Technical guideFree to readYear not stated

Cospowers short-duration UPS backup: model parameters: Short-duration backup / CFS512120U

Cospowers

A Cospowers product page for the CFS512120U immersion-cooled LFP battery cabinet for data-centre UPS backup: 512 Vdc nominal, 120 Ah / 61.44 kWh, 600 A continuous discharge at 5C and 275 kW for 12 minutes from a single cluster.

On this page

Overview

The page sits in the short-term power backup series of the data-centre energy storage range of Cospowers, based in Dongying in China's Shandong province. The CFS512120U is a battery cabinet in which lithium iron phosphate (LFP) cells are fully immersed in liquid. The manufacturer states that immersion isolates the cells from oxygen and protects against fire, explosion and smoke. The temperature difference between cells is 2 °C or less, and the manufacturer claims that the thermal management raises system efficiency by 3%.

Basic parameters: nominal voltage 512 Vdc, rated charging voltage 560 Vdc, nominal capacity 120 Ah (61.44 kWh). Standard discharge current is 120 A (1C) and maximum continuous discharge current is 600 A (5C). Standard charging current is 60 A (0.5C) and maximum charging current is 120 A (1C). Cycle life is 3000 cycles at 80% depth of discharge and 0.5C/0.5C. Self-discharge is at most 3% over three months at 0 to 30 °C. The cabinet measures 600 x 1200 x 2300 mm.

The specification table separates cell, module and cluster levels. A single cell is 60 Ah (1C), 3.2 Vdc nominal, with a 2.5 to 3.6 Vdc operating range and 1.71 kg. The module is a 2P20S arrangement: 120 Ah, 64 Vdc, 56 to 72 Vdc and 92 kg. The cluster is 2P160S: 120 Ah, a 448 to 560 Vdc operating range and 1100 kg. The cluster row lists a nominal voltage of 215 Vdc, whereas the basic parameters and the 160-series cell arrangement give 512 Vdc.

The single-cluster performance data has three discharge points: 275 kW and 600 A for 12 minutes, 222 kW and 480 A for 15 minutes, and 167 kW and 360 A for 20 minutes. Operating ambient temperature is 0 to 45 °C, storage -20 to 45 °C, transport -20 to 60 °C, relative humidity 5% to 95% and altitude at most 2000 metres. Communication is by CAN, RS485 and dry contact. The system suits different UPS models through two-wire or three-wire DC connection. The page does not state certifications or the type of immersion fluid.

Key points

  1. CFS512120U: immersion-cooled battery cabinet with LFP cells; 512 Vdc nominal, 560 Vdc rated charging voltage, 120 Ah / 61.44 kWh.
  2. Discharge: 120 A standard (1C), 600 A maximum continuous (5C). Charge: 60 A standard (0.5C), 120 A maximum (1C).
  3. Single-cluster performance: 275 kW for 12 minutes (600 A), 222 kW for 15 minutes (480 A), 167 kW for 20 minutes (360 A).
  4. Cell: 60 Ah, 3.2 Vdc, 2.5...3.6 Vdc, 1.71 kg. Module (2P20S): 120 Ah, 64 Vdc, 56...72 Vdc, 92 kg.
  5. Cluster (2P160S): 120 Ah, operating range 448...560 Vdc, 1100 kg; cabinet 600 x 1200 x 2300 mm.
  6. The cluster row lists a nominal voltage of 215 Vdc; the product nominal voltage is 512 Vdc.
  7. Cycle life: 3000 cycles at 80% DOD, 0.5C/0.5C; self-discharge at most 3% in 3 months at 0...30 °C.
  8. Environment: operating 0...45 °C, storage -20...45 °C, relative humidity 5...95%, altitude up to 2000 m.
  9. Cell-to-cell temperature difference at most 2 °C; communication by CAN, RS485 and dry contact.

Using it in design

  • Match the UPS load and target autonomy to the single-cluster table: 275 kW at 12 minutes, 222 kW at 15 minutes, 167 kW at 20 minutes; derive the cluster count for larger loads from these values.
  • Compare the UPS DC bus window with the 448...560 Vdc operating range and the 560 Vdc charging voltage.
  • Size DC cables and protective devices for the 600 A continuous discharge current per cluster.
  • Use the 1100 kg cluster weight on a 600 x 1200 mm footprint for floor loading, and confirm total cabinet weight with the manufacturer.
  • Calculate recharge time from the 60 A standard and 120 A maximum charging currents and compare it with the UPS charger capacity.
  • Obtain the immersion fluid type, leak containment measures and certifications from the manufacturer in writing and include them in the fire safety assessment.

Who should read it

Electrical designers selecting lithium-ion energy storage for data-centre UPS systems, engineers planning battery rooms, and fire safety specialists.

Document contents

  1. Product features
  2. Basic Parameters
  3. Environment
  4. Specification Parameters: Cell, Battery Module, Battery Cluster
  5. Single Cluster Performance Data
  6. Specification Download

Publication details

Authors
Cospowers
Publisher
Cospowers
Year
Year not stated
Document language
Unverified
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Cospowers Cospowers short-duration UPS backup: model parameters: Short-duration backup / CFS512120U. Cospowers. https://en.cospowers.com/products/info/97/1366.html

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.