Indeletra CHESTR-5K-2222 user instruction manual, technical specifications
Indeletra
The CHESTR-5K-2222 user manual from Brazilian manufacturer Indeletra describes a 5000 VA/W single-phase static transfer switch in a 19-inch 1U rack format: 220 V input, 220 V output, 22.7 A nominal input current, transfer time below 10 ms and efficiency above 99%.
On this page
Overview
The two-page manual describes the CHESTR-5K-2222 model in Indeletra's rack-mount static switch line. The unit is designed for electronic equipment whose supply must not be interrupted, and it switches between two sources: the main source is a UPS and the secondary source is the mains or a second UPS. When the main source fails or is taken out for maintenance the load moves automatically to the secondary source, and when the main source returns the unit recognises its priority and transfers the load back. Target loads are servers, personal computers, modems and switches, and CCTV systems.
According to the specification table the rated power is 5000 VA/W, the input is single-phase 220 V, the output is 220 V, the nominal input current is 22.7 A and the mains frequency is 60 Hz ±1%. The unit has no transformer; input and output share the same 220 V level. Transfer time is below 10 ms, efficiency is above 99% and the unit adds no harmonic distortion. There is no under-voltage or over-voltage protection; overcurrent protection is provided by a circuit breaker on the secondary-source side. A line filter is built in. There are 7 outputs: one socket on the front panel and six on the rear.
Mechanically the unit mounts in a 19-inch 1U rack or on a wall; its dimensions are 419 x 230 x 45 mm (W x D x H) and the chassis is steel with electrostatic paint. LEDs on the front panel show power-on, reversed phase, earth fault and the presence of the main source, and an audible alarm sounds when the main source is lost. Operating conditions are 0-50 °C and 90% relative humidity without condensation. The manual requires earthing to ABNT NBR 5410 and the NBR 14136 socket arrangement. The warranty is 1 year. The document dates from 2013.
Key points
- Model CHESTR-5K-2222; rated power 5000 VA/W; single phase.
- Input 220 V, output 220 V; mains frequency 60 Hz ±1%.
- Nominal input current 22.7 A.
- Transfer time below 10 ms; efficiency above 99%; adds no harmonic distortion.
- Overcurrent protection by a circuit breaker on the secondary-source side; no under-voltage or over-voltage protection; line filter fitted.
- 7 output sockets: 1 on the front panel, 6 on the rear.
- 19-inch 1U rack or wall mounting; dimensions (W x D x H) 419 x 230 x 45 mm.
- Operating environment 0-50 °C, 90% RH non-condensing; 1-year warranty.
Using it in design
- Use it to back up single-corded rack equipment (a network switch, modem or CCTV recorder) between a UPS and the mains; the load stays fed from the mains during UPS maintenance.
- Compare the transfer time of under 10 ms with the hold-up time of the supplied device's power supply.
- Keep the sum of connected loads below the 5000 VA limit and the 22.7 A input current, and protect the supply circuit for that current.
- There is no under-voltage or over-voltage protection, so secure the voltage quality of the secondary source separately.
- The unit is specified for a 60 Hz supply; obtain the manufacturer's confirmation before using it on 50 Hz systems.
Who should read it
Infrastructure designers choosing source-backup solutions for small network rooms and rack equipment, and teams cataloguing products sold in Brazil.
Document contents
- 1. Apresentação
- 2. Segurança e cuidados básicos
- 3. Condições ambientais de operação
- 4. Apresentação dos painéis
- 5. Instalação e funcionamento
- 6. Especificações técnicas
- 7. Assistência técnica
- 8. Garantia
Publication details
- Authors
- Indeletra
- Publisher
- Indeletra
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Indeletra Indeletra CHESTR-5K-2222 user instruction manual, technical specifications. Indeletra. https://indeletra.com.br/pdf/Manual_Chave_Estatica-5KVA-220V_220V-2013_Ver01.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.
