Schaefer Static Switches Series SS: Catalogue Pages 88-89

Original title Schaefer Static Switches Series SS, catalogue pp.88–89

Schaefer

Schaefer SS series single-phase static switches: 115 or 230 VAC, any fixed frequency from 40 to 400 Hz, 0.8 to 10 kVA; models up to 15 A transfer in at most half a period, typically a quarter period.

On this page

Overview

The document is the catalogue pages for Schaefer's SS series of static switches from the United States. The series is a compact device that transfers a load without break between two single-phase AC supplies (a priority and a non-priority input). There are ten models: for 115 V, SS 1506, 3506, 3516, 3526 and 3536 (0.8, 1.6, 3, 5 and 10 kVA), and for 230 V, SS 1508, 3508, 3518, 3528 and 3538 (0.8, 1.6, 3.2, 5 and 10 kVA). A frequency suffix is added to the model number (.3 fixed 40 to 400 Hz, .4 400 Hz, .5 50 Hz, .6 60 Hz); for 50 Hz, 230 VAC and 1.6 kVA, for instance, the model is SS 3508.5.

Operation is defined in three modes: mains service mode, inverter service mode and an automated function with priority selection. In automatic mode the priority input's supply stays on the load; if monitoring detects a deviation, the load is transferred to the non-priority input, and it is returned when the priority supply is back within voltage and frequency limits. Priority selection and inhibit can be set externally through opto-coupler inputs. The typical arrangement is a UPS system fed from mains and an inverter, with an external manual bypass switch recommended for maintenance.

Technical values: transfer time is at most half a period (including failure detection) for models with rated current up to 15 A, typically a quarter period, and one period, typically half a period, above 15 A. On return there is practically no interruption up to 15 A. The transfer trigger window is 0.8 × Unom to 1.15 × Unom, and surge capability is 5 × Inom for 1 second. Operating temperature is -20 to +75 °C with a 2.5 percent per °C load derating above +55 °C, protection is IP 20 and cooling is natural convection. ESD, fast transient and surge immunity are IEC 61000-4-2/-4/-5 level 3.

The document also covers mechanical options (19 inch sub-rack Eurocassette, wall mount, increased mechanical strength, tropical protection, extended temperature range down to -40 °C) and LED and potential-free contact status indication; it is not for three-phase needs or loads above 10 kVA.

Key points

  1. Ten models: SS 1506/3506/3516/3526/3536 (0.8 to 10 kVA) at 115 V and SS 1508/3508/3518/3528/3538 (0.8 to 10 kVA) at 230 V.
  2. Frequency suffix: .3 fixed 40 to 400 Hz, .4 400 Hz, .5 50 Hz, .6 60 Hz.
  3. Transfer time is at most half a period at 15 A and below, typically a quarter period; one period above 15 A, typically half a period.
  4. Transfer trigger window is 0.8 × Unom to 1.15 × Unom; surge current is 5 × Inom for 1 second.
  5. Priority and inhibit inputs are opto-coupled: logic low 0 to 5 V, logic high 12 to 30 V.
  6. Operating temperature -20 to +75 °C; 2.5 percent per °C load derating above +55 °C; IP 20.
  7. Immunity: ESD, fast transients and surges to IEC 61000-4-2/-4/-5 level 3.
  8. Weight is about 3.3 kg (SS 15xx Eurocassette) to 8 kg (SS 35xx wall mount).

Using it in design

  • Pick the model for load and voltage (for example SS 3508 for 230 VAC at 1.6 kVA) and add the frequency suffix for the supply.
  • Confirm that the two supplies are at the same frequency and synchronous; the static switch synchronizes the frequency of one supply to the other.
  • For models above 15 A, use an external slow-characteristic fuse.
  • Provide an external manual bypass switch in the design for maintenance.
  • For sensitive loads, compare the quarter-period transfer with the load's ride-through.

Who should read it

Electrical designers and UPS system integrators selecting static switches for small dual-source critical loads.

Document contents

  1. Features and model table
  2. UPS system with static switch
  3. Operating modes
  4. Specifications
  5. Mechanical options and environment

Publication details

Authors
Schaefer
Publisher
Schaefer
Year
Year not stated
Document language
Unverified
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Schaefer Schaefer Static Switches Series SS, catalogue pp.88–89. Schaefer. https://schaeferpower.com/wp-content/uploads/2015/12/Static-Switches.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.