100-400 A, AC-33iB and a conversion time of at most 5-6 s, and the HGLD covers conventional heating currents up to 3200 A.
The catalogue shows why published conditions must stay attached to each configuration: within one series the pole count, utilisation category and voltage class change with current, so a single number cannot be applied across the series.
Key points
- The 2025-2026 catalogue gives discrete current tables for TSMQ1-100, TSMQ8 and TSMQ2.
- TSMQ1-100: 20-100 A, 2P/4P, AC-33iB, up to 415 V, 50 kA limited short-circuit, 5000 operations mechanical life.
- TSMQ8: PC class, up to 400 V and 63 A; 6-40 A steps, 5 kA, NT00 63 A fuse.
- TSMQ3: three-position 1-0-2, AC-33iB; steps 16-63, 20-125, 160-250, 315-630 A; mechanical life 20000 and 4000 operations.
- TSMQ4: two-position 1-2, AC-33B; 16-250 A; mechanical life 20000, electrical life 6000, cycle at most 360/h.
- TSMQ2 intelligent switch: 100-400 A, AC-33iB, conversion time no more than 5-6 s, 8 kV impulse voltage.
- HGLD: up to 400 V, heating current 100 A to 3200 A; conversion time about 0.5 s to 1.25 s.
- Working-mode codes: R mains priority, B standby priority, F generator priority, T with communication.
Using it in design
- Record each ATS configuration with series, pole count, current step, utilisation category and voltage; do not separate the published conditions.
- State in the specification the difference between PC class (TSMQ8, TSMQ3, TSMQ4) and CB class (TSMQ7-XFZ) with respect to short-circuit making capacity.
- Do not use the intelligent switches with a 5-6 s conversion time at a UPS output; reserve them for generator changeover or mechanical load.
- Write the transfer priority code (mains, standby, generator) into the specification; R is the default, so any other preference must be stated.
- Compare the operating cycle limit (60 per hour for TSMQ3, 360 for TSMQ4) with the number of transfers in the test and maintenance programme.
Who should read it
Electrical engineers selecting low-voltage distribution and changeover switches.
Document contents
- TSMQ7-XFZ dual power automatic changeover switch
- TSMQ1-100 and TSMQ8
- TSMQ3 and TSMQ4
- TSMQ2 intelligent dual power switch, HGLD and HGLZ
Publication details
- Authors
- TOSUNlux
- Publisher
- TOSUNlux
- Year
- 2025
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
TOSUNlux (2025). TOSUNlux Power Distribution System 2025–2026, automatic changeover switches. TOSUNlux. https://www.tosunlux.eu/wp-content/uploads/2023/03/TOSUN-Power-Distribution-System-2025-2026.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.