Schaefer Static Switches Series SS: Catalogue Pages 88-89
Original title Schaefer Static Switches Series SS, catalogue pp.88–89
Schaefer
Schaefer SS series single-phase static switches: 115 or 230 VAC, any fixed frequency from 40 to 400 Hz, 0.8 to 10 kVA; models up to 15 A transfer in at most half a period, typically a quarter period.
On this page
Overview
The document is the catalogue pages for Schaefer's SS series of static switches from the United States. The series is a compact device that transfers a load without break between two single-phase AC supplies (a priority and a non-priority input). There are ten models: for 115 V, SS 1506, 3506, 3516, 3526 and 3536 (0.8, 1.6, 3, 5 and 10 kVA), and for 230 V, SS 1508, 3508, 3518, 3528 and 3538 (0.8, 1.6, 3.2, 5 and 10 kVA). A frequency suffix is added to the model number (.3 fixed 40 to 400 Hz, .4 400 Hz, .5 50 Hz, .6 60 Hz); for 50 Hz, 230 VAC and 1.6 kVA, for instance, the model is SS 3508.5.
Operation is defined in three modes: mains service mode, inverter service mode and an automated function with priority selection. In automatic mode the priority input's supply stays on the load; if monitoring detects a deviation, the load is transferred to the non-priority input, and it is returned when the priority supply is back within voltage and frequency limits. Priority selection and inhibit can be set externally through opto-coupler inputs. The typical arrangement is a UPS system fed from mains and an inverter, with an external manual bypass switch recommended for maintenance.
Technical values: transfer time is at most half a period (including failure detection) for models with rated current up to 15 A, typically a quarter period, and one period, typically half a period, above 15 A. On return there is practically no interruption up to 15 A. The transfer trigger window is 0.8 × Unom to 1.15 × Unom, and surge capability is 5 × Inom for 1 second. Operating temperature is -20 to +75 °C with a 2.5 percent per °C load derating above +55 °C, protection is IP 20 and cooling is natural convection. ESD, fast transient and surge immunity are IEC 61000-4-2/-4/-5 level 3.
The document also covers mechanical options (19 inch sub-rack Eurocassette, wall mount, increased mechanical strength, tropical protection, extended temperature range down to -40 °C) and LED and potential-free contact status indication; it is not for three-phase needs or loads above 10 kVA.
Key points
- Ten models: SS 1506/3506/3516/3526/3536 (0.8 to 10 kVA) at 115 V and SS 1508/3508/3518/3528/3538 (0.8 to 10 kVA) at 230 V.
- Frequency suffix: .3 fixed 40 to 400 Hz, .4 400 Hz, .5 50 Hz, .6 60 Hz.
- Transfer time is at most half a period at 15 A and below, typically a quarter period; one period above 15 A, typically half a period.
- Transfer trigger window is 0.8 × Unom to 1.15 × Unom; surge current is 5 × Inom for 1 second.
- Priority and inhibit inputs are opto-coupled: logic low 0 to 5 V, logic high 12 to 30 V.
- Operating temperature -20 to +75 °C; 2.5 percent per °C load derating above +55 °C; IP 20.
- Immunity: ESD, fast transients and surges to IEC 61000-4-2/-4/-5 level 3.
- Weight is about 3.3 kg (SS 15xx Eurocassette) to 8 kg (SS 35xx wall mount).
Using it in design
- Pick the model for load and voltage (for example SS 3508 for 230 VAC at 1.6 kVA) and add the frequency suffix for the supply.
- Confirm that the two supplies are at the same frequency and synchronous; the static switch synchronizes the frequency of one supply to the other.
- For models above 15 A, use an external slow-characteristic fuse.
- Provide an external manual bypass switch in the design for maintenance.
- For sensitive loads, compare the quarter-period transfer with the load's ride-through.
Who should read it
Electrical designers and UPS system integrators selecting static switches for small dual-source critical loads.
Document contents
- Features and model table
- UPS system with static switch
- Operating modes
- Specifications
- Mechanical options and environment
Publication details
- Authors
- Schaefer
- Publisher
- Schaefer
- Year
- Year not stated
- Document language
- Unverified
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Schaefer Schaefer Static Switches Series SS, catalogue pp.88–89. Schaefer. https://schaeferpower.com/wp-content/uploads/2015/12/Static-Switches.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.