Lauritz Knudsen Industrial Switchgear Catalogue (15.08.2026)

Original title Lauritz Knudsen Industrial Switchgear catalogue, 15.08.2026

Lauritz Knudsen

The Lauritz Knudsen catalogue covering contactors, motor protection, automatic transfer switches, changeover switches, moulded case and air circuit breakers, power quality and automation; for data centres the integrated and enclosed ATS products and the DC solutions stand out.

On this page

Overview

The catalogue consists of Switching and Control, Motor Protection Solutions, Starters, Powergear, Energy Management and Automation Solutions. Powergear includes the integrated ATS, enclosed automatic transfer switch, on-load changeover switch-disconnectors, CZ bypass and disconnector switches, gPV fuses, FN switch disconnectors and fuses, moulded case circuit breakers, sub-main distribution boards and air circuit breakers. Energy Management covers power quality components, active harmonic filters and ASVG, protection relays, and metering and communication devices. Prices are M.R.P. in Indian rupees.

For automatic transfer products, nine integrated ATS and seven enclosed ATS order codes are published. Integrated ATS current steps are 125, 160, 200, 250, 315, 400, 630, 800 and 1000 A (frames 2 to 5); enclosed ATS are 125, 160, 200, 250, 315, 400 and 630 A (frames 2 to 4), 415 V AC. Enclosed ATS features: priority source selection, adjustable time delay from 0.1 second to 3 hours, suitability for three-phase and single-phase sources, generator control (ON-OFF, cooling cycle, self-test), a cyclic event logger recording 100 events, under/over voltage, phase sequence, single-phasing and frequency protections, password-protected access, a double-break contact system and mechanical and electrical life double that required by the IS/IEC standard.

Changeover switch-disconnectors conform to IEC 60947-3: manual from 63 A to 2000 A, motorised from 40 A to 2000 A, 415 V, AC-23A, 4 pole (motorised control voltage 240 Vac). The catalogue also offers solutions up to 1500 V DC for BESS, central inverter and EV applications: moulded case breakers from 16 A to 800 A (DC operating voltages 1500, 1000, 750, 500 and 250 V, Ics up to 50 kA), disconnector air circuit breakers up to 6300 A (Ics up to 100 kA), 125 to 630 A switch disconnectors and 2 to 32 A gPV fuses. The document is a product and price catalogue; conditions of each configuration are in the product data sheets.

Key points

  1. Nine integrated ATS codes: 125, 160, 200, 250, 315, 400, 630, 800 and 1000 A (frames 2 to 5).
  2. Seven enclosed ATS codes: 125, 160, 200, 250, 315, 400 and 630 A, 415 V AC (frames 2 to 4).
  3. Enclosed ATS: time delay adjustable from 0.1 second to 3 hours; cyclic event log of 100 events; suitable for three-phase and single-phase sources.
  4. Enclosed ATS protections: under/over voltage, phase sequence, single-phasing and frequency; password access control; double-break contact system.
  5. Changeover switch-disconnector: manual 63 to 2000 A, motorised 40 to 2000 A; 415 V, AC-23A, 4 pole.
  6. DC moulded case breakers 16 A to 800 A; DC voltages 1500, 1000, 750, 500 and 250 V; Ics up to 50 kA.
  7. DC disconnector air circuit breaker up to 6300 A (1500 V version upcoming); Ics up to 100 kA.
  8. gPV fuses 2 to 32 A, 1000 V and 1500 V DC, 20 kA breaking capacity.
  9. Power quality: active harmonic filters and ASVG, protection relays, metering and SmartComm gateway products.

Using it in design

  • When selecting an ATS, record order code, current step, frame and enclosure version (integrated or enclosed) together; published conditions must stay attached to each configuration.
  • In the generator-transfer scenario, define the time delay (0.1 s to 3 hours), priority source and cooling-cycle settings in the design document.
  • Set the mains voltage, phase sequence, single-phasing and frequency protection thresholds to match the generator and UPS acceptance window.
  • In BESS or DC-distributed systems, compare the DC moulded case breaker's operating voltage (1500 to 250 V) and Ics with the fault current.
  • Integrate the event log (100 events) into commissioning and maintenance records.

Who should read it

Electrical designers, panel builders and procurement teams selecting low-voltage switchgear and source-transfer equipment for the Indian market.

Document contents

  1. Switching and Control (contactors, accessories, spares)
  2. Motor Protection Solutions (thermal overload relays, electronic motor protection relays, iMMR, manual motor starters)
  3. Starters
  4. Powergear (integrated ATS, enclosed automatic transfer switch, on-load changeover switch-disconnectors, CZ bypass and disconnector switches, gPV fuses, FN switch disconnectors, moulded case circuit breakers, sub-main distribution boards, air circuit breakers)
  5. Energy Management (power quality, AHF and ASVG, protection relays, metering, SmartComm)
  6. Automation Solutions (AC drives, soft starters, PLC and HMI)
  7. Final Distribution Products

Publication details

Authors
Lauritz Knudsen
Publisher
Lauritz Knudsen
Year
2026
Document language
Unverified
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Lauritz Knudsen (2026). Lauritz Knudsen Industrial Switchgear catalogue, 15.08.2026. Lauritz Knudsen. https://novatrading.co.in/assets/catalogs/industrial-switchgear.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.