Up Select ALP 20-80K Series 3-Phase True Online UPS Specifications

Original title Up Select ALP20-80K series3-phase true online, specifications p.2

Up Select Electronics

The Up Select ALP 20-80 kVA series is an IGBT-based three-phase in/out on-line UPS with unity output power factor, up to 96% efficiency in online mode, over 99% in ECO mode, input PF 0.99 and THDi under 3%.

On this page

Overview

The document gives the 20K, 30K, 40K, 60K and 80K models of Up Select Electronics' (Taiwan) ALP series, in STD internal-battery and KS external-battery versions, in one table. Power ratings in kVA and kW are equal: 20, 30, 40, 60 and 80. The input is PWM, IGBT based; nominal 230/400 Vac (220/380 and 240/415 selectable), voltage range -50% to +20% depending on load, input PF 0.99 or better, THDi under 3%, and frequency 50/60 Hz auto-sensing over 40-72 Hz.

Output power factor is 1, efficiency is up to 96% in online mode and over 99% in ECO mode; THDv is under 2% on linear load and unbalanced load capability is 100%. Overload on the 20KS-80KS models is 102-110% for 60 min, 111-125% for 10 min, 126-150% for 1 min and above 150% for 150 ms. An internal static switch and maintenance bypass are standard, and bypass voltage is 400 V +/-10% (maximum +/-20%). Battery type is VRLA, NiCd or lithium on the KS models and VRLA on the battery kit and STD internal models. Default battery voltage is 432 VDC (320-607 V), and 320-552 V on STD internal and kit models.

On STD internal-battery models the battery is 1 x 40 x 9 Ah for 20K, 2 x 32 x 9 Ah for 30K, 2 x 40 x 9 Ah for 40K, 3 x 40 x 9 Ah for 60K and 4 x 40 x 9 Ah for 80K, with backup of 3.5 minutes at 100% load. Charger current is up to 20, 30, 40, 60 and 80 A. On KS models backup depends on battery capacity and load. Dimensions (W x D x H) are 330 x 700 x 525 mm for 20-40K and 330 x 772 x 977 mm for 60-80K on KS models, and 500 x 859 x 887 mm for 20-40K and 500 x 846 x 1500 mm for 60-80K on kit and STD internal models. Weight is not in the table. Noise is 65 dBA or less at 1 m at 75% load, and altitude is up to 1000 m without derating. Standards are IEC/EN 62040-1, -2 and -3, marking CE.

Key points

  1. Models 20K, 30K, 40K, 60K, 80K (STD and KS versions); 20-80 kVA = 20-80 kW (PF 1).
  2. Input 230/400 Vac (220/380, 240/415 selectable); -50% to +20% (load dependent); PF >=0.99; THDi <3%; 40-72 Hz.
  3. Efficiency up to 96% in online mode, >99% in ECO mode; THDv <2% (linear load); unbalanced load 100%.
  4. Overload (KS): 102-110% for 60 min, 111-125% for 10 min, 126-150% for 1 min, >150% for 150 ms.
  5. Battery: VRLA/NiCd/lithium on KS models, 432 VDC default (320-607 V); VRLA on STD internal and kit models, 320-552 V.
  6. STD internal battery: 20K 1x40x9 Ah, 30K 2x32x9 Ah, 40K 2x40x9 Ah, 60K 3x40x9 Ah, 80K 4x40x9 Ah; backup 3.5 min at 100% load.
  7. Charger current up to 20/30/40/60/80 A; interface 2 intelligent slots, EPO, 3 building alarm inputs, RS-232, USB.
  8. Dimensions from 330 x 700 x 525 mm to 500 x 846 x 1500 mm; noise <=65 dBA; altitude <=1000 m without derating.

Using it in design

  • With output PF 1, kVA equals kW; compare load in kW directly.
  • The STD internal-battery version gives only 3.5 minutes at 100% load; for a target runtime, calculate the KS (external battery) or kit model and battery capacity.
  • If lithium or NiCd is required, choose the KS model; STD and kit models are VRLA only.
  • Match the battery voltage window (432 VDC default) to the cell count of the string.
  • On critical load, the 99% ECO-mode efficiency means bypass operation with reduced conditioning; compare against load sensitivity.

Who should read it

Electrical designers and specification engineers selecting UPSs in the 20-80 kVA range.

Document contents

  1. Product specification table: Capacity
  2. Input
  3. Output
  4. Bypass
  5. Battery
  6. Communication
  7. Environment
  8. Dimension
  9. Regulation

Publication details

Authors
Up Select Electronics
Publisher
Up Select Electronics
Year
Year not stated
Document language
Unverified
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Up Select Electronics Up Select ALP20-80K series3-phase true online, specifications p.2. Up Select Electronics. https://upselect.com/wp-content/uploads/2026/11/ALP-Series-3-3-phase-20-80KVA.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.