BATER OPzS stationary batteries: technical data: OPzS Optima / 2-OPzS-100
BATER
A product page from the Polish manufacturer BATER for OPzS Optima 2 V flooded lead-acid cells for standby use: 27 cell types, nominal capacities from 100 to 3250 Ah and a 20-year design life.
On this page
Overview
The page describes BATER's OPzS Optima series with low-antimony (LA) tubular positive plates. The series is consistent with DIN 40736 and consists of single 2 V cells; the page summarises the capacity range as 107 to 3340 Ah. Cells are produced at the Gliwice plant, while the polyethylene-coated steel stands and the patented recombination plugs come from the Warsaw facility. The manufacturer states a 20-year operational life, self-discharge below 3% per month and very low water consumption, with topping up needed once every 12 to 15 years.
The construction section explains each component. The spines of the tubular positive plate are die cast from a 1.7% antimony alloy. Negative plates are cast from a low-antimony alloy and placed in a special mesh made by Sireg. Separators are Daramic microporous polyethylene; the container is transparent and the lid is grey SAN plastic. Connectors are fully insulated solid copper, fixed with insulated bolts that have a measurement hole. Standard RegPlug1 recombination plugs prevent hydrogen emission and reduce battery-room ventilation requirements to the level of VRLA batteries.
The technical table applies at +20 °C and lists 27 cell types from 2-OPzS-100 to 26-OPzS-3250. Each row gives C10 to an end voltage of 1.80 V/cell, C5 and C3 to 1.75 V/cell, C1 to 1.67 V/cell, and the nominal capacity Cnom. According to the footnotes, nominal capacity and current mean C10 and I10 under PN EN 60896-11:2003, while the C10 column shows capacity after ten cycles. For 2-OPzS-100 the nominal value is 100 Ah and C10 after ten cycles is 107 Ah.
The same table gives charging current, length, width, height, and weight without and with electrolyte (±5%). Cell height rises in steps with capacity: 369, 485, 660, 810 and 792 mm. The smallest cell, 2-OPzS-100, weighs 11 kg filled, and the largest, 26-OPzS-3250, weighs 250 kg. The page contains no discharge current tables, short-circuit current or internal resistance values; those data require the manufacturer's detailed documents.
Key points
- Series: low-antimony tubular-plate 2 V OPzS Optima cells; consistent with DIN 40736; 20-year operational life.
- 27 cell types from 2-OPzS-100 to 26-OPzS-3250; nominal capacity 100...3250 Ah.
- 2-OPzS-100: Cnom 100 Ah, C10 after ten cycles 107 Ah, C5 92 Ah, C3 79 Ah, C1 60 Ah, charging current 10 A; 103 x 206 x 369 mm; 11 kg filled.
- 10-OPzS-1000: C10 after ten cycles 1093 Ah, C1 590 Ah; 210 x 233 x 660 mm; 80 kg filled.
- 26-OPzS-3250: C10 after ten cycles 3610 Ah, C1 1845 Ah, charging current 325 A; 212 x 576 x 792 mm; 250 kg filled.
- End voltages: 1.80 V/cell for C10 and Cnom, 1.75 V/cell for C5 and C3, 1.67 V/cell for C1; all values at +20 °C.
- Nominal capacity and current are C10 and I10 under PN EN 60896-11:2003.
- Self-discharge is below 3% per month; water refill is needed once every 12...15 years.
- RegPlug1 recombination plugs are standard and reduce ventilation requirements to VRLA level.
Using it in design
- Size the battery on nominal capacity (Cnom) and store the C10-after-ten-cycles figure as a separate field.
- For UPS discharges of one hour or less, use the C1 column; C1 is roughly half of nominal capacity (60 Ah for 2-OPzS-100).
- Base rack, floor-loading and handling plans on the filled weight; the large cells reach 250 kg.
- Set rack tier height and top maintenance clearance from the cell height, which ranges from 369 to 810 mm.
- Separate the with-plug and without-plug cases in the battery-room ventilation calculation, and verify the calculation against the standard in force.
- Request capacity correction factors for temperatures other than 20 °C from the manufacturer.
Who should read it
Electrical designers selecting large flooded stationary batteries, engineers planning battery rooms, and operators of utility, telecom or industrial sites.
Document contents
- Description
- Key features of OPzS Optima batteries
- Construction of OPzS Optima
- Dimensions and technical data
Publication details
- Authors
- BATER
- Publisher
- BATER
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
BATER BATER OPzS stationary batteries: technical data: OPzS Optima / 2-OPzS-100. BATER. https://baterbattery.com/product/bater-lead-acid-batteries-opzs-optima-type-for-standby-application/
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.
