Up Select ULP 6-10 kVA Rack or Tower Convertible 1P/1P Split-Type UPS Datasheet

Original title Up Select ULP6-10kVA Rack/Tower1P/1P split-type datasheet p.1

Up Select Electronics

The Up Select ULP series 6 kVA/5.4 kW and 10 kVA/9 kW are single-phase in/out, 3U rack or tower, true double-conversion UPSs with 0.9 output power factor, 0 ms transfer, over 92% efficiency and an optional isolation transformer.

On this page

Overview

The datasheet gives the Up Select Electronics ULP series in four model columns: ULP602R and ULP602RB (6 kVA/5.4 kW) and ULP103R and ULP103RB (10 kVA/9 kW). The R version comes with a specified battery bank and the RB version with external batteries and is extendable. Options include an isolation transformer in a split rack box with maintenance bypass switch, N+X parallel redundancy, an external battery box and EPO. Input THDi is under 5% and output THD under 2%.

Input is single phase two-wire with ground, 208/220/230/240 Vac (100-300 Vac), 40-70 Hz, power factor 99% or better. Output is 208/220/230/240 Vac single phase, or with the isolation transformer 1-phase 3-wire with ground at 220/110, 230/115 or 240/120 Vac; regulation is +/-1% (+/-2% with transformer), battery-mode frequency 50 or 60 Hz +/-0.05 Hz, pure sine, crest factor 3:1. Efficiency is over 92% in AC mode, over 92% in battery mode and over 96% in ECO mode. Transfer time is 0 ms from line to battery and from inverter to bypass, and under 10 ms from ECO to inverter.

The battery is maintenance-free VRLA: 12 V/7 Ah x 20 (240 VDC) for the 6 kVA R and 12 V/9 Ah x 20 (240 VDC) for the 10 kVA R, with recharge to 90% in 7 and 8 hours. Backup is 9 minutes at full load and 20 minutes at half load. The cabinet is 3U rack or tower convertible; the main UPS box, isolation transformer box and battery bank box are each 610 x 440 x 135 mm (L x W x H), and each adds another chassis. Noise is under 50 dB at 1 m and operation is 0-40 C. Communication is USB, optional dry contact and an SNMP slot. Weight is not in the table.

Key points

  1. Models ULP602R/RB 6 kVA/5.4 kW and ULP103R/RB 10 kVA/9 kW; output PF 0.9.
  2. Input 208/220/230/240 Vac (100-300 Vac), 40-70 Hz, PF >=99%, THDi <5%.
  3. Output regulation +/-1% (+/-2% with transformer); THD <2% (linear), <5% (non-linear); crest factor 3:1.
  4. Efficiency >92% in AC mode, >92% in battery mode, >96% in ECO mode.
  5. Transfer: line-battery 0 ms, inverter-bypass 0 ms, ECO-inverter <10 ms.
  6. Battery on R versions 12 V/7 Ah x20 and 12 V/9 Ah x20 (240 VDC); 90% recharge in 7 and 8 hours.
  7. Backup 9 min (full load), 20 min (half load).
  8. Main box 610 x 440 x 135 mm; isolation transformer and battery bank boxes are separate chassis of the same size; noise <50 dB.

Using it in design

  • With a 0.9 output power factor the 6 kVA model gives 5.4 kW and the 10 kVA model 9 kW; select load by watts.
  • In the split-type design each added box (transformer, battery bank) means another 3U and weight; plan rack space by total box count and ask the manufacturer for net values.
  • Backup is only 9 minutes at full load, so for a target runtime evaluate the RB version and the external battery box.
  • For dual-voltage (110/220 V) loads, state the isolation transformer option in the order code.
  • The ECO-to-inverter transfer is under 10 ms; verify this for sensitive loads.

Who should read it

Designers selecting 6-10 kVA single-phase UPSs for small data rooms and edge sites.

Document contents

  1. Features
  2. Input
  3. Output
  4. Efficiency
  5. Battery
  6. Transfer time
  7. Display and alarms
  8. Communications
  9. Environment
  10. Physical

Publication details

Authors
Up Select Electronics
Publisher
Up Select Electronics
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Up Select Electronics Up Select ULP6-10kVA Rack/Tower1P/1P split-type datasheet p.1. Up Select Electronics. https://upselect.com/wp-content/uploads/2026/10/ULP-6-10KVA-Rack-Mount-Series.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.