Enersafe ATS-30A user guide V1.2
Enersafe
An 11-page V1.2 user guide from Enersafe for the ATS-30A, a single-phase automatic transfer switch for 19-inch racks: 30 A maximum input current, 220/230/240 VAC, typical transfer time of 8-12 ms (16 ms maximum), 44 mm height and 5 kg net weight.
On this page
Overview
The guide covers installation and operation of a rack-mount automatic transfer switch that feeds one output from two independent inputs. The unit supplies the load from the priority source, moves to the second source when that source fails and returns when the priority source is restored. Priority is set to A or B with the source preference selector on the front panel; the default is source A. The sections run through introduction, product overview, safety warnings, indicators, installation, operation, communication port, troubleshooting, specifications and an appendix of thresholds.
According to the specifications section, input is 220/230/240 VAC with an acceptable range of 180-258 VAC at 50/60 Hz and a maximum input current of 30 A. The inputs are made through two cable glands. There are three output groups: a cable-gland terminal output at 30 A, one IEC C19 outlet at 16 A and four IEC C13 outlets at 10 A. The C13 and C19 output groups are protected by separate circuit breakers on the front panel. The chassis measures 330 x 483 x 44 mm (DxWxH) and weighs 5 kg net.
The appendix gives the transfer thresholds. The acceptable voltage range for each source is 180-258 V by default; return to the priority source takes place at a low point of 190 V and a high point of 248 V, which applies a 10 V hysteresis. The acceptable frequency range is 45-55 Hz. Transfer time is given as 8-12 ms typical and 16 ms maximum. The operating environment is -5 °C to 45 °C at 0-95% non-condensing relative humidity; ventilation is required where ambient will rise above 40 °C.
For monitoring there are RS-232 and USB ports on the front panel (only one can be used at a time), a communication slot and a six-pin dry contact port on the rear. The contacts report which source feeds the output, the status of each source and the general status of the ATS; they carry at most 8 A and 250 VAC and can be connected to a building management system. The guide requires the unit to be earthed and used indoors and professionally only. The troubleshooting table explains how to reset the thermal protection on the 10 A and 16 A outputs.
Key points
- Model: ATS-30A, single-phase, 19-inch rack-mount, two-input automatic transfer switch.
- Input: 220/230/240 VAC, acceptable range 180-258 VAC, 50/60 Hz, maximum input current 30 A.
- Outputs: cable-gland terminal 30 A, 1 x IEC C19 at 16 A, 4 x IEC C13 at 10 A.
- Transfer time: 8-12 ms typical, 16 ms maximum.
- Default thresholds: voltage 180-258 V with return at 190 V and 248 V; frequency 45-55 Hz.
- Dimensions 330 x 483 x 44 mm (DxWxH), net weight 5 kg.
- Environment: -5 °C to 45 °C, 0-95% relative humidity non-condensing; ventilation required above 40 °C.
- Communication: USB or RS-232 (one excludes the other), a communication slot and a 6-pin dry contact port (8 A, 250 VAC maximum).
- Default priority source is A; priority is changed from the front panel.
Using it in design
- Use it to connect single-corded rack equipment to the A and B distribution feeds; limit total load to 30 A (about 6.9 kVA at 230 V) and outlet loads to 10 A and 16 A.
- Compare the 16 ms maximum transfer time with the hold-up time of the load power supplies; use a static transfer switch for loads that cannot ride through 16 ms.
- Protect the circuits feeding the two inputs for 30 A, and confirm UPS output settings keep both sources inside the 180-258 V window.
- Wire the dry contact port to the BMS or DCIM to monitor the active source and source health; the contact limit is 8 A, 250 VAC.
- Allow 1U (44 mm) of height and 330 mm of depth in the rack layout, with bending allowance for the rear cable-gland entries.
- Check whether rear-of-rack temperature on the hot aisle side exceeds 40 °C, and mount the unit nearer the cold side if needed.
Who should read it
Electrical engineers designing rack-level power distribution and IT infrastructure and operations teams connecting single-corded equipment to redundant infrastructure.
Document contents
- 1. Introduction
- 2. Product Overview
- 3. Important Safety Warnings
- 4. Operation Indicators & Status
- 5. Installation
- 6. Operation
- 7. Communication Port
- 8. Trouble Shooting
- 9. Specifications
- 10. Appendix: Input Voltage and Frequency Thresholds
Publication details
- Authors
- Enersafe
- Publisher
- Enersafe
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Enersafe Enersafe ATS-30A user guide V1.2. Enersafe. https://enersafelatam.com/wp-content/uploads/2024/04/ATS-30A_Enersafe_manual.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.
