DSPM Power Lynx 3 datasheet 083-0036-01 Rev. D
Original title DSPM Power Lynx 3 datasheet 083-0036-01 Rev. D, PDF p.2
DSPM
A two-page datasheet, number 083-0036-01 Rev. D, from US manufacturer DSPM describing six models of the Power Lynx 3 (PLX3) three-phase online UPS family: 15, 30, 50, 75, 100 and 125 kVA (12-100 kW at power factor 0.8), efficiency above 92% and UL 924 and UL 1778 listing.
On this page
Overview
The sheet presents the Power Lynx 3 series from DSPM of Ontario, California, as a specification submittal page with catalogue number, project and signature fields at the top. The series is an always-on (online) UPS built from a rectifier, a DSP/PWM-controlled inverter, a static bypass and a maintenance bypass switch, and it supplies the load without interruption when the utility fails. The output sine wave is generated by high-frequency PWM and an output transformer isolates the critical load from source noise.
The table on the second page gives six ratings in kVA and kW: 15/12, 30/24, 50/40, 75/60, 100/80 and 125/100. At each rating the kW value is 0.8 times the kVA. Input can be 208Y/120, 480Y/277, 208 or 480 VAC; output is 208Y/120 or 480Y/277 VAC regulated to ±2%. The UPS cabinet is 42 x 71 x 22.5 in for 15-75 kVA and 50 x 71 x 32 in for 100 and 125 kVA. No separate battery cabinet is required at 15 and 30 kVA; from 50 kVA upward a 42 x 71 x 22.5 in battery cabinet is added.
Batteries are sealed, maintenance-free lead calcium (AGM); temperature-compensated battery monitoring and microprocessor-controlled recharge are standard. The ordering code is built from family, kVA, input and output voltage, options and runtime in minutes. Runtime choices are 10, 15, 20, 25, 30, 45, 60, 120 and 180 minutes. Options include a remote indicator panel, Form C contacts, an SNMP card, output circuit breakers, a seismic-rated bracket and an external maintenance bypass switch.
The product is listed to UL 924 (emergency lighting and power equipment) and UL 1778 (UPS) and complies with the Buy American Act, which places the series in the North American building and emergency power market. Surge withstand is defined against ANSI/IEEE C62.45 categories A and B. Weights are given as combined totals in pounds, from 1750 lb to 4150 lb. The sheet notes that special voltages may change the weight, size and number of cabinets.
Key points
- Models: PLX3 15 kVA / 12 kW, 30 / 24, 50 / 40, 75 / 60, 100 / 80 and 125 kVA / 100 kW.
- Input: 208Y/120, 480Y/277, 208 or 480 VAC; output: 208Y/120 or 480Y/277 VAC, ±2%.
- Efficiency is above 92%.
- UPS cabinet: 42 x 71 x 22.5 in (WxHxD) for 15-75 kVA, 50 x 71 x 32 in for 100-125 kVA.
- Battery cabinet: not required at 15 and 30 kVA; 42 x 71 x 22.5 in for 50-125 kVA.
- Combined weight: 1750, 2200, 2780, 3200, 3700 and 4150 lb (from 15 to 125 kVA).
- Runtime options: 10, 15, 20, 25, 30, 45, 60, 120 and 180 minutes.
- Codes: UL 924 and UL 1778; surge protection per ANSI/IEEE C62.45 categories A and B.
- Warranty: 1 year full on electronics, 1 year full plus 9 years pro-rated on batteries, 5 years on the powertrain.
Using it in design
- With a 0.8 power factor, compare the IT load against the kW column: a 100 kW load needs the 125 kVA model.
- On North American projects, select the input and output voltage combination (for example 480 in, 208Y/120 out) in the ordering code, and assess the need for a separate PDU transformer in light of the standard output transformer.
- In the layout, allow for a 42 in wide battery cabinet alongside the UPS cabinet from 50 kVA upward, and confirm the cabinet count with the manufacturer for long runtimes.
- Check floor loading with the combined weight: the 125 kVA system weighs 4150 lb (about 1880 kg).
- Use the 92% efficiency floor for the heat load; at 100 kW output the losses reach about 8.7 kW.
- In seismic zones add the SRB seismic bracket option to the specification, and the SNMP or Form C contact option for remote monitoring.
Who should read it
Electrical designers selecting a 15-125 kVA UPS at North American voltages and engineers writing specifications for emergency power and small data room projects.
Document contents
- Specifications
- Power Rating
- Input
- Output
- Batteries
- Codes
- Protection
- Diagnostics and Maintenance
- Cabinet
- Installation
- Warranty
- Model table
- Ordering Information
- Notes
Publication details
- Authors
- DSPM
- Publisher
- DSPM
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
DSPM DSPM Power Lynx 3 datasheet 083-0036-01 Rev. D, PDF p.2. DSPM. https://dspowerm.co/downloads/uninterruptible_power_systems_indoor_three_Data_Sheet.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.