Cospowers short-duration UPS backup: model parameters: CFC UPS backup / CFC64100U

Cospowers

A Cospowers product page for the CFC512300U containerised short-duration backup system for data centres: 512 Vdc nominal, 300 Ah, 153.6 kWh rated energy and a maximum continuous discharge current of 1500 A, built from 64 Vdc 100 Ah CFC64100U battery cabinets.

On this page

Overview

The page sits in the short-term power backup series of the data-centre energy storage range of Cospowers, based in Dongying in China's Shandong province. The CFC512300U is an integrated solution that combines the UPS host, battery pack, distribution cabinet, monitoring and security systems in one cabin. The manufacturer states that this reduces on-site installation and commissioning work, that UPS capacity and battery autonomy can be configured to user needs, and that the compact structure eases transport and hoisting.

The parameter table is organised on four levels. The lowest is the CFC64100U battery cabinet: 64 Vdc rated voltage, a 56 to 70 Vdc range, 100 Ah, 440 x 630 x 182 mm and 110 kg. The second is the CB5-600S03 control cabinet rated 600 A (440 x 600 x 310 mm, 50 kg). The third is the CFC512100U battery cluster: 512 Vdc nominal, a 448 to 560 Vdc operating range, 100 Ah, 51.2 kWh, 600 x 800 x 2200 mm and 810 kg.

At system level the CFC512300U carries values equal to three clusters: 512 Vdc, 300 Ah, 153.6 kWh, a standard charging current of 150 A, a standard discharging current of 300 A and a maximum continuous discharging current of 1500 A. The container measures 2991 x 2438 x 2896 mm and weighs 7 tonnes. At cluster level, standard charging current is 50 A, standard discharging current 100 A and maximum continuous discharging current 600 A. The table gives a standard charging current; it lists no separate maximum charging current.

Operating temperature is 0 to 45 °C and cycle life is 3000 cycles at 80% depth of discharge and 0.5C/0.5C. Communication is by CAN, RS485 and dry contact; protection functions cover over-temperature, over-current, short circuit, over-charge and over-discharge. The cluster is monitored on a 7-inch LCD touch screen and the system on a 10-inch one, and the system has four-level security protection. The page does not state the cell chemistry, constant-power discharge durations, fire suppression details or certifications.

Key points

  1. CFC64100U battery cabinet: 64 Vdc, 56...70 Vdc, 100 Ah; standard charge 50 A, standard discharge 100 A, maximum continuous discharge 600 A; 440 x 630 x 182 mm; 110 kg.
  2. CB5-600S03 control cabinet: 600 A; 440 x 600 x 310 mm; 50 kg.
  3. CFC512100U battery cluster: 512 Vdc nominal, 448...560 Vdc, 100 Ah, 51.2 kWh; 600 x 800 x 2200 mm; 810 kg.
  4. CFC512300U system: 512 Vdc, 300 Ah, 153.6 kWh; standard charge 150 A, standard discharge 300 A, maximum continuous discharge 1500 A.
  5. System container 2991 x 2438 x 2896 mm and 7 t.
  6. Cycle life: 3000 cycles at 80% DOD and 0.5C/0.5C; operating temperature 0...45 °C.
  7. Communication: CAN, RS485, dry contact; 7-inch cluster screen, 10-inch system screen.
  8. The system integrates the UPS host, battery, distribution cabinet, monitoring and security systems in one cabin.

Using it in design

  • Compare the UPS DC bus window with the cluster's 448...560 Vdc operating range; the end-of-discharge voltage must not fall below 448 V.
  • Check the required discharge current against the continuous limits of 1500 A for the system and 600 A per cluster, and size DC cables and protective devices for that current.
  • In the site plan verify the 2991 x 2438 x 2896 mm container footprint, the 7 t weight, foundation loading and crane access.
  • Keep cabinet, cluster and system values as separate levels in the catalogue entry, and do not use the standard charging current as a maximum.
  • Compare the 0...45 °C operating range with the site climate, and obtain the cell chemistry and fire detection and suppression details from the manufacturer in writing.
  • Map the CAN or RS485 interface to the UPS and to the building monitoring system (BMS/DCIM).

Who should read it

Electrical designers selecting UPS energy storage for containerised or modular data centres, and engineers planning site layout.

Document contents

  1. Product features
  2. Basic Parameters: Battery Cabinet Parameters
  3. Basic Parameters: Control Cabinet Parameters
  4. Basic Parameters: Battery Cluster Parameters
  5. Basic Parameters: System-Level Parameters
  6. Specification Download

Publication details

Authors
Cospowers
Publisher
Cospowers
Year
Year not stated
Document language
Unverified
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Cospowers Cospowers short-duration UPS backup: model parameters: CFC UPS backup / CFC64100U. Cospowers. https://en.cospowers.com/products/info/97/1367.html

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.