Technical guideFree to readYear not stated

BATER OPzS stationary batteries: technical data: OPzS Block / 6x1-OPzS-50

BATER

A product page from the Polish manufacturer BATER for OPzS Block flooded lead-acid monoblocs for standby use: seven 12 V and 6 V models, C10 capacities from 54 to 322 Ah at 20 °C and an 18-year design life.

On this page

Overview

The page describes BATER's OPzS Block series with low-antimony (LA) tubular positive plates. The series is consistent with DIN 40736, and its dimensions follow DIN 40736-1 and DIN 40737-3. The manufacturer produces the cells at its Gliwice plant, and makes the polyethylene-coated steel stands and the patented recombination plugs, which eliminate hydrogen emission and water loss, at its Warsaw facility. The range consists of 12 V monoblocs of 54, 107 and 161 Ah and 6 V monoblocs from 161 to 332 Ah.

The construction section lists the cell components. The positive plate is tubular, with spines die cast from a 1.7% antimony alloy. Negative grids are also cast from a low-antimony alloy. Separators are microporous polyethylene made by Daramic. Terminals are a corrosion-resistant lead alloy with a brass core. The transparent container and the grey lid are SAN (styrene acrylonitrile) plastic, and the transparent container allows a quick visual check of the electrolyte level. Flexible inter-cell connectors and bolts are fully insulated.

The technical table applies at +20 °C and gives five capacity figures per model: C10 to an end voltage of 1.80 V/cell, C5 and C3 to 1.75 V/cell, C1 to 1.67 V/cell, and the nominal capacity Cnom. According to the footnotes, nominal capacity and nominal current mean C10 and I10 as defined in DIN 40737-3, while the C10 column is the capacity after ten cycles. For 6x1-OPzS-50, for example, nominal capacity is 50 Ah and C10 after ten cycles is 54 Ah.

The table also lists charging current, length, width, height, and weight without and with electrolyte (±5%). Every model is 205 mm wide and 347 mm high; length is 272 or 380 mm. The smallest block, 6x1-OPzS-50, weighs 39 kg filled, and the largest 12 V block, 6x3-OPzS-150, weighs 70 kg. Self-discharge is below 3% per month. The page gives no discharge curves, short-circuit current or internal resistance values.

Key points

  1. Series: low-antimony tubular-plate OPzS Block; consistent with DIN 40736; 18-year design life.
  2. Seven models: 12 V 6x1-OPzS-50, 6x2-OPzS-100, 6x3-OPzS-150; 6 V 3x3-OPzS-150, 3x4-OPzS-200, 3x5-OPzS-250, 3x6-OPzS-300.
  3. 6x1-OPzS-50: 12 V, Cnom 50 Ah, C10 after ten cycles 54 Ah, C5 46 Ah, C3 40 Ah, C1 30 Ah, charging current 5 A.
  4. 6x1-OPzS-50 measures 272 x 205 x 347 mm; weight 30 kg dry and 39 kg filled (±5%).
  5. 3x6-OPzS-300: 6 V, C10 after ten cycles 322 Ah, C1 178 Ah, 380 x 205 x 347 mm, 67 kg filled.
  6. End voltages: 1.80 V/cell for C10 and Cnom, 1.75 V/cell for C5 and C3, 1.67 V/cell for C1; all values at +20 °C.
  7. Self-discharge is below 3% per month.
  8. Positive plate alloy contains 1.7% antimony; container and lid are SAN plastic.
  9. The 3x3-OPzS-150 row lists a charging current of 78 A; the same-capacity 6x3-OPzS-150 lists 15 A.

Using it in design

  • Size the battery on nominal capacity (Cnom, DIN 40737-3) and store the C10-after-ten-cycles figure as a separate field.
  • For short discharges such as UPS duty, work from the C1 figure and its 1.67 V/cell end voltage, not from C10.
  • Use the filled weight and the ±5% tolerance for rack and floor loading.
  • Because these are flooded cells, plan battery-room ventilation, access for electrolyte level checks and acid spill containment.
  • Obtain capacity correction for room temperatures other than 20 °C from the manufacturer; the table gives +20 °C values only.
  • Confirm the charging current of 3x3-OPzS-150 with the manufacturer before ordering.

Who should read it

Electrical designers selecting long-life flooded stationary batteries, engineers planning battery rooms, and telecom or utility operators.

Document contents

  1. Description
  2. Key features of OPzS Block batteries
  3. Construction of OPzS Classic cells
  4. Dimensions and technical data

Publication details

Authors
BATER
Publisher
BATER
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

BATER BATER OPzS stationary batteries: technical data: OPzS Block / 6x1-OPzS-50. BATER. https://baterbattery.com/product/bater-lead-acid-batteries-opzs-block-type-for-standby-application/

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.