Up Select ALP 20-80K Series 3-Phase True Online UPS Specifications
Original title Up Select ALP20-80K series3-phase true online, specifications p.2
Up Select Electronics
The Up Select ALP 20-80 kVA series is an IGBT-based three-phase in/out on-line UPS with unity output power factor, up to 96% efficiency in online mode, over 99% in ECO mode, input PF 0.99 and THDi under 3%.
On this page
Overview
The document gives the 20K, 30K, 40K, 60K and 80K models of Up Select Electronics' (Taiwan) ALP series, in STD internal-battery and KS external-battery versions, in one table. Power ratings in kVA and kW are equal: 20, 30, 40, 60 and 80. The input is PWM, IGBT based; nominal 230/400 Vac (220/380 and 240/415 selectable), voltage range -50% to +20% depending on load, input PF 0.99 or better, THDi under 3%, and frequency 50/60 Hz auto-sensing over 40-72 Hz.
Output power factor is 1, efficiency is up to 96% in online mode and over 99% in ECO mode; THDv is under 2% on linear load and unbalanced load capability is 100%. Overload on the 20KS-80KS models is 102-110% for 60 min, 111-125% for 10 min, 126-150% for 1 min and above 150% for 150 ms. An internal static switch and maintenance bypass are standard, and bypass voltage is 400 V +/-10% (maximum +/-20%). Battery type is VRLA, NiCd or lithium on the KS models and VRLA on the battery kit and STD internal models. Default battery voltage is 432 VDC (320-607 V), and 320-552 V on STD internal and kit models.
On STD internal-battery models the battery is 1 x 40 x 9 Ah for 20K, 2 x 32 x 9 Ah for 30K, 2 x 40 x 9 Ah for 40K, 3 x 40 x 9 Ah for 60K and 4 x 40 x 9 Ah for 80K, with backup of 3.5 minutes at 100% load. Charger current is up to 20, 30, 40, 60 and 80 A. On KS models backup depends on battery capacity and load. Dimensions (W x D x H) are 330 x 700 x 525 mm for 20-40K and 330 x 772 x 977 mm for 60-80K on KS models, and 500 x 859 x 887 mm for 20-40K and 500 x 846 x 1500 mm for 60-80K on kit and STD internal models. Weight is not in the table. Noise is 65 dBA or less at 1 m at 75% load, and altitude is up to 1000 m without derating. Standards are IEC/EN 62040-1, -2 and -3, marking CE.
Key points
- Models 20K, 30K, 40K, 60K, 80K (STD and KS versions); 20-80 kVA = 20-80 kW (PF 1).
- Input 230/400 Vac (220/380, 240/415 selectable); -50% to +20% (load dependent); PF >=0.99; THDi <3%; 40-72 Hz.
- Efficiency up to 96% in online mode, >99% in ECO mode; THDv <2% (linear load); unbalanced load 100%.
- Overload (KS): 102-110% for 60 min, 111-125% for 10 min, 126-150% for 1 min, >150% for 150 ms.
- Battery: VRLA/NiCd/lithium on KS models, 432 VDC default (320-607 V); VRLA on STD internal and kit models, 320-552 V.
- STD internal battery: 20K 1x40x9 Ah, 30K 2x32x9 Ah, 40K 2x40x9 Ah, 60K 3x40x9 Ah, 80K 4x40x9 Ah; backup 3.5 min at 100% load.
- Charger current up to 20/30/40/60/80 A; interface 2 intelligent slots, EPO, 3 building alarm inputs, RS-232, USB.
- Dimensions from 330 x 700 x 525 mm to 500 x 846 x 1500 mm; noise <=65 dBA; altitude <=1000 m without derating.
Using it in design
- With output PF 1, kVA equals kW; compare load in kW directly.
- The STD internal-battery version gives only 3.5 minutes at 100% load; for a target runtime, calculate the KS (external battery) or kit model and battery capacity.
- If lithium or NiCd is required, choose the KS model; STD and kit models are VRLA only.
- Match the battery voltage window (432 VDC default) to the cell count of the string.
- On critical load, the 99% ECO-mode efficiency means bypass operation with reduced conditioning; compare against load sensitivity.
Who should read it
Electrical designers and specification engineers selecting UPSs in the 20-80 kVA range.
Document contents
- Product specification table: Capacity
- Input
- Output
- Bypass
- Battery
- Communication
- Environment
- Dimension
- Regulation
Publication details
- Authors
- Up Select Electronics
- Publisher
- Up Select Electronics
- Year
- Year not stated
- Document language
- Unverified
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Up Select Electronics Up Select ALP20-80K series3-phase true online, specifications p.2. Up Select Electronics. https://upselect.com/wp-content/uploads/2026/11/ALP-Series-3-3-phase-20-80KVA.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.